PROJECT NOTES
<br />ELECTRICAL LEGEND
<br />1. GENERAL: WORK SHALL BE DONE IN ACCORDANCE WITH CODES
<br />AS ADOPTED BY THE CITY OF EVERETT, SNOHOMISH COUNTY,
<br />AND THE STATE OF WASHINGTON.
<br />2. LOCATIONS OF ELECTRICAL DEVICES, LIGHTING FIXTURES, ETC.,
<br />INDICATED ON CIVIL / STRUCTURAL PLANS - INCLUDING
<br />SECTIONS, ELEVATIONS, NOTES, OR OTHER INDICATORS - TAKE
<br />PRECEDENCE OVER LOCATIONS SHOWN ON ELECTRICAL
<br />DRAWINGS.
<br />3. REFER TO CIVIL, STRUCTURAL, MECHANICAL, ETC., DRAWINGS
<br />FOR WORK IN OTHER DIVISIONS. INFORMATION CONVEYED
<br />WITHIN THE ELECTRICAL DRAWINGS ILLUSTRATING OR
<br />REFERENCING WORK OF OTHER DIVISIONS IS FOR REFERENCE
<br />ONLY. SPECIFICATION BYTHE APPROPRIATE DIVISIONS SHALL
<br />APPLY.
<br />4. GENERAL NOTES ARE SHOWN ON SHEETS MOST RELEVANT TO
<br />SPECIFIC NOTE; HOWEVER, GENERAL NOTES ON EACH SHEET
<br />SHALL APPLY IN PRACTICE TO ALL ELECTRICAL DRAWINGS.
<br />5. NOT ALL COMPONENTS OF THE ELECTRICAL SYSTEMS ARE
<br />SHOWN (FOR SIMPLICITY). PROVIDE MATERIALS AND LABOR
<br />NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM.
<br />6. STAINLESS STEEL HARDWARE: MATERIALS USED FOR THE
<br />MOUNTING AND SUPPORT OF BOXES CABLES, RACEWAYS, LIGHT
<br />FIXTURES, OUTLETS, AND OTHER ELECTRICAL EQUIPMENT, SHALL
<br />BE 316 STAINLESS STEEL. THIS REQUIREMENT APPLIES TO THE
<br />AFOREMENTIONED COMPONENTS WHEN INSTALLED OUTSIDE
<br />ABOVE GRADE OR WHEN INSTALLED OVER WATER (APPROACH
<br />PIER, PIER, & FLOATING DOCKS).
<br />7. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. EXACT LOCATIONS
<br />OF ELECTRICAL EQUIPMENT ARE APPROXIMATE. CHANGES MADE
<br />BY THE OWNER IN LOCATING ELECTRCAL COMPONENTS OF UP
<br />TO TEN FEET HORIZONTALLY IS A PART OF THIS CONTRACT FOR
<br />FLOATS. THESE CHANGES MAY BE IMPLEMENTED, AT NO CHARGE
<br />TO THE OWNER, UNTIL FINAL APPROVAL OF SHOP DRAWINGS.
<br />8. COORDINATE LOCATIONS OF ELECTRICAL AND COMMUNICATION
<br />CHASES AND CONDUITS WITH OTHER TRADES. ADJUST
<br />LOCATIONS AS NECESSARY TO AVIOD CONFLICTS.
<br />A,AMP AMPERES EF
<br />AF AMPERE RATED FUSES EMT
<br />(RATED)
<br />Lv AFF ABOVE FINISHEDFLOOR ENCL
<br />AEG ABOVE
<br />LUMINUM(ALLO GRADE FOIL
<br />AL ALUMINUM (ALLOY) EPA
<br />o ALC AUTOMATEDLIGHTING
<br />SWITCH
<br />CONTROL EWC
<br />� AS AMPERE (RATED)SWITCH EWH
<br />ATS AUTOMATIC TRANSFER SWTCH FA
<br />AUTO AUTOMATIC FAA
<br />AUX AUXILIARY FC
<br />AWG AMERICAN WIREGAUGE FL
<br />BAT BATTERY FLEX
<br />o BFG BELOW FINISIT ED GRADE FU
<br />C CONDUIT (CIRCULAR RACEWAY) GEN
<br />o CAB CABINET PC
<br />CB CIRCUIT BREAKER
<br />CFM CUBIC FEET PER MINUTE AND
<br />U GOT CIRCUIT ABC
<br />w CLG CEILING GRID
<br />CO CONDUIT ONLY HP
<br />d CT CURRENT TRANSFORMER HE
<br />CU COPPER AS
<br />r` DC DIRECT CURRENT ID
<br />DISC DISCONNECT IG
<br />CD DIA DIAMETER IN
<br />cs
<br />w N DIV DIVISION ISO
<br />/ DP DISTRIBUTION PANEL K
<br />T% DPDT DOUBLE POLE DOUBLETHROW KCM
<br />o r DPST DOUBLE POLE SINGLETHROW KO
<br />DWG DRAWING KW
<br />Eor(E) EXISTING LOA
<br />� t4
<br />AS&::�BOR POWER
<br />E E R 5, IN(.
