SECTION 23 38 13 13 on drawings.Static pressure requirements shall be precise and 3.2 INSTALLATION <br /> SPECIFICATIONS rater air velocity and volume Information shall be accurate within <br /> TAGS Commercial Kitchen Ventilation Hoods,Listed Commercial Kitchen Hoods 1-ft Increments along the length of the ventilator. A.Install In accordance with manufacturer's Instructions,drawings, <br /> PART 1-GENERAL written specifications,manufacturers Installation manual,and ail <br /> applicable building codes. <br /> 1.1 SUMMARY <br /> 2.2 CONSTRUCTION <br /> A.The S series n Type I,sloped well canopy hood for use over A.Construction shall be type 430 stainless steel. <br /> 600•F cooking surface temperatures.The sloped canopy Is the Ideal <br /> hood choice for low celling heights. B.Double wall Insulated front to eliminate condensation and Increase <br /> B.The hood shall have the size,shape,and performance specified on rigidity on wide sizes.The Insulation shall have a flexural odulus of <br /> drawings. 475 EI,meet UL 181 requirements and be In accordance with NFPA 90A <br /> and 90B. <br /> C.Hood shall be equipped with a minimum of four connections for <br /> 1.2 SUBMITTALS hanger rods.Hood lengths greater then 12will have added hangers. <br /> A.The m nufacturer n o liability for the u or"suits of A Exhaust duct collar to be 4"high with flange. <br /> use from this document.Specifications are to bea^reviewed by the E.The grease drain system shall be an enclosed Integral port of the <br /> grater to confirm <br /> the protects requirements d nett Federal, hood back and have slopes with an exposed,removable 1/2 grease <br /> State,nntl Local codes nntl regulations. <br /> cup to facilitate cleaning. <br /> B.As the manufacturer continues product development,It restry es F.Hood shall be furnished with UL classified filters,supplied In size <br /> the right to change design nntl specifications without notice. and quantity as required by ventilator. <br /> C.The manufacturer shall supply complete computer generated G.All tams shall be welded nntl have stainless steel on exposed <br /> submittal drawings,including hood section view(s)and hood plan .surfaces. <br /> view's).These drawings must be available to the engineer,architect, <br /> and owner for their use In construction,operation,and maintenance. <br /> 2.3 LIGHTING <br /> 1.3 QUALITY ASSURANCE A.Recessed round LED fixture and LED light,3500K Warm output. <br /> A.This hood Is ETL-listed to standard UL710,ULC710,and ULC-S646 2,4 FILTERS <br /> when Installed In accordance with these Installation instructions and <br /> National Fire Protection Association Standard NFPA 96,Standard for A.Stainless Steel Cuptrute Solo filter with hook,ETL Listed. <br /> Ventilation Control and Fire Protection of Commercial Cooking Particulate capture efficiency-85%efficient at 9 microns,76X <br /> Operations." efficient at 5 microns. <br /> B.Built-In compliance with NSF/ANSI Standard 2. <br /> C.The hood shall be ETL Listed as, 2.5 OPTIONS <br /> 1. Exhaust Hood Without Exhaust Damper. A.Fire Suppression System,UL 300 fire suppression system. <br /> 2.ETL Sanitation Listed and built in accordance with NFPA 96. H.Optional perforated supply plenum shall provide make-up air <br /> 3.The ETL label shall list temperature rating(s)and minimum CFM/ft discharged below the cooking equipment. <br /> rating(s). 1.Perforated diffuser plates shall be Included In the design to <br /> provide even air distribution. <br /> 1.4 WARRANTY 2.Unexposed surfaces shall be constructed of aluminized steel. <br /> Plenum shall be Insulated to prevent condensation. <br /> A.All units shall be provided with the following standard warranty, 3.Perforated Supply Plenum(PSP) <br /> 1.This equipment Is warranted to be free from defects In materials C.Wail Mounted Utility Cabinet-Cabinet can store listed fire <br /> and workmanship,under normal use and service,for a period of suppression system,listed components,pre-wired electrical controls. <br /> 2-years from date of shipment. <br /> 2.6 ACCESSORIES <br /> B.The manufacturer shall n liable for Incidental and consequential <br /> Losses <br /> and homages potentially <br /> he equipment <br /> to prove <br /> malfunctioning A.End Pnnelft In <br /> hood performance and ell of s the effects of <br /> equipment.Should any port it the equipment prove{o be defective cross drafts In the kitchen.Units constructed of stainless steel <br /> examination ini o orkm anufa within the 2-year w nnty period,upon and slzetl according to hood width nntl cooking equipment.Exposed <br /> by the manufacturer,such part will be repaired a edges hemmed for safety and rlgitli{y.Selected panels- <br /> rep <br /> laced by mnnufncturer at no charge.The buyer shall pay all 1.Vertical End Panel <br /> Labor costs Incurred Inc ection with such repair o repiacement. <br /> Equipment shall not be returned without m nufncturer's prior 2.Wall as End Panel <br /> authorization,and <br /> all returned equipment shot be shipped by the H.S{nndoff(s)selvcted� <br /> buyer,freight prepaid to a destination determined by the <br /> mnnufncturer. 1.Right End Standoff <br /> C.Refer to Manufacturer's Operation,Installation,and Maintenance C.Mlscelianeous option(s)selected- <br /> (DIM) to <br /> for detailed descriptions of what is/Is not covered and <br /> contact Information for warranty cinims. 1.Insulation for Top of Hood-Fully Insulated top of hood. <br /> 2.Insulntlon for Back of Hood -Backside of hood Is fully Insulated. <br /> PART 2-PRODUCTS 3.Sensor-Capture Volume -Duct stat Installed In the capture <br /> 2.1 GENERAL volume of the hood. <br /> A.Construction shall be dependent on the structural application to PART 3-EXECUTION <br /> minimize distortion and other defects.All seams,Joints,and <br /> penetrations of the hood enclosure to the Lower outermost 3.1 EXAMINATION <br /> perimeter,which directs and captures grease-laden vapor and <br /> exhaust gases,shall have a liquid-tight continuous external weld In A.Examine areas <br /> and conditions under which the system Is Installed.Do <br /> accordance with NFPA 96. not proceed with work until unsatisfactory conditions have been <br /> B.Duct sizes,CFM,and static pressure requirements shall be as shown corrected in a manner acceptable to Instate'. <br /> FOR REFERENCE ONLY <br /> FACILITY DESIGN BY CEI DATE <br /> ✓OBEverett Mexican — Broadway <br /> LOCATION EVERETT, WA, 98201 <br /> /�/� = DATE 6/27/2022 JOB 5534351 <br /> n oNa®c; O �/� ■� , -� DAY 5 V)Z4#Ar F BYJDC-85 <br /> R—FV SCALE 1/4' = 1'-0' <br />