IXINIXRFIF. FOUNDATIONS. ANTI RFINFORrsNC c r1• 16. ELECTRICAL METALLIC TUBING (EMT) OR METAL-CLAD CABLE (MC) SHALL BE USED FOR CONCEALED INDOOR LOCATIONS.
<br /> 1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301. ACI 318. ACI 336,ASTM A184.ASTM A185 AND THE DESIGN 17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90e AND ALL APPROVED ABOVE •
<br /> AND CONSTRUCTION SPECIFICATION FOR CAST-IN-PLACE CONCRETE. GRADE PVC CONDUIT. d ,„„, sh
<br /> 2. UNLESS NOTED OTHERWISE, SOIL BEARING PRESSURE USED FOR DESIGN OF SLABS AND FOUNDATIONS IS ASSUMED TO BE 1000 18. LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT(LIQUID-TITE FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE VIBRATION
<br /> PAT- OCCURS OR FLEXIBILITY IS NEEDED.
<br /> 3. AU.CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH We) OF 3000 psi AT 28 DAYS (THE CONCRETE HAS BEEN
<br /> DESIGNED BASED ON 2500 PSI), UNLESS NOTED OTHERWISE. NO MORE THAN 90 MINUTES SHALL ELAPSE FROM BATCH TIME TO TIME OF SCREW
<br /> CONDUIT AND TUBING FITTINGSFIfT1NGS ARE NOT ACCEPTTAABLE
<br /> SHALL BE THREADED OR COMPRESSION-TYPE AND APPROVED FOR THE LOCATION USED. SET wireless.
<br /> PLACEMENT UNLESS APPROVED BY THE ENGINEER OF RECORD. TEMPERATURE OF CONCRETE SHALL NOT EXCEED 90'f AT TIME OF
<br /> PLACEMENT. 20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL,ANSI/IEEE AND THE 5701 SOUTH SANTA FE DRIVE
<br /> 4. CONCRETE EXPOSED TO FREEZE-THAW CYCLES SHALL CONTAIN AIR ENTRAINING ADMIXIURES. AMOUNT OF AIR ENTRAINMENT TO BE NEC. UTTLETON, CO 80120
<br /> BASED ON SIZE OF AGGREGATE AND F3 CLASS EXPOSURE (VERY SEVERE). CEMENT USED TO BE TYPE II PORTLAND CEMENT WITH A 21. VAREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS
<br /> MAXIMUM WATER-TO-CEMENT RATIO (W/C) OF 0.45. (WIREMOLD SPECMATE WIREWAY).
<br /> 5. ALL STEEL REINFORCING SHALL CONFORM TO ASTM A615.ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASIM A185. ALL 22. SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUIT TYPE E OR EQUAL).
<br /> SPLICES SHALL BE CLASS 'B'TENSION SPLICES, UNLESS NOTED OTHERWISE. ALL HOOKS SHALL BE STANDARD 90 DEGREE HOOKS, 23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON-PERFORATED STRAPS AND HANGERS. EXPLOSIVE
<br /> UNLESS NOTED OTHERWISE. YIELD STRENGTH (Fy) OF STANDARD DEFORMED BARS ARE AS FOLLOWS: DEVICES (i.e. POWDER-ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE UNES OF �
<br /> #4 BARS AND SMALLER THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES. CHANGES IN DIRECTION TO &A,
<br /> ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BOGIES. CONDUIT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE
<br /> #5 BARS AND LARGER 60 ksi MANNER. PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEIUNG UNES.ALL CONDUIT SHALL BE FISHED TO CLEAR
<br /> OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO PREVENT CONCRETE, PLASTER OR DIRT
<br /> 6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE ON FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY GALVANIZED MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED 1000 HOLCOMB WOODS PION,
<br /> DRAWINGS: MAI I Few F IRON LOCKNUT ON OUTSIDE AND INSIDE. ROSWELL,UGA ITEE210007s
<br /> • CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3' 24. EQUIPMENT CABINETS,TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY-COATED SHEET 678-280-2325
<br /> • CONCRETE EXPOSED TO EARTH OR WEATHER: STEEL SHALL. MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND NEMA 3 (OR BETTER) FOR
<br /> EXTERIOR LOCATIONS.
<br /> • #6 BARS AND LARGER 2' 25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY-COATED OR NON-CORRODING; SHALL L MEET OR
<br /> • #5 BARS AND SMALLER 1-1/2" EXCEED UL 514A AND NEMA 0S 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR WILIOt,
<br /> • CONCRETE NOT EXPOSED TO EARTH OR WEATHER: BETTER) FOR EXTERIOR LOCATIONS.
