r Mr. Martin Reimers <br /> Concept Architecture, LLC <br /> Plan Check Number: B2210-002, Second Building Review <br /> May 24, 2023 <br /> Structural <br /> Lateral System: <br /> 7. This comment has not been completely addressed. The lateral load path for the new roof will <br /> be primarily to the existing building through wood and masonry anchorage. This includes the <br /> north-south direction due to the metal deck that provides a relatively stiffer load path than the <br /> proposed steel moment frames. See IBC Sections 107.2.1 and 1603.1. The following <br /> comments should be addressed: <br /> a. Detail 11/S801 should be revised to clarify the existing wall construction; it is presumed that <br /> the fasteners are transferring load to an existing sheathed wall. The blocking construction <br /> should be revised to specify fasteners between the blocking and the studs. The minimum <br /> fastener lengths should be specified. <br /> b. Detail 16/S801 should be revised to specify fasteners suitable for connection to unreinforced <br /> masonry and approved for seismic loading. Documentation substantiating the selected <br /> fasteners should be submitted for review. <br /> c. Calculations substantiating the fastener design in both principal directions (i.e., shear and <br /> withdrawal) for both the wood and masonry attachments should be submitted for review. <br /> See IBC Sections 1604.1 and 1604.4. <br /> Additional Comments: <br /> 11. General Structural Note 1.11 on Sheet S000 should include a schedule of special inspections. <br /> The schedule should specify the types and frequency for each inspection. Work requiring <br /> inspections includes but is not limited to geotechnical, concrete, and steel construction. See <br /> IBC Section 1704.3.1. <br /> 12.The General Structural Notes on Sheet S000 should include criteria for the lateral loading and <br /> lateral system(s). See IBC Section 1603.1.5. <br /> 13.The proposed lateral system includes an ordinary steel moment frame on the east side include <br /> drag struts. See IBC Sections 1604.1, 1604.4, and 1613.1. The following comments should be <br /> addressed: <br /> a. Calculations substantiating the design of the beams being utilized as drag struts should be <br /> submitted for review. The design should consider concurrent axial and flexural loading. <br /> b. Calculations substantiating each mechanism of the connection should be submitted for <br /> review. It is noted that the connection plates are welded to the column faces instead of <br /> utilizing knife plates. The flexure of the column faces should be included in the design, or <br /> knife-plates should be used to provide a direct load path. <br /> 14.The beam shear connections in Details 2, 6, and 7 on Sheet S801 utilize a single bolt and result <br /> in significant eccentricity. The second bolt will not contribute to shear transfer. It is noted that <br /> Details 6 and 7 do not specify the distance to the first bolt. Calculations substantiating the <br /> shear connections should be submitted for review. See IBC Sections 1604.1 and 2205.1. <br /> O3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett, WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 3 of 4 <br />