<br />E
<br />I PM: ED DAVID, PE TEL: 205.855.4600
<br />0 U U
<br />Co
<br />J
<br />/
<br />�o
<br />Port of
<br />00
<br />"'
<br />W,
<br />EVERETT
<br />O Y
<br />N
<br />P.O. BOX 538
<br />EVERETT, WA 98205
<br />o / (425) 259-3164
<br />2 U
<br />9. SCOPE OF WORK: THE SCOPE OF ELECTRICAL WORK FOR THIS
<br />PROJECT INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING:
<br />A. FURNISH AND INSTALL POWER, LIGHTING, AND
<br />COMMUNICATIONS, SYSTEMS FOR FUEL DOCK, INCLUDING
<br />SHORE POWER PEDESTALS. SCOPE INCLUDES THE
<br />INSTALLATION AND CONNECTION OF SHORE POWER PEDESTALS
<br />ON EXISTING FUEL DOCK (EXISTING FUEL DOCK DISPENSING
<br />SYSTEM TO BE REMOVED). PROVIDE COMMUNICATIONS WIRING
<br />AS SPECIFIED, INCLUDING RACEWAYS FROM DATA OUTLETS TO
<br />DATA J-BOXES OR RACKS. CONNECT THE FOLLOWING SYSTEMS
<br />PER DRAWINGS OR MANUFACTURERS REQUIREMENTS:
<br />A.A. FUEL SYSTEM CONTROLS; INTERCONNECT DISPENSING
<br />CONTROL SYSTEM TO (E) UPLAND FUEL PUMP CONTROL
<br />PANEL.
<br />A.B. LEAK DETECTION SYSTEM
<br />A.C. POINT OF SALE (POS) SYSTEM
<br />A.D. FIRE ALARM SYSTEM WITH RADIO TRANSPONDER.
<br />A. E. LIGHTING CONTROL SYSTEM WITH HUBBELL WISCAPE.
<br />A.F. SECURITY SYSTEM CABLING (EQUIPMENT BY OTHERS).
<br />A.G. PORT NETWORKWIRING, INCLUDING FIBER OPTIC
<br />CABLING AND CATEGORY WIRE. PROVIDE WALL
<br />MOUNTED DATA RACK AND 5-FOOT PLUG -STRIP.
<br />A.H. EPO SYSTEM WIRING; CONNECT TO (E) UPLAND EPO.
<br />B. PERMITS: GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS
<br />AND PAY ALL GOVERNMENT TAXES, FEES AND OTHER COSTS IN
<br />CONNECTION WITH THIS WORK. OBTAIN ALL REQUIRED
<br />CERTIFICATES OF INSPECTION OF THE WORK AND DELIVER
<br />SAME TO THE ENGINEER AT THE TIME OF SUBSTANTIAL
<br />COMPLETION AND BEFORE REQUEST FOR FINAL PAYMENT.
<br />C. PHASING: PHASED INSTALLATION OF THE ELECTRICAL SERVICE
<br />EQUIPMENT IS REQUIRED. ELECTRICAL OUTAGES REQUIRED
<br />FOR THE EXECUTION OF THIS WORK SHALL BE LIMITED TO (2)
<br />8-HOUR PERIODS DURING DAYLIGHT HOURS. SCHEDULE
<br />OUTAGES WITH OWNER A MINIMUM OF 72 HOURS IN ADVANCE.
