Mr. Martin Reimers <br /> Concept Architecture, LLC <br /> Plan Check Number: B2210-002, First Building Review <br /> January 20, 2023 <br /> Architectural <br /> General: <br /> 1. The structural details generally consist of architectural details that have been reproduced on <br /> structural sheets and sealed by the engineer. This is not recommended as it creates redundant <br /> and potentially conflicting information. The architectural sheets should include a note stating <br /> that the structural drawings control for all structural construction. See IBC Section 107.2.1, <br /> RCW 18.43, and structural comments below. <br /> Fire Protection: <br /> 2. Sheet A2.1 includes a Wall Legend that references and conflicts with Detail 5/A0.2. The Wall <br /> Legend appears to specify wood panel structural sheathing that is not specified in the detail. In <br /> addition, the narrative appears to indicate that the GWB occurs between the structural <br /> sheathing and the GWB. The drawings should be revised to clearly indicate the proposed <br /> construction. See IBC Section 107.2.1 and structural comments below. <br /> 3. The building is classified as Type VA construction and required minimum one-hour rated <br /> protection per IBC Table 601. The sections and details do not indicate the beams and columns <br /> are protected, including the elements at the basement level. Details providing the minimum- <br /> required protection should be included. The details should include references to tested <br /> assembly listings per IBC Section 703.2, or be designed per IBC Section 721 or 722. Details <br /> designed per Section 721 should include the appropriate code reference. Details designed per <br /> Section 722 should be substantiated by calculations. <br /> 4. Detail 4/A0.2 references IBC Table 721.1(3)-21-1.1 for the rated assembly. This assembly is for <br /> wood-framed construction, not solid steel joists as indicated in the detail. The assembly <br /> reference should be revised, or a tested assembly should be referenced per IBC Section 703.2. <br /> Egress: <br /> 5. The new entryway doors should specify panic hardware. See IBC Section 1010.1.10. <br /> 6. Additional exit sign should be specified in the new entryway. See IBC Section 1013. <br /> 7. Additional interior and exterior emergency egress lighting should be specified at the entryway <br /> doors. See IBC Sections 1008.3.1 and 1008.3.2(5). <br /> Accessibility: <br /> 8. The new south entry doorway appears intended to include both a latch and closer. The door <br /> should specify a minimum 12-inch clearance on the latch side. See IBC Section 1101.2 and ICC <br /> A117.1-09 Figure 404.2.3.2(b). <br /> 3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 2 of 5 <br />