DN-60686:A1
<br /> UDACT-2 © NOTFEW
<br /> :
<br /> Universal Digital Alarm
<br /> Communicator Transmitter byHoneywell
<br /> General
<br /> The Universal Digital Alarm Communicator Transmitter(UDACT- �.'
<br /> 2)is designed for use on Notifier Fire Alarm Control Panels and
<br /> on the NCA-2 Network Control Annunciator.When used in con- : ,
<br /> junction with the NCA-2 network control annunciator, the `
<br /> UDACT-2 can report the status of all control panels on ," Li I �
<br /> NOTI•FIRE•NETTM.The UDACT-2 transmits system status to UL • '
<br /> listed Central Station Receivers via the public switched y
<br /> tele-
<br /> phone network.The UDACT-2 can be installed in the panel cab- *, " IL,
<br /> inet or remotely in a separate enclosure. `� v r
<br /> z.NOTE: The UDACT-2 can also be used with legacy panels. ,
<br /> Please refer to the UDACT-2 manual for more information. '
<br /> The UDACT-2 upload/download programming and firmware j rvII f
<br /> updates are accomplished with VeriFire Tools. Refer to the Pro- •
<br /> - s *-.
<br /> gramming Section for further details.
<br /> '�„
<br /> The UDACT-2 is capable of transmitting the status of software -<„
<br /> zones (Alarm and Trouble), System Trouble, Panel Off-Normal,
<br /> Supervisory, Bell Trouble, Low Battery, and AC Fail. The 3 `
<br /> UDACT2 is capable of transmitting all of the zone and point sta-
<br /> tus associated with each panel. tom, q •;
<br /> When the UDACT-2 is used with the NFS-3030, NFS2-3030, I� 7f� : t
<br /> and NCA-2 it is capable of reporting up to 2,040 points. Report- # i j
<br /> f1U(9 Tft ,:: 6, ( ,1
<br /> ing may be in the form of points or zones(refer to the UDACT-2a
<br /> manual for specific reporting parameters). Points transmitted
<br /> may be programmed for a variety of types,including fire,water- '"F
<br /> flow,supervisory,etc.
<br /> UDACT-2
<br /> NOTE:Descriptions regarding point capacity, listed above,are for
<br /> receivers which receive in Ademco Contact ID format. See chart • Open Collector relay driver for Total Communications Failure
<br /> on page 2 for compatible receivers. or UDACT-2 trouble.
<br /> Features • Real-time clock.
<br /> • Extensive transient protection.
<br /> • Programmable with VeriFire Tools version 6.60 or higher, . EIA-485 interface to host panel.
<br /> allowing the UDACT-2 programming to be uploaded/down-
<br /> loaded and saved. Programming
<br /> • Maximum of 14 point trouble messages transmitted per hour. The UDACT-2 programming is created and downloaded using
<br /> • Dual phone lines with line voltage detect. VeriFire Tools.This enables the unit to be programmed prior to
<br /> • Compact in size:6.75"x 4.25"(17.145 x 10.795 cm). installation, be easily modified, and saved either online or
<br /> • USB port for upload/download programming. offline. A printed report with point or zone information can be
<br /> Manual Test Report function. generated from VeriFire Tools for an ONYX Series panel or net-
<br />, • work annunciator.The point report consists of the central station
<br /> • Manual Transmission Clear function. point address,ACS point,ACS point function,panel label,panel
<br /> • Mounts in a separate enclosure(ABS-8RB or UBS-1B/R). point,type code,custom and extended label,alarm verification,
<br /> • Communicates vital system status including: walktest participation,presignal,and PAS information.The zone
<br /> —Independent zone fire alarm. report consists of a grid with the central station point address,
<br /> ACS point address, source, ACS point function, custom label
<br /> —Independent zone non-fire alarm. and panel label.This report may be sent to the Central Station
<br /> —Independent zone trouble. for their records. VeriFire Tools also supports upgrading the
<br /> —Independent zone supervisory. UDACT-2 operating firmware.
<br /> —AC(mains) Power Loss(programmable).
<br /> —Low Battery and Earth Fault.
<br /> —System Off-Normal.
<br /> —12 or 24 hour test signal.
<br /> —Abnormal Test Signal per new UL requirements.
<br /> —EIA-485 Communication Bus Failure.
<br /> • Annunciation of UDACT-2 Troubles including: loss of phone
<br /> lines, communication failure with either Central Station,total
<br /> communications failure.
<br /> • Individual LEDs for: Power, EIA-485 Loss, Manual Test, Kis-
<br /> soff, Comm Fail, Primary Line Seize, Secondary Line Seize
<br /> and Modem Communications.
<br /> =VW V, . ..
<br /> DN-60686:A1 •4/2/12—Page 1 of 2