<br />PROVIDE CODE COMPLIANT TEMPORARY CONNECTIONS AND
<br />SERVICES AS NEEDED FOR CONSTRUCTION; INCLUDING
<br />SERVICES TO PORTABLE TRAILERS, POWER TOOLS, AND OTHER
<br />EQUIPMENT, USED FOR CONSTRUCTION.
<br />D. DEMOLITION: SEE OTHER DIVISIONS FOR SCOPE OF DEMOLITION
<br />WORK. REMOVE ELECTRICAL AND COMMUNICATIONS SYSTEMS
<br />THAT EXIST IN DEMOLISHED AREAS. MAKE SYSTEMS SAFE, SEAL
<br />OPENINGS, AND UPDATED SIGNAGE/SCHEDULES. FINAL
<br />CONFIGURATION SHALL COMPLY WITH CURRENT CODE.
<br />E. COORDINATION WITH FLOAT FABRICATOR: THE CONTRACTOR
<br />SHALL COORDINATE ELECTRICAL, EQUIPMENT, CHASE, AND
<br />JUNCTION BOX LOCATIONS WITH THE FLOAT MANUFACTURER.
<br />VERIFY PROVISIONS FOR EQUIPMENT ANCHORING, AND THAT
<br />CHASES AND JUNCTION BOX SIZES/LOCATIONS ARE SUITABLE
<br />FOR THE INSTALLATION OF SPECIFIED ELECTRICAL SYSTEM
<br />COMPONENTS USING THE MEANS/METHODS PLANNED FOR
<br />INSTALLATION. FLOAT SHOP DRAWINGS WILL NOT BE APPROVED
<br />WITHOUT WRITTEN VERIFICATION THAT THE AFOREMENTIONED
<br />COORDINATION HAS TAKEN PLACE AND THAT THE FLOAT SHOP
<br />DRAWINGS HAVE BEEN APPROVED BYTHE ELECTRICAL SYSTEM
<br />INSTALLER. IMPORTANT: COORDINATE CHASE ALIGNMENT IN
<br />NEW FLOATS WITH EXISTING CHASES.
<br />ABBREVIATIONS
<br />EXHAUST FAN
<br />LOP
<br />LIGHT CONTROL PANEL
<br />PRI
<br />PRIMARY
<br />ELECTRI CAL METALLIC TUBI NG
<br />MAX
<br />MAXIMUM
<br />PSE
<br />PUGET POWER ENERGY
<br />ENCLOSURE
<br />MCA
<br />MI NIMUM CI ROUT AMPERES
<br />REQD
<br />REQUIRED
<br />END OF LINE
<br />HER
<br />MANUFACTURER
<br />RNC
<br />RIGID NONMETALLIC CONDUIT (PVC)
<br />EFFECTIVE PROJECTED AREA
<br />MIN
<br />MINIMUM
<br />PS
<br />RAPID START
<br />ELECTRIC WATER COOLER
<br />MISC
<br />MISCELLANEOUS
<br />SEC
<br />SECONDARY
<br />ELECTRICWATER HEATER
<br />MLO
<br />MAIN LUGS ONLY
<br />SLWD
<br />SINGLE LINE WRING DIAGRAM
<br />FIRE ALARM
<br />AND
<br />MOUNTED
<br />SPOT
<br />SINGLE POLE DOUBLE THROW
<br />FIRE ALARM ANNUNIATOR
<br />MTR
<br />MOTOR
<br />SPST
<br />SINGLE POLE SINGLE THROW
<br />FOOT CANDLES
<br />-N
<br />NEUTRAL (GROUNDED CONDUCTOR)
<br />SURF
<br />SURFACE
<br />FULL LOAD AMPERES
<br />NC
<br />NORMALLY COSED
<br />SAVED
<br />SWITCHBOARD
<br />FLEXIBLE
<br />NEC
<br />NATIONAL ELECTRICAL CODE
<br />SWGR
<br />S ITU GEAR
<br />FUSE
<br />-,LED
<br />NEGATIVE
<br />TB
<br />TERMINAL BOARD
<br />GENERATOR
<br />NEAR,
<br />NATIONAL ELECTRICAL
<br />TDC
<br />TIME DELAY CLOSING
<br />GROUND FAULT CIRCUIT
<br />MANUFACTURE'S ASSOC
<br />TOO
<br />TIME DELAY OPENING
<br />INTERRUPTER
<br />NL
<br />NIGHT LIGHT(UNSWITCHED)
<br />TEL
<br />TELEPHONE
<br />GROUND
<br />NO
<br />NORMALLY OPEN
<br />TOP
<br />TYPICAL
