Laserfiche WebLink
� rt e st <br /> Roof Top Unit <br /> PROJECT: Kaiser Permanente EMCE DATE: 2/15/2024 <br /> LOCATION: Everett,WA CONTACT: Shane Moore <br /> PROJECT#: 230035 AUTHOR: Adam Hoskins <br /> SYSTEM/UNIT: RTU-01 Tested By: Shane Moore <br /> AREA: Level 1 Date: 11/21/2023 <br /> .. . Air Test Data <br /> Unit Manufacturer Daikin Design Actual <br /> Unit Model Number RPS130D Total CFM 41000 CFM <br /> Return CFM 36000 CFM <br /> RTU-01 Return Inlet Summary <br /> Area Served Outlet Size LxW Design <br /> Inlet-001 Exam 9 RG 8 RD 175 135 150 86 <br /> Inlet-002 Exam 10 RG 8 RD 180 160 160 89 <br /> Inlet-003 Exam 11 RG 8 RD 175 150 165 94 <br /> Inlet-004 Exam 12 RG 8 RD 190 170 175 92 <br /> Inlet-005 Hallway RG 12 RD 340 295 320 94 <br /> Inlet-006 Exam 13 RG 8 RD 160 140 145 91 <br /> Inlet-007 Exam 14 RG 8 RD 160 130 145 91 <br /> Inlet-008 Exam 15 RG 8 RD 160 130 145 91 <br /> Inlet-009 Exam 16 RG 8 RD 140 130 140 100 <br /> Inlet-010 Hallway RG 14 RD 410 325 370 90 <br /> Inlet-011 Hallway RG 14 RD 485 430 445 1 92 <br /> Inlet-012 Hallway RG 10 RD 235 210 190 81 <br /> Inlet-013 Med Prep 2 RG 10 RD 205 200 245 120 <br /> Inlet-014 Work Room 2 RG 8 RD 180 155 165 92 <br /> Inlet-015 Exam 8 RG 8 RD 175 100 155 89 <br /> Inlet-016 Exam 7 RG 8 RD 130 130 120 92 <br /> Inlet-017 Exam 6 RG 8 RD 130 110 1 120 92 <br /> Inlet-018 Exam 5 RG 8 RD 130 95 120 92 <br /> Inlet-019 Hallway RG 10 RD 245 190 220 90 <br /> Inlet-020 Hallway RG 10 RD 245 225 240 98 <br /> Inlet-021 Hallway RG 6 RD 245 95 100 41 <br /> Inlet-022 1822 Office RG 8 RD 110 110 100 91 <br /> Inlet-023 Med Prep 1 RG 8 RD 205 180 1 185 90 <br /> Inlet-024 Nutrition RG 10 RD 285 250 265 93 <br /> Inlet-025 1844 Procedure RG 12 RD 305 250 275 90 <br /> Inlet-026 Hallway RG 10 RD 245 200 225 92 <br /> Inlet-027 Exam 2 RG 8 RD 130 125 115 1 88 <br /> Inlet-028 Work Room 1 RG 8 RD 130 120 120 92 <br /> Inlet-029 Lobby RG 12 RD 320 300 300 94 <br /> Inlet-030 Lobby RG 12 RD 400 400 370 93 <br /> Inlet-031 Lobby RG 12 RD 400 415 370 93 <br /> Inlet-032 Reception RG 8 RD 155 125 140 90 <br /> Inlet-033 Cafe RG 12 RD 390 365 1 370 95 <br /> Inlet-034 Cafe Seating RG 14 RD 505 455 465 92 <br /> Inlet-035 Cafe Seating RG 14 RD 500 420 470 94 <br /> Inlet-036 Lobby RG 15 RD 1040 705 960 92 <br /> Inlet-037 Storage RG 8 RD 100 0 100 100 <br /> Inlet-038 Lobby Entrance RG 15 RD 565 425 525 93 <br /> Inlet-039 Elevator Lobby RG 14 RD 430 390 1 415 97 <br /> Inlet-040 Elevator Lobby RG 14 RD 430 375 415 97 <br /> Inlet-041 Waiting Area RG 14 RD 590 520 540 92 <br /> Inlet-042 Waiting Area RG 14 RD 420 365 370 88 <br /> Inlet-043 Waiting Area RG 14 RD 420 370 375 1 89 <br /> Inlet-044 Waiting Area RG 14 RD 630 1 560 585 93 <br /> Airtest Co. LLC <br /> Preliminary TAB Report <br />