4.8 Install Pressure Relief Valve <br /> A WARNING Water discharged from the pressure relief valve could cause severe <br /> burns instantly or death from scalds. <br /> 4.8.1 Guidelines <br /> An approved pressure relief valve is required The American National Standard (ANSI <br /> by the American National Standard (ANSI Z21.10.3)does not require a combination <br /> Z21.10.3)for all water heating systems and shall temperature and pressure relief valve for <br /> be accessible for servicing. When connecting a this appliance. However, local codes may <br /> pressure relief valve, follow the guidelines below: require a combination temperature and <br /> • The pressure relief valve must comply with <br /> pressure relief valve. <br /> the standard for Relief Valves and Auto- Protect pressure relief valve and pressure <br /> matic Gas Shutoff Devices for Hot Water relief valve discharge line from freezing. <br /> Supply Systems ANSI Z21.22 and /or the Do not plug or restrict flow of the pressure <br /> standard Temperature, Pressure, Tem- relief valve. <br /> perature and Pressure Relief Valves and DO NOT plumb the pressure relief valve <br /> Vacuum Relief Valves, CAN1-4.4. with the condensate drain; both must be <br /> • The pressure relief valve must be rated plumbed independently to drain. <br /> up to 150 psi and to at least the maximum DO NOT plug the pressure relief valve and <br /> Btu/hr of the appliance. do not install any reducing fittings or other <br /> • The discharge from the pressure relief restrictions in the relief line. The pressure <br /> valve should be piped to the ground or into relief line should allow for complete drain- <br /> a drain system per local codes. age of the valve and the line. <br /> • The pressure relief valve must be man- DO NOT place any other valve or shutoff <br /> ually operated once a year to check for device between the pressure relief valve <br /> correct operation. and the water heater. <br /> • The discharge line from the pressure relief <br /> valve should pitch downward and termi- <br /> nate 6 in. (152 mm) above drains where <br /> discharge will be clearly visible. <br /> • The discharge end of the line shall be plain <br /> (unthreaded) and a minimum of 3/4 in. <br /> nominal pipe diameter. The discharge line <br /> material must be suitable for water at least <br /> 180' Fahrenheit. <br /> • The pressure relief valve is assembled to <br /> the pressure relief valve adapter as illus- <br /> trated on the next page. DO NOT place <br /> any other valve or shut off device between <br /> the pressure relief valve and the water <br /> heater. <br /> • If a pressure relief valve discharges peri- <br /> odically, this may be due to thermal expan- <br /> sion in a closed water supply system. Con- <br /> tact the water supplier or local plumbing <br /> inspector on how to correct this situation. <br /> Do not plug the pressure relief valve. <br /> Rinnai Tankless Water Heater Installation and Operation Manual 56 <br />