<br />GALVANIZED RIGID STEEL CONDUIT
<br />NTS
<br />NOT TOSCALE
<br />UL
<br />UNDERWRITERS LAB
<br />OC
<br />ON CENTER
<br />LION
<br />UNLESS OTHEPWSE NOTED
<br />IN
<br />H
<br />HORSEPOWER
<br />HORSEPOWER
<br />OUTSIDE
<br />UPS
<br />UNINTERRUPTIBLE POWER SUPPLY
<br />HERTZ (CYCLES PER SECOND)
<br />OFDCI
<br />OWNER FUDRNISIIED CONTRACTOR
<br />V
<br />VOLTS
<br />ILLUMINATING ENGINEERING SOCIETY
<br />INSTALLED
<br />VA
<br />VOLT-AMPERES
<br />I US DE DIAMETER
<br />OFOI
<br />OWNER FURNISHED, OWNER
<br />VFD
<br />VARIABLE FREQUENCY DRIVE
<br />W
<br />WATT
<br />ISOLATED GROUND
<br />INSTALLED
<br />INCANDESCENT
<br />OS
<br />OCCUPANCY SENSOR
<br />W/
<br />WITH
<br />W/0
<br />WITHOUT
<br />INTERMEDIATE METAL CONDUIT
<br />P
<br />POLE
<br />KEY OPERATED
<br />PB
<br />PUSH-BUTTON
<br />PAR
<br />WEATHERPROOF
<br />THOUSAND CIRCULAR MILS
<br />PEND
<br />PENDANT
<br />ROMR
<br />TRANSFORMER
<br />KNOCKOUT
<br />PH
<br />PHASE
<br />IN
<br />INCHES
<br />KILOWATTS
<br />PNL
<br />PANEL
<br />',FT
<br />FEET
<br />KILOVOLT -AMPERES
<br />+EPOS
<br />POSITIVE
<br />-
<br />PHASE
<br />1Tff0 05/19/2023 EJD ISSUED FOR BID
<br />1601 5th Avenue, Suite 1300
<br />Seattle, Washington 98101 0 04/11 /2023 EJD ISSUED FOR PERMIT REVIEW
<br />(206) 382-0600 Fax (206) 382-0500
<br />PROJECT NO. 1600120 No. DATE BY REVISION
<br />FIRE ALARM SYSTEM
<br />SYMBOL
<br />DESCRIPTION
<br />FACP
<br />FIRE ALARM CONTROL PANEL
<br />FMB 1
<br />FI RE ALARM REMOTE AN NUN CI ATOP
<br />❑F
<br />FIRE ALARM SYSTEM MANUAL PULL STATION, WALL
<br />MOUNTED
<br />SPEAKER- CEILING, WALL MOUNTED
<br />ED
<br />STROBE, WALL MOUNTED (X=CANDELA RATING)
<br />x
<br />m4
<br />COMBINATION SPEAKERSTROBE, WALL MOUNTED
<br />X
<br />(X- CANDELA RATING)
<br />SPRINKLER VALVE TAMPER SWITCH LOCATION
<br />SPRINKLER FLOW SWITCH CONNECTION
<br />51
<br />SMOKE DETECTOR CEILING OR PLENUM MOUNTED.
<br />PHOTOELECTRIC TYPE LION
<br />OC
<br />SMOKE SENSOR DUCT MOUNTED, WITH SAMPLING TUBES.
<br />PHOTOELECTRIC TYPE LION
<br />Q
<br />ELECTROMAGNETIC DOOR HOLDER, WALL MOUNTED
<br />®
<br />FIREMAN PHONE JACK, WALL MOUNTED
<br />m
<br />FIREMAN PHONE HAND SET, WALL MOUNTED
<br />FIRE ALARM CONNECTION TO COMBINATION EIRE/SMOKE
<br />®
<br />DAMPER
<br />®
<br />FLAME DETECTOR (FLICKER DETECTOR)
<br />❑
<br />LIGHT (LIGHT SIGNAL LIGHT, INDICATOR LAMP, STROBE)
<br />HEAT DETECTOR CEILING MOUNTED. RATE OF RISE AND
<br />FIXED TEMPERATURE TYPE, DUN
<br />QF
<br />HEATDETECTOR-FIXEDTEMP. ONLY
<br />%
<br />HEATDETECTOR-RATEOFRISEONLY
<br />pry
<br />POST INDICATOR VALVE (PIV) CONNECTION
<br />SIGNAL DEVICES
<br />SYMBOL
<br />DESCRIPTION
<br />EQUIPMENT TERMINAL BOARD 8HIGH X W IDTH AS SHOWN,
<br />FIRE TREATED.
