Seismic Bracing
<br /> TOLCO"' Fig. 980 - Universal Swivel Sway Brace Attachment - 3/8" to 3/4" (UL Listed)
<br /> Size Range: One size fits bracing pipe 1" (25mm)thru 2" (5omm), B-Line series OPM C&US
<br /> 12 gauge (2.6mm)channel, and all structural steel up to 1/4" (31.7mm)thick. LISTED
<br /> Material: Steel
<br /> Function: Multi-functional attachment to structure or braced pipe fitting.
<br /> Features: This product's design incorporates a concentric attachment >_,�
<br /> opening which is critical to the performance of structural seismic connections.
<br /> NFPA 13 (2016) 9.3.5.8.4 indicates clearly that fastener table load values are D
<br /> based only on concentric loading. Mounts to any surface angle. Break off bolt
<br /> head assures verification of proper installation. \
<br /> Installation: Fig.980 is the structural or transitional attachment component A >
<br /> of a longitudinal or lateral sway brace assembly. It is intended to be combined
<br /> with the "bracing pipe"and TOLCO"braced pipe"attachment, Fig. 1000, 1001,
<br /> 2002, 3000, 4L, 4LA,4A or approved attachment to pipe to form a complete Set Bolt
<br /> bracing assembly. NFPA 13 guidelines should be followed. Included
<br /> Mounting Hardware
<br /> To Install: Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until Is Not Included
<br /> the head breaks off.Attachment can pivot for adjustment to proper brace angle.
<br /> Approvals:—Underwriters Laboratories Listed in the USA(UL)and
<br /> Canada (cUL). Included in our Seismic Engineering Guidelines approved by the
<br /> State of California Office of Statewide Health Planning and Development
<br /> (OSHPD). For additional load, spacing and placement information relating to
<br /> OSHPD projects, please refer to our Seismic Engineering Guidelines, l
<br /> OPM-0052-13.
<br /> For FM Approval information refer to FM Approved page 61.
<br /> Note: Fig. 980 Swivel Attachment and Fig. 1001, 1000, 2002, 4A, 4L,4LA, or
<br /> approved attachment to pipe that make up a sway brace system of UL Listed
<br /> attachments and bracing materials which satisfies the requirements of
<br /> Underwriters Laboratories and the National Fire Protection Association (NFPA)
<br /> Finish: Plain, Electro-Galvanized or Stainless Steel. r-7,,
<br /> Contact customer service for alternative finishes.
<br /> Fig.1001
<br /> Order By: Figure number and finish.
<br /> .980
<br /> Fig.980
<br /> Pat.#6,273,372, Pat.#6,517,030,Pat.#6,953,174,Pat.#6,708,930, Pat.#7,191,987, Pat.#7,441,730,
<br /> Pat.#7,669,806 + Brace Lateral Brace Brace
<br /> Fig.413
<br /> shown
<br /> Part Mtg.Hdw. Mounting Hole Max.Design Approx.
<br /> Number Size A B D Load(cULus) Wt./100
<br /> in. (mm) in. (mm) in. (mm) in. (mm) in. Win) lbs. (kg)
<br /> 980-3/8 3/8- (9.5) 51/4" (133.3) 17/8" (47.6) 13/32" (10.3) 2015 (8.96) 149 (67.6)
<br /> 980-1/2* 1/2- (12.7) 51/4" (133.3) 17/8" (47.6) 17/32" (13.5) 2015 (8.96) 148 (67.1)
<br /> 980-5/8 5/8- (15.9) 51/4" (133.3) 17/8- (47.6) 11/16- (17.5) 2015 (8.96) 147 (66.7)
<br /> 980-3/4 3/4" (19.0) 51/4" (133.3) 17/8" (47.6) 13/16- (20.5) 2015 (8.96) 146 (66.2)
<br /> * Standard size.
<br /> Important! - For load information when using Fig. 980 with pre-installed or post-installed concrete anchors in
<br /> compliance with NFPA 13 (2016) or ASCE 7-10, including prying factors,see load tables on pages AL-1 thru AL-21.
<br /> Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
<br /> resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
<br /> provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
<br /> exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
<br /> combined with products not provided by Eaton.
<br /> All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified.
<br /> Eaton 60 B-Line series Fire Protection Solutions
<br />
|