<br /> • SLAB AND WALLS 3/4' 26. NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEW.OS 2 (NEWEST REVISION)AND BE RATED
<br /> NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR LOCATIONS.
<br /> • BEAMS AND COLUMNS 1-1/2' 27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR DISH Wireless LLC. AND '1-
<br /> 7. A TOOLED EDGE OR A 3/4'CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED OTHERWISE, TOWER OWNER BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS. * 55949
<br /> IN ACCORDANCE WITH ACI 301 SECTION 4.2.4. 28. THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS, CABLES AND DISTRIBUTION PANELS IN ACCORDANCE ♦♦��_���!!��!!**1���A
<br /> WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD UFE AND PROPERTY.
<br /> AL
<br /> EaCTRICAL INSTALLATION NOTE 29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW 'DISH Wireless L.L.C.'. /24/20
<br /> 22
<br /> 1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL APPUCABLE 30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED. UBI NUMBER: 604-106-184
<br /> FEDERAL, STATE, AND LOCAL CODES/ORDINANCES. IT IS A HaATOW OF LAW FOR AM/PERSON.
<br /> 2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED UNLESS OF THEY ARE ACTING PPSOFFESSLOONA.ENG DIRECTION
<br /> AND TRIP HAZARDS ARE ELIMINATED. TO ALTER THE DOCUMENT.
<br /> 3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC. DRAWN BY: CHECKED BY:APPROVED BY:
<br /> 4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC. MAM RM MSB
<br /> 4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL AND SHALL CONFORM TO REQUIREMENT OF RFDs REV/: ---
<br /> THE NATIONAL ELECTRICAL CODE.
<br /> 4.2. ALL OVERCURRENT DEVICES SHALT.HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT CIRCUIT CONSTRUCTION
<br /> CURRENT TO WHICH THEY ARE SUBJECTED, 22,000 MC MINIMUM. VERIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT EXCEED THE
<br /> RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT ADOPTED CODE PRE THE DOCUMENTS
<br /> GOVERNING JURISDICTION.
<br /> 5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR, AND TELCO CONDUCTOR OR CABLE SHALL BE
<br /> LABELED WITH COLOR-COOED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2" PLASTIC ELECTRICAL TAPE WITH LW PROTECTION.
<br /> DATE SUBMITTALSDESCRIPTION
<br /> PROTECTION. OR A w rRo e FOR ROM
<br /> ON
<br /> EQUAL). THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA.
<br /> 6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE o aAeV smm tas te
<br /> UCTON
<br /> CONFIGURATION, WIRE CONFIGURATION, POWER OR AIPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i.e. PANEL BOARD AND CIRCUIT
<br /> ID'S).
<br /> 7. PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS.
<br /> 8. TIE WRAPS ARE NOT ALLOWED.
<br /> AkE PROJECT NUMBER
<br /> 9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14 OR LARGER) 22CCDO5N-0032
<br /> WITH TYPE THHW,THWN, THWN-2, XHHW, XHHW-2,THW, THW-Z, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
<br /> LC.
<br /> 10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOROR LARGER) WITH DISHO Wireless ATIO
<br /> (#6 PROJECT INFORMATION
<br /> TYPE THHW,THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
<br /> 11. POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALT. BE MULTI-CONDUCTOR, TYPE SOOW CORD (#14 OR LARGER) UNLESS SESEA001056
<br /> OTHERWISE SPECIFIED. 2408 39th ST
<br /> EVERETT, WA 98201
<br /> 12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI-CONDUCTOR.TYPE TC CABLE (#14 OR LARGER). WITH
<br /> TYPE THAW, THWN, THWN-2, XHHW, XHHW-2, THW,THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. SHEET TITLE
<br /> 13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRAP-STYLE. COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS AND GENERAL NOTES
<br /> BERS (OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75 C (90' C IF AVAILABLE).
<br /> 14. RACEWAY AND GABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEW.. UL ANSI/IEEE AND
<br /> NEC. SHEET NUMBER
<br /> 15. ELECTRICAL METALLIC TUBING (EMT), INTERMEDIATE METAL CONDUIT(IMC), OR RIGID METAL CONDUIT (RMC) SHALL BE USED FOR GN-4
<br /> EXPOSED INDOOR LOCATIONS.