<br />®
<br />COMBO TELEPHONE/DATA OUTLETWALL
<br />V
<br />TELEPHONEOUTLET-WALL
<br />V
<br />DATA OUTLET - WALL
<br />OS
<br />SPEAKER WALL CEILING
<br />VOLUMECONTROL-WALL
<br />BELL
<br />^LY
<br />�y
<br />BUZZER
<br />q3:r
<br />CHIME
<br />© C�
<br />SYSTEM CLOCK WALL CEILING
<br />®
<br />EMERGENCY CALL BOX
<br />®
<br />LEAK DETECTOR
<br />SECURITY SYSTEM
<br />DESCRIPTION
<br />iSYM�BOL�
<br />i w" Iv
<br />(LTV SECURITY CAMERA
<br />�p
<br />DOOR POSITION MONITORSWTCH
<br />INFRARED REQUEST TO EXIT DEVICE-WALLICEILING
<br />MOUNTED
<br />INTERCOMSTATION- WALL, DESKMOUNTED,
<br />M
<br />M = MASTER STATION
<br />❑
<br />PUSH BUTTON STATION
<br />®
<br />CARDREADER-WALLMOUNTED
<br />ELECTRIC LOCK
<br />OS
<br />ELECTRIC STRIKE
<br />®
<br />MAGNETIC LOCK
<br />©
<br />ELECTRIC POWER TRANSFER HINGE
<br />NO. I DATE I BY I REVISION
<br />LIGHTING
<br />SYMBOL
<br />DESCRIPTION
<br />FLUORESCENT RECESSED LUMINAIRE
<br />(REFER TO LUMINAIRE SCHEDULE FOR TYPE)
<br />FLUORESCENT SURFACE- MOUNTED LUMINAIRE
<br />(REFER TO LUMINAIRE SCHEDULE)
<br />SITAN NG OF ANY LUMINAIRE INDICATES CONNECTION
<br />®
<br />TO EMERGENCY CIRCUIT.
<br />O g
<br />HID FIXTURE
<br />Q
<br />DOWNLIGHT- SURFACE, RECESSEDCEIUNG MOUNT
<br />®
<br />FLOOR OR GRADE MOUNTED FIXTURE
<br />0
<br />WALLWASHSURFACE, RECESSED CEILING MOUNT
<br />�S
<br />TRACK LIGHTING WITH HEALS AS INDICATED.
<br />FLUORESCENT STRIPLIGHT- POWER FEED SECTION,
<br />FEED THOUGH SECTION, LENGTH AS SHOWN.
<br />FLUORESCENT WALL BRACKET-RESTROOM
<br />DIRECTIONAL HID FIXTURE
<br />In
<br />ADA APPROVED WALL SCONCE
<br />®
<br />ILLUMINATED EXIT SIGN, SHADEDQUADRANT
<br />INDICATESFACES, ARROWASSHOVNV
<br />0-0
<br />POLE MOUNTED LUMINAIRE
<br />4
<br />FOOT" INDICATES WALL MOUNTED LUMINAIRE
<br />>:NX
<br />FIXTURE TYPE IDENTIFICATION DESIGNATION
<br />GGO
<br />BATTERY POWER EMERGENCY UNIT EQUIPMENT (SEE
<br />SCHEDULE FOR QUANTITY OF HEADS) WALL
<br />CEILING MOUNTED.
<br />d
<br />REMOTEHEAD
<br />OPTICAL SENSOR AND REFLECTOR
<br />SWITCHING CONTROLS
<br />SYMBOL
<br />DESCRIPTION
<br />SINGLE POLE SWTCH (SUPERSCRIPT DENOTES SIMILARLY
<br />a
<br />MARKED LUMINARIES CONTROLLED TOGETHER)
<br />TWO POLE SWTCH
<br />THREE WAY SWITCH
<br />+
<br />FOUR WAY SWITCH
<br />KEY OPERATED SWITCH
<br />r'hP
<br />DIMMER SWITCH. NUMBER INDICATES WATTAGE RATING. IF
<br />NOT SHOWN 800W MINIMUM.
