INITIAL CONDUCTOR FINAL CONDUCTOR #OF CURRENT-CARRYING TERM.CONDUIT FILL TEMP.CORR. CONDUIT CONT. MAX. BASE DEBATED VOLTAGE <br /> ID TYPICAL LOCATION LOCATION CONDUCTOR CONDUIT PARALLEL CONDUCTORS IN PERCENT OCPD EGC FACTOR FILL FACTOR CURRENT CURRENT AMP. AMP. TEMP. LENGTH DROP <br /> CIRCUITS CONDUIT RATING <br /> 1 2 ARRAY JUNCTION BOX 12 AWG Q CABLE 1 2 N/A N/A 6 AWG BARE 0.82 (48°C) N/A 12.OA 15.OA NIA N/A 90°C 63FT 0.55% <br /> COPPER <br /> 2 1 JUNCTION BOX IQ COMBINER BOX 12 AWG THHN-2 COPPER MIN 0.75"Dia EMT 2 4 10.43% 15A 8 AWG THWN-2, 1.0 (26°C) 0.8 12.OA 15.OA 30A 24.OA 90°C 30FT 0.62% <br /> COPPER <br /> 3 1 IQ COMBINER BOX FUSED AC 10 AWG THHN-2 COPPER MIN 0.75"Dia EMT 1 3 15.27% 30A 8 AWG THWN-2, 1.0 (26°C) 1 24.OA 30.OA 40A 40.OA 90°C 5FT 0.13% <br /> DISCONNECT COPPER <br /> 4 1 FUSED AC MSP 6 AWG THHN-2 COPPER MIN 0.75"Dia EMT 1 3 36.53% N/A 8 AWG THWN-2, 1.0 (26°C) 1 24.OA 30.OA 75A 75.OA 90°C 5FT 0.05% <br /> DISCONNECT COPPER <br /> SYSTEM INFO. <br /> (24)HANWHA Q CELL <br /> (Q.PEAK DUO-G8+340W) <br /> (24)ENPHASE IQ7-60-2-US(240V) <br /> DC SYSTEM SIZE:8.16 KWDC <br /> AC SYSTEM SIZE:6.00 KWAC <br /> TO UTILITY GRID REVISIONS <br /> DESCRIPTION DATE REV <br /> �Ll L2 N <br /> BRANCH 1 BI-DIRECTIONAL UTILITY <br /> 12- HANWHA Q CELL (Q.PEAK DUO-G8+ 340W) MODULES Oo METER#24 089 857 <br /> POINT OF 1-PH,3-W, 120V/240V Signature with Seal <br /> INTERCONNECTION <br /> SUPPLY SIDE TAP a L2 N <br /> • • • <br /> E MAIN BREAKER T <br /> HOUSE 240 V,20OA/2P <br /> DATE:08/10/2021 <br /> (E)MAIN SERVICE PROJECT NAME&ADDRESS <br /> Q CABLE JUNCTION BOX L1 L1 PANEL,200A RATED, <br /> 600 V, NEMA 3R, 2 Li L2 N Lz Lz <br /> 1-PH,3-W,240V <br /> AV � 1 UL LISTED ENVOY 240V, 30A FUSED L1 L1 <br /> 10A/2P NEMA 3R, UL LISTED <br /> 15A/2P Lz Lz <br /> I­EG <br /> (2)30A FUSES <br /> Li L1 L1 L1 <br /> BRANCH 2 15A/2P L2 L2 L2 L2 0 <br /> 12- HANWHA Q CELL (Q.PEAK DUO-G8+ 340W) MODULES --- - G x DN------EN 0 <br /> --- G — LL]� o � <br /> .---- G -- - N J LL 04 04 O <br /> J rn <br /> I 3 4 c O U J a <br /> 0 <br /> . . . Lam_ of LLU LU d7 <br /> (N) ENPHASE IQ o_ H10 <br /> Lo <br /> COMBINER 3 z (n J w p <br /> I (X-IQ-AM1-240-3) EXISTING GROUND Q w � � , , <br /> ELECTRODE CONDUCTOR LLI <br /> ti ti ti D ~ w z <br /> J U) 0- <br /> Q <br /> (24)ENPHASE IQ7-60-2-US(240V)MICROINVERTERS <br /> SHEET NAME <br /> SERVICE INFO. ELECTRICAL LINE <br /> & CALCS. <br /> AHJ NAME: CITY OF EVERETT <br /> UTILITY PROVIDER: SNOPUD SHEET SIZE <br /> MAIN PANEL BRAND: EATON ANSI B <br /> MAIN SERVICE VOLTAGE: 240V <br /> MAIN SERVICE PANEL: 200A 11" X 17" <br /> MAIN BREAKER RATING: 200A SHEET NUMBER <br /> 1 ELECTRICAL LINE DIAGRAM MAIN SERVICE LOCATION: EAST <br /> PV-4 SCALE: NTS SERVICE FEED SOURCE: OVERHEAD PV_4 <br />