GROUNDING NOTE& <br /> 1. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION AND AC POWER GES'S) SHALL • <br /> BE BONDED TOGETHER AT OR BELOW GRADE, BY TWO OR MORE COPPER BONDING CONDUCTORS IN ACCORDANCE WITH THE NEC. r <br /> 2. THE CONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTIAL RESISTANCE TO EARTH TESTING (PER IEEE 1100 AND 81) FOR d ...sh <br /> GROUND ELECTRODE SYSTEMS.THE CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL GROUND ELECTRODES AS NEEDED TO <br /> ACHIEVE A TEST RESULT OF 5 OHMS OR LESS. <br /> 3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO wireless. <br /> PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT AND PROVIDE TESTING RESULTS. <br /> 4. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR BY 5701 SOUTH SANTA FE DRIVE <br /> BONDING ACROSS THE DISCONTINUITY WITH /6 COPPER WIRE UL APPROVED GROUNDING TYPE CONDUIT CLAMPS. UTTLETON, Co 80120 <br /> 5. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR. STRANDED COPPER CONDUCTORS <br /> WITH GREEN INSULATION, SIZED IN ACCORDANCE WITH THE NEC, SHALL BE FURNISHED AND INSTALLED WITH THE POWER CIRCUITS TO BTS <br /> EQUIPMENT. <br /> 8. EACH CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE MASTER GROUND BAR WITH GREEN INSULATED SUPPLEMENTAL <br /> EQUIPMENT GROUND WIRES, /8 STRANDED COPPER OR LARGER FOR INDOOR B15; /2 BARE SOUD TINNED COPPER FOR OUTDOOR BTS. <br /> 7. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED BACK TO BACK CONNECTIONS ON OPPOSITE SIDE <br /> OF THE GROUND BUS ARE PERMITTED. <br /> 8. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING SHALL BE /2 SOLID TINNED 1000 HOLCOMB WOODS PKWY, <br /> COPPER UNLESS OTHERWISE INDICATED. SUITE 210 <br /> 78-2 <br /> 9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS. RO 6 OA 30076 <br /> 78-280-2325 <br /> 10. USE OF 90' BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45 BENDS CAN BE ADEQUATELY <br /> SUPPORTED. <br /> 11. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE. <br /> 12. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR AND EXTERIOR) SHALL BE FORMED USING HIGH PRESS CRIMPS. 600 <br /> 13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS. it <br /> 14. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE AND THE TOWER GROUND <br /> �� <br /> BAR. <br /> 15. APPROVED ANTIOXIDANT COATINGS (i.e. CONDUCTIVE GEL OR PASTE) SHALL BE USED ON AU.COMPRESSION AND BOLTED GROUND <br /> CONNECTIONS. <br /> 18. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL. 11' <br /> 17. MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND <br /> RING, IN ACCORDANCE WITH THE NEC. ,./24/2022 <br /> 18. BOND ALL METALLIC OBJECTS WITHN 8 ft OF MAIN GROUND RING WITH (1) 12 BARE SOUD TINNED COPPER GROUND UBI NUMBER: 604-106-184 <br /> CONDUCTOR. IT IS A PORTION OF LAW FOR ANY PERSON. <br /> RECTION <br /> 19. GROUND CONDUCTORS USED FOR THE FACILITY GROUNDING AND UGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED OAF A LICENSED PROFESSIONAL ENGTHEY ARE ACTING UNDER'ME INEER <br /> THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR. SUCH AS METALLIC CONDUITS. METAL SUPPORT CUPS OR TO ALIOR 1 s DOCUMENT. <br /> METALLIC <br /> SLEEVES THROUGH WALLS OR FLOORS. WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL <br /> DRAWN BY. CHECKED BY:APPROVED BY: <br /> CONDITIONS, NON-METALLIC MATERIAL SUCH AS PVC CONDUIT SHALL BE USED. WHERE USE OF METAL CONDUIT IS UNAVOIDABLE (i.e.. <br /> NONMETALLIC CONDUIT PROHIBITED BY LOCAL.CODE) THE GROUND CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT. MAN RM MSB <br /> 20. ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE MUST BE#2 BARE SOLID TINNED COPPER IN 3/4" RFDS REV/: --- <br /> NON-METALLIC, FLEXIBLE CONDUIT FROM 24" BELOW GRADE TO WITHIN 3"TO 8"OF CAD-WELD TERMINATION POINT. THE EXPOSED END <br /> OF THE CONDUIT MUST BE SEALED WITH SILICONE CAULK. (ADD TRANSITIONING GROUND STANDARD DETAIL AS WELL). CONSTRUCTION <br /> 21. BUILDINGS WHERE THE MAIN GROUNDING CONDUCTORS ARE REQUIRED TO BE ROUTED TO GRADE THE CONTRACTOR SHALL ROUTE DOCUMENTS <br /> TWO GROUNDING CONDUCTORS FROM THE ROOFTOP.TOWERS.AND WATER TOWERS GROUNDING RING,TO THE EXISTING GROUNDING <br /> STsiEM.THE GROUNDING CONDUCTORS SHALL NOT BE SMALLER THAN 2/0 COPPER. ROOFTOP GROUNDING RING SHALL BE BONDED TO SUBMITTALS <br /> THE EXISTING GROUNDING SYSTEM, THE BUILDING STEEL COLUMNS, UGHTNING PROTECTION sYs,eM,AND BUILDING MAIN WATER UNE REV DATE DESCRIPTION <br /> (FERROUS OR NONFERROUS METAL PIPING ONLY). DO NOT ATTACH GROUNDING TO FIRE SPRINKLER SYSTEM PIPES. A 04/11/11022 IMO FM IMO/ <br /> 0 04/25/2022 calm Fa O NSWAX1nel <br /> A&E PROJECT NUMBER <br /> 22CCDO5N-0032 <br /> DISH Wireless L.L.C. <br /> PROJECT INFORMATION <br /> SESEA00105B <br /> 2408 39th ST <br /> EVERETT, WA 98201 <br /> SHEET TITLE <br /> GENERAL NOTES <br /> SHEET NUMBER <br /> GN-5 <br />