<br />W
<br />SWITCH WITH PILOT (PILOT IS ON WHEN SWITCH IS "ON")
<br />R
<br />SCOTCH WITH PILOT (PILOT Is ON WHEN SWITCH Is °oEP')
<br />$T
<br />TIMER SWITCH
<br />WEATHERPROOF SCOTCH
<br />d M
<br />MOTOR RATED TOGGLE WJTHERMAL
<br />P
<br />OVERLOAD PROTECTION
<br />®
<br />PHOTOCELL
<br />0
<br />TIME CLOCK
<br />1-1
<br />WALL MOUNTED DUAL LEVEL SWITCHING OCCUPANCY
<br />nw�
<br />SENSOR
<br />S
<br />EMERGENCY POWER OFF HEAVY-DUTY OIL TIGHT RED
<br />MUSHROOM HEAD PUSH-BUTTON
<br />®
<br />LIGHTING CONTROL PANEL
<br />LIGHTING CONTROL STATION
<br />DISTRIBUTION & EQUIPMENT
<br />SYMBOL
<br />DESCRIPTION
<br />BRANCH CIRCUIT PANELBOARDS, SURFACE AND RECESS
<br />®
<br />MOUNTED
<br />SOLID=129208V
<br />HATCHED 277/480V
<br />TRANSFORMER
<br />T
<br />SERVICE AND/OR DISTRIBUTION EQUIPMENT
<br />MOTOR CONNECTION .X= HORSEPOWER (WHERE SHOWN)
<br />®
<br />CONNECTI ON TO DIV. 15 FURNISHED VARIABLE FREQUENCY
<br />®
<br />DRIVE WITH INTEGRAL DISCONNECT DIV. 16TOINSTALL
<br />VFD EST PMENT
<br />DISCONNECTSWITCH SIZE AS NOTEDOR IF NOT SHOWN
<br />SIZE PER CONNECTED MOTOR SIZE (ARCH -BY DIVISION 15, TYR).
<br />�jp�
<br />FUSED DISCONNECT SWITCH SIZE AS NOTED OR IF NOT SHOWN
<br />SIZE PER CONNECTED MOTOR SIZE (ARCH '-BY DIVISION 15, TYR).
<br />DISCONNECT W/ MAGNETIC MOTOR STARTER (CONTROLLER)OR
<br />]OG
<br />CONTACTOR. AREAS NOTED OR IF NOT SHOWN SIZE PER
<br />CONNECTED MOTOR SIZE ('MECH'=BY DIVISION 15, TOP).
<br />MAGNETIC MOTOR STARTER (CONTROLLER) OR CONTACTOR
<br />®
<br />ORNOT SHOWNCONNECTED
<br />MOTORSIZENOTED
<br />15 LLD
<br />05/19/2023
<br />POWER DEVICES
<br />SYMBOL
<br />DESCRIPTION
<br />O_ q. [t�]
<br />SIMPLEX RECEPTACLE- WALL, CEILING, FLOOR
<br />C �
<br />DUPLEXRECEPTACLE- WALL, CEILING, FLOOR
<br />(OF 11011c 10
<br />DOUBLE DUPLEX RECEPTACLE WALL CLG, FLOOR
<br />DUPLEX RECEPTACLE AT SPECIAL HEIGHT
<br />+44
<br />DOUBLE DUPLEX RECEPTACLE AT SPECIAL HEIGHT
<br />DUPLEXRECEPTACLE-WALL -DEDICATED
<br />OR
<br />DUPLEXRECEPTACLE- WALL -HALFSWITCHED
<br />CE
<br />DUPLEX RECEPTACLE- WALL- ABOVE COUNTER/
<br />BACKSPLASH SEE ARCHITECTURAL DRAWINGS.
<br />C
<br />DUPLEXRECEPTACLE-WALL- WTH INTEGRAL GROUND
<br />�'131
<br />FAULT CIRCUIT INTERRUPTER
<br />06
<br />DUPLEX RECEPTACLE W/WEATHERPROOF COVER
<br />® ®C
<br />SPECIAL PURPOSE RECEPTACLE WALL CEILING
<br />NEAR, CONFIGURATION AS NOTED
<br />®
<br />ELECTRICAL EQUIPMENT CONNECTION
<br />PROVIDE#10 AWG NEUTRALS. USELIQHDDTIGHTFLEX.
