Laserfiche WebLink
KAISER PERMANENTE Site Prep #1 Electrical Service <br />ASC & Clinic (HUB) March 18, 2020 <br />Everett, WA Project No. 19.05002.00 <br />B. DDC Analog Signal Wiring: Analog signal wiring for analog inputs and analog outputs <br />shall be 18 AWG single or multiple twisted pair. Each pair greater than one shall be 100 <br />percent shielded, and have 20 AWG drain wire. Exception is direct connect RTD wiring, <br />which shall be 18 AWG minimum twisted pair, 100 percent shielded, and with 20 AWG <br />drain wire. Each wire shall have insulation rated to 300 VAC. Cables shall have an <br />overall aluminum -polyester or tinned -copper cable -shield tape, overall 20 AWG tinned <br />copper cable drain wire, and overall cable insulation rated to 300 VAC. <br />C. Plenum Cable: Plenum cable shall be UL approved for use only in accessible ceiling <br />spaces. Plenum cable external to electrical raceway is permissible in the following <br />locations: <br />1. DDC communication trunk serving application specific controllers within a <br />building. <br />2. DDC system sensor wire installed above suspended accessible ceilings. <br />2.5 CONTROL COMPONENTS <br />A. Actuators: Actuators shall have ISO 9001 quality certification and shall be UL Listed. <br />Provide for all motor -operated dampers, valves, and AHU fan flow control device of <br />sufficient size and type, matched to application and rated for maximum operating <br />temperature/pressures conditions. <br />1. Electric or Electronic Actuators: Solid state positioner to stop automatically at <br />end of travel. Complete with permanently lubricated gear train. Provide <br />proportional, or 2-position (with adjustable SPDT auxiliary end -switch) actuators. <br />Provide with spring return to normally -open or normally -closed on loss of control <br />power. Power return type actuators shall not be acceptable. Modulating <br />actuators shall be provided with position feedback signal corresponding to the <br />actual valve position. All actuators shall be provided with visual position <br />indicator. Substitution for 3-point floating type actuators suitable for pulse width <br />modulation control in lieu of analog type actuators shall be permitted only for <br />terminal units, [Unit Heaters][, ][Fan Coil Units][, ][Cabinet Heaters], [Finned <br />Tube Radiation][, ][ and ][Convectors]. Use of non -analog type actuators for <br />any other applications shall not be allowed without prior approval. [Provide <br />position feedback for actuators as indicated in "DDC Point List".] <br />2. Manufacturers: <br />a. TAMCO Series 1000. <br />b. Ruskin CD-50. <br />C. [Approved equal]. <br />B. Control Valves: Valves shall have stainless steel stems and stuffing boxes with extended <br />necks to clear the piping insulation. Valve bodies shall be designed for not less than 125 <br />psig working pressure or 150 percent of the system operating pressure, whichever is <br />greater. Valve leakage rating shall be 0.01 percent of rated Cv. Unless otherwise <br />specified, bodies for valves 1-1/2 inches and smaller shall be brass or bronze, with <br />threaded or union ends; bodies for 2 inch valves shall have threaded ends; and bodies <br />for 2 inches to 3 inches shall be of brass, bronze or iron. Bodies for valves 2-1/2 inches <br />and larger shall be provided with flanged -end connections. Valve Cv shall be within 100 <br />to 125 percent of the calculated Cv. Valves shall provide effective control within pumping <br />system total head pressure with a minimum of 100:1 turndown. Pressure drop not to <br />exceed 5 psig at maximum flow rate for hydronic systems. <br />1. Two -Way Valves: Two-way modulating valves shall have equal -percentage <br />characteristics. <br />2. Three -Way Valves: Three-way valves shall provide linear flow control with <br />constant total flow throughout full plug travel. <br />INSTRUMENTATION AND CONTROLS FOR HVAC 23 09 00 - 6 <br />