C MMERCIAL COOKING SYSTEMS SECTION 904.12 3.All nozzles shall Incorporate a stamped part number to quickly <br /> O <br /> TAG,CORE Fire Protection Identify nozzle type. <br /> PART 1-GENERAL C.Distribution System <br /> 1.1 SUMMARY 1.The distribution system shall consist of Copper,Schedule 40 black <br /> Iron,chrome-plated or stainless-steel pipe and fittings.All <br /> A.The CORE Fire Protection system Is a pre-engineered wet chemical exposed piping and fittings must be chrome-plated or <br /> water based(surfactant)fire suppression system for use in stainless-s{eel. <br /> commercial kitchens. 2.Fittings shall be minimum class 150.Galvanized fittings shall not be <br /> 1.2 SUBMITTALS used. <br /> A.The manufacturer assumes no liability for the use or results of 3.Flow rate for the hood,when In a fire condition,would be 1.5 <br /> useof this document,This speclflcatlon Is to be reviewed by the gallons per minute per foot of hood. <br /> engineer <br /> {o confirm requirements of the protect and building codes 4.Operating pressure for water lines,both hot water and dedicated <br /> are et. line,Is 30 to 70 psi,depending on the system configuration. <br /> B.As the manufacturer continues product develoipmentI{hou{,Ina{Ice.reserves <br /> the 5.The maximum static pressure cannot exceed 125 sil pressure <br /> right to change design tl pedfica{Ions reducing valves can utilized to meet the correct operating <br /> 1.3 QUALITY ASSURANCE water pressure n e <br /> A.CORE Fire Protection System shall be UL 6 ULC listed In accordance D.Suppression System <br /> with UL300,and ULC/ORD-C1254.6. 1.The system control equipment shall be capable of all functions <br /> B.Microprocessor-based control board shall be ETL Listed to UL associated with automatically and manually discharging surfactant <br /> Standard 864 and CAN/ULC-S527-11. from surfactant tank,Including automatic shutdown of the heat <br /> C.CORE Fire Protection System Is Intended for Installation and for use ource or fuel and electrical power to all protected areas upon <br /> In accordance with the National Fire Protection Association system discharge. <br /> Standards- 2.For automatic activation,the system will be activated by a <br /> 1.Wet Chemical Extinguishing Systems,NFPA 17A Flrestat(heat)detector. <br /> 2.National Electrical Code,NFPA 70 3.For manual activation,an electrically operated manual release <br /> shall be used to actuate the system manually. <br /> 3.National Fire Alarm 6 Signaling Code,NFPA 72 E.Flrestat <br /> 4.Installation of Equipment for the Removal of Smoke and 1.Hood 411,Normally Open,Close on Rise 360'F. <br /> Grease-Laden Vapors from Commercial Cooking Equipment,NFPA 96 <br /> Additional firestatsay be required based on hood temperature <br /> D.The CORE Fire Protection System is approved for use In New York 2.rating and length of ductwork.Refer to Installation,Operation, <br /> City per FDNY COLA#5877. and Maintenance Manual for Information. <br /> 1.4 WARRANTY F.Electrical <br /> A.All units are provided with the following 5-year standard warranty 1.Electrical Division to provide shunt trip breakers at main power <br /> from date of shipment.Warranty does not cover consumable rr panel,or disconnects,as designated by the Electrical Engineeri <br /> products such as <br /> batteries,surfactant,and nozzle caps. Interconnection provided at hood control panel for the signal to <br /> B.This warranty shall not apply if, shut down all electricity in and under the exhaust hood.Shunt <br /> trips/disconnects to accomplish shut off of electricity In the <br /> 1.The equipment Is not Installed by a qualified Installer per the event of fire system activation by others. <br /> manufacturer's Installation Instructions shipped with the product. 2.Printed circuit board with microprocessor-based controller that <br /> 2.The equipment Is not Installed in accordance with Federal,State, provides all the necessary monitoring,timing,and supervision <br /> and <br /> Local retiabcodes and regulations. functions required for the tellable operation of the fire system. <br /> 3.The equipment Is misused,neglected,or not maintained per the 3.Independent supervised loops Incorporate redundancy and fault <br /> manufacturer's maintenance Instructions. detection. <br /> 4.The equipment Is not operated within Its published capacity. 4.Real-time cloud-based monitoring connection provided with system <br /> 5.The Invoice Is not paid within the terms of the sales agreement. by ownership. <br /> C.The manufacturer shall not be liable for Incidental.antl c sequential 5.All wiring must be In accordance to NFPA 70 and the Authority <br /> losses and damages potentially attributable to malfunctioning Having Jurisdiction(AHJ). <br /> equipment.Should any part of the equipment prove to be defective 6.Electric gas valve provided for equipment below exhaust hood. <br /> In material or workmanship within the 5-year warranty period,upon Coordinate size and Installation with PWmbing Division. <br /> examination by the manufacturer,such part will <br /> be repaired or <br /> replaced by the manufacturer at n charge.The buyer shall pay all 7.Ali wiring is to be In accordance with the applicable <br /> Labor <br /> costs Incurred In connection with such repair o replacement. n facturers Instructions for the fire alarm control.panel,gas <br /> Equipment shall not be returned without manufacturer's prior shut-off valve,manual reset relay,and contractor supplied <br /> authorization.All returned equipment shall be shipped by the buyer, shut-off devices. <br /> freight prepaid to a destination determined by the manufacturer. PART 3-EXECUTION <br /> PART 2-PRODUCTS 3.1 EXAMINATION <br /> 2.1 GENERAL ASSEMBLY A.Examine all areas <br /> and conditions under which package(s)are to be <br /> A.A pre-engineered,fixed pipe,automatic wet chemical(surfactant) Installed.Do not proceed with work until unsatisfactory conditions <br /> Fire suppression system for protection of all hazard a have been corrected In a manner acceptable to Installer. <br /> sociated with cooking operations,Including exhaust hoods,plenums, 3R INSTALLATION <br /> ductwork,and cooking appliances. <br /> B.The fire system shall be factory assembled,tested,and shipped as A.Install the package In accordance with manufacturer's Instructions, <br /> n complete unit. drawings,written specifications,manufacturer's Installatlon manual, <br /> and all applicable building codes. <br /> C.The following specifications,delivering all capacities scheduled and 3.3 CONNECTIONS <br /> conforming to the design Indicated herein.Alternate layouts or <br /> dimensional changes will not be accepted. A.Electrical connections conform to applcabie requirements In Division <br /> 2.2 COMPONENTS 26 Sections. <br /> A.Exhaust hood fire system components to be factory Installed. 3.4 SYSTEM START-UP <br /> B.Distribution Nozzles A.System start-up is performed by a factory-trained Service <br /> Technician. <br /> 1.Nozzles shall be located to protect the exhaust ducts,plenums, <br /> and aU cooking appliances requiring protection. <br /> 2.AN nozzles shall be equipped with a metal blow off cap.The cap <br /> prevents contamination from entering the pipe network and Is <br /> designed to pop-off upon system discharge,allowing agent to <br /> flow to the protected hazard area. <br /> FOR REFERENCE ONLY <br /> FACILITY DESIGN BY CEI DATE <br /> ✓OBEverett Mexican - Broadway <br /> LOCATION EVERETT, WA, 98201 <br /> /M/M = DATE 6/27/2022 JOB # 5534351 <br /> a oNa®�c; O �/� ■� , - DAY # 6 V)Z4#Ar F BYJDC-85 <br /> R-FV SCALE 1/4' = F-0' <br />