<br />FLUSH FLOOR BOX DEVICE-DEVICETYPESPER
<br />®77
<br />SYMBOLS SHOWN.
<br />PEDESTAL FLOOR DEVICE-DEVICETYPESPER
<br />®�
<br />SYMBOLS SHOWN.
<br />TWO-PIECE SURFACE METAL RACEWAY WITH RECEPTACLE
<br />AS NOTED, LENGTH AS INDICATED ON THE DRAWINGS
<br />AND WITH ALL FITTINGS AS REQUIRED
<br />TELE/POWER POLE, POWER POLE
<br />COURTEST PHONE WITH ENCLOSURE
<br />TWO-PIECE SURFACE METAL RACEWAY WITH RECEPTACLE
<br />AT6" O.C(LENGTH AS INDICATED).
<br />X FyI
<br />POWER PEDESTAL
<br />X = 30 = 30A,120V OUTLET
<br />X = 50 = 50A,120/240V OUTLET
<br />X = 20GFCI = 20g120V DUPLEX GFCI PROTECTED OUTLET
<br />Y=DOCK OR ROW ID#
<br />Z = SLIP NUMBER/STALL(S) - (1)POWER HEAD EA
<br />NOTE. X' DESIGNATES OUTLET PER SLIP. MULTIPLE REFERENCES
<br />(30150) INDICATES MULTIPLE OUTLETS PER SLIP.
<br />DIAGRAMS
<br />SYMBOL
<br />DESCRIPTION
<br />OFF
<br />IYY
<br />HAND/OFF/AUTO SWTCH
<br />SWTCH
<br />OVERLOADS
<br />NORMALLY CLOSED CONTACTOR OR RELAY CONTACTS
<br />j^
<br />NORMALLY OPEN CONTACTOR OR RELAY CONTACTS
<br />BUS DUCT
<br />BUS BAR
<br />BATTERY (GENERAL)
<br />CONNECTOR, FEMALE AND MALE RESPECTIVELY
<br />©
<br />CONTACTOR COIL
<br />RELAY COIL
<br />®
<br />TRANSIENT VOLTAGE SURGESUPPRESSED
<br />CURRENTTRANSFORMER
<br />POTENTIAL TRANSFORMER
<br />NORMALLY OPEN PUSH BUTTON
<br />NORMALLY CLOSED PUSH BUTTON
<br />®
<br />METER POWER FACTOR
<br />®
<br />METER KILOWATT HOUR
<br />METER COMBINATION KILOWATT HOURKVAR METER
<br />UTILITY CO. APPROVED SOCKET WITH METER INSTALLED
<br />DELTA CONNECTION
<br />GROUND WVECONNECTOR
<br />II
<br />CONNECTION TO GROUND
<br />(.�XXX/Y
<br />CIRCUIT BREAKER
<br />FOX =AMPACITY Y=POLES
<br />FUSED SWITCH, WITH FUSE AND SWTCH AMPERE RATING
<br />CIRCUIT BREAKER, MEDIUM VOLTAGE, DRAWOUT
<br />�E �N
<br />DRAWOUT CI RCUT BREAKER
<br />®
<br />GROUND FAULT TRIP UNIT
<br />KEY INTERLOCK
<br />CAPACITOR, POWER FACTOR CORRECTION, SIZEINKVAR
<br />YG
<br />MOTORGENERATOR
<br />SOLENOID
<br />WIRING
<br />SYMBOL
<br />DESCRIPTION
<br />CONDUIT CONCEALED IN CEILING OR WALL. LINE WEIGHT
<br />TOP TO BOTTOM = NEW, EXISTI NG TO REMAIN.
<br />CONDUIT CONCEALED IN OR BELOW CONCRETE UNDER GRADE
<br />UNDERFED IN CEILING SPACE OF FLOOR BELOW. LINE WEIGHT
<br />TOP TO BOTTOM- NEW, EXISTING TO REMAIN.
<br />---
<br />CONDUITEXPOSED. LINE WEIGHT TOP TO BOTTOM- NEW
<br />-
<br />EXISTINGTOREMAIN.
