Laserfiche WebLink
410 <br /> Mr. Mazen Wallaia <br /> Plan Check Number: B2107-068, First Building Review <br /> August 18, 2021 <br /> General <br /> 1. The governing building codes should be listed in the construction drawings, including but not <br /> limited to the 2018 IRC and 2018 WSEC-Residential. The 2018 IBC may also apply as noted in <br /> the comments below. See Section R106.1.1 and EMC Section 16.005.030. "Updated the info <br /> on Sheet A0.1" <br /> 2. It appears that the proposed project may involve converting the single-family residence (SFR) <br /> to an adult family home(AFH). The project scope should be clarified. Additional requirements <br /> may apply, including but not limited to submitting the AR-I worksheet. See Sections R330. 'As <br /> of today, we are planning to convert the house to(AFH)" <br /> LAJo-1 <br /> 3. Engineered design may be required per Section R301.1.3 and the comments below. Structural <br /> drawings and calculations should be sealed and signed by a professional engineer licensed in <br /> the state of Washington per IBC Section 107.3.4 and RCW Sections 18.43.010, 18.43.020, and <br /> 18.43.070. "We have determined that converting the carport into a leaving room is not cost <br /> affective. Therefore, we have revised the project description to Remold the existing home by <br /> adding the 4th bedroom an office and study room;remodel the bathrooms, remolding the <br /> kitchen and relocating the washer and dryer location to the main bathroom. <br /> Architectural <br /> 1. The primary egress door should be designated on the drawings and specified to have a <br /> minimum 32 clear opening. See Section R311.2. "N/A" <br /> 2. Landing should be specified at all exterior doors per Sections R311.2 and R311.3.1. Where <br /> landings are not level with the grade leading from the house, the height of the landing above <br /> the adjacent grade should comply with Section R311.7.5.1. "N/A" <br /> 3. The smoke and CO alarms required immediately outside the sleeping areas should be relocated <br /> closer to the bedrooms. See Sections R314.3 and R315.3. "Updated" <br /> 4. Sheet A0.4 includes windows adjacent the Living Room exterior door. The windows should be <br /> specified to include safety glazing. See Section R308.4.2. "N/A„ <br /> 5. The text in the"Typical Wall Section"at the right side of Sheet A0.4 is not legible and should be <br /> enlarge. See Section R106.1.1. "N/A" <br /> 6. The range in the Kitchen on Sheet A0.4 should be provided with an exhaust fan per Sections <br /> R303.4 and M1505.4.4. "Updated" <br /> 7. The drawings should include a calculation for the minimum area of roof ventilation. The <br /> ventilation should be evenly distributed between the eaves and ridge. See Section R806. "N/A" <br /> 8. The project should comply with the energy credit requirements of WSEC Section R406. The <br /> minimum number of credits should be determined including the normalization credit per Table <br /> 0 3200 Cedar Street 0 425.257.8810 0 everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> ge2of4 <br />