Laserfiche WebLink
,A. i <br /> Roof Top Unit <br /> PROJECT: Kaiser Permanente EMCE DATE: 2/15/2024 <br /> LOCATION: Everett,WA CONTACT: Shane Moore <br /> PROJECT#: 230035 AUTHOR: Adam Hoskins <br /> SYSTEM/UNIT: RTU-01/VAV-1-1-03 w Tested By: Hayden Lindsay <br /> AREA: 1812 Office Date: 1/16/2024 <br /> ini�� Unit .. . Data <br /> Manufacturer Titus Design Primary Max CFM 150 CFM <br /> Model Number DESV Actual Max Primary CFM 160 CFM <br /> Controls System Siemens Design Primary Min.CFM 90 CFM <br /> VAV Type Shut-Off Actual Primary Min.CFM 95 CFM <br /> Box Inlet Size 6 RD <br /> K Factor 0.56 <br /> RTU-01/VAV-1-1-03 w Supply Outlet Summary <br /> Atem/UAIL Area Served Outlet Size LxW Design Prelim Final %Final <br /> Type D CFM Reading Reading <br /> Outlet-01 1812 Office CD 6 RD 50 50 55 110 <br /> Outlet-02 1813 Office CD 6 RD 50 55 50 100 <br /> Outlet-03 1814 Office CD 6 RD 50 50 55 110 <br /> RTU-01/VAV-1-1-03 w Autoflow Valve Summary <br /> .. ,. <br /> Autoflow Valve- Heating Water Griswold MCK21RIR1 FH 0.500.5 2-32 1 10.00 <br /> 01 <br /> SYSTEM/UNIT: RTU-01/VAV-1-1-04 SWD w Tested By: Hayden Lindsay <br /> Date: 1/31/2024 <br /> Unit Data <br /> Manufacturer Titus Design Primary Max CFM 555 CFM <br /> Model Number DESV Design Primary Min.CFM 115 CFM <br /> Controls System Siemens <br /> VAV Type Shut-Off <br /> Box Inlet Size 8 RD <br /> RTU-01/VAV-1-1-04 SWD w Autoflow Valve Summary <br /> .- .- <br /> EW <br /> Autofl!VIv,- Heating Water Griswold MCK21RIR1 FH 0.50 0.55 2-32 12.00 <br /> Airtest Co. LLC <br /> Preliminary TAB Report <br />