<br />EA STING CONDUIT& WIRING TO BE REMOVED
<br />—C—
<br />COMMUNICATION CONDUIT/CABLE
<br />—MY—
<br />MEDIUM VOLTAGE CONDUIT
<br />—LV—
<br />LOW VOLTAGE CONDUCTORS
<br />—C—
<br />GROUNDING GRID OR CONDUCTORS
<br />—TV—
<br />CABLE TV WIRE/CONDUIT
<br />—C/H—
<br />AERIAL CONDUCTOR(S)/OVERHEAD LINE
<br />STROKES INDICATE QUANTITY OF#12 AWG. CONDUCTORS,
<br />LION. NOTE NOT ALL WIRING IS SHOWN ON DRAWNG.
<br />CONTRACTOR SHALL SCHEDULE OR STANDARD WIRING
<br />PRACTICES FOR BRANCH CIRCUITS.
<br />GROUND
<br />HOT
<br />GROUND, ISOLATED
<br />NEUTRAL
<br />HOME RUN TO INDICATED DESTINATION, 3/4"C MIN. LION
<br />CONDUIT RUN TURNED UP THROUGH FLOOROR CEILING.
<br />CORE AS REQUIRED.
<br />CONDUIT STUBBED OUT AT LOCATION SHOWN PROVIDED
<br />INSULATED BUSHING & PULLROPE.
<br />TELEPHONE/DATA SLEEVE THROUGH WALL, ABOVE
<br />CEILING EXTENDTO ACCESSIBLE LOCATION BOTH SIDES.
<br />[�
<br />TERMINATE WITH BUSHINGS. (1) 11/4" CO LION. COORDINATE
<br />LOCATIONS WITH CABLE INSTALLER(A PRIOR TO
<br />ROUGHIN
<br />CABLETRAY
<br />®C [a
<br />JUNCTION BOXES WALL CEILING AND FLUSH FLOOR
<br />MOUNTED. 4" SQ. BOX, LION.
<br />®
<br />PULL BOX MIN. SIZE PER NEC., LION.
<br />FLEXIBLE CONDUIT CONNECTION
<br />GROUND ROD CONNECTION
<br />OGROUND
<br />ROD CONNECTION WITH TESTWELL BOX
<br />+
<br />LIGHTNING SYSTEM AIR TERMINAL
<br />UNDERGROUND PULLBOX/VAULT (P-POWER T=TEL/COM U=UTILITY)
<br />®
<br />UNDERGROUND PULLBOX/VAULT(PLASTIC)
<br />HANDHOLE
<br />REFERENCE SYMBOLS
<br />SYMBOL
<br />DESCRIPTION
<br />SHEET NOTE REFERENCE (FLAG NOTES)
<br />XXXX
<br />FEEDER NOMINAL AMPACITO& TYPE. SEE FEEDER
<br />SCHEDULE
<br />TOFETAIT TEDNOT ALL
<br />REFER TODERENCES.
<br />R SHOWN
<br />REFERENCES AL DETAIDLS APPLY
<br />DETAI ALLD
<br />V-V
<br />TO ALL APPLICABLE SITUATIONS, U ON.
<br />X
<br />ELEVATION/PHOTOTAG. REFERTONUMBER
<br />V-V
<br />AND SHEET INDICATED
<br />SECTION TAG'. REFER TO DETAIL NO. ON DRAWING.
<br />NOT ALL DETAIL REFERENCES ARE SHOWN. ALL
<br />V-V
<br />DETAI ITS APPLY.
<br />PROJECT ENGINEER: SCALE
<br />E. DAVID None : PORT OF EVERETT
<br />DE. DAVID 05/19/2023 CENTRAL MARINA FUEL DOCK
<br />DRAWN BY: CHECKED BY:
<br />K. DAVID E. DAVID
<br />APPROVED BY: NOTES, LEGEND, ABBREVIATIONS,
<br />& LUMINAIRE SCHEDULE
<br />IF SHEET IS LESS THAN 2204
<br />REDUCE SCALE ACCORDINGLY
<br />DWG. NO. E0.0
<br />CIE No. H
<br />2-0-073-01 L/U�
<br />PROJECT V,
<br />No, MR—CM-2023-01 MQ
<br />SHEET No. 61 OF 88 W