Laserfiche WebLink
SPECIFICATIONS NBG-12LX:Addressable pull station,visible LED. <br /> • Primary input power,120VAC,50/60 Hz,3.0 A;forAFP-200E: ISO-X: Isolator module. <br /> 230 VAC,50/60 Hz, 1.5 A. FMM-1:Monitor module. <br /> • Total Internal 24 VDC Power:5.0 A(total shared power). FMM-101: Monitor module, miniature. <br /> ✓ High-ripple regulated power:1.5 A(suitable for EIA-485 FDM-1:Monitor module,dual,two independent Class B circuits. <br /> devices,except ACM-8R);1.0 A maximum standby. FZM-1: Monitor module,two-wire smoke detectors. <br /> Non-resettable power:500 mA. FCM-1: Control module. <br /> V/ Four-wire smoke detector power 500 mA. FRM-1:Relay module. <br /> ✓ Four built-in notification circuits: FSM-101: Pull station monitor module. <br /> •NAC Circuit 1:2.25 A. XP5-M:Transponder,monitor,5 addressable Class B circuits. <br /> •NAC Circuits 2-4:2.25 A(shared total). XP5-C:Transponder,control/relay,5 addressable Class B cir- <br /> NOTE:with optional APS-6R Power Supply NAC circuits 3& suits. <br /> 4 are expanded to 3.0 A(8.0 A total power). XP6-C:Six-circuit supervised control module. <br /> • Battery charger range:7 AH-18 AH. XP6-MA: Six-zone interface module;connects intelligent alarm <br /> • Charge high rate:29.1 V.Float rate:27.0 V. system to two-wire conventional detection zone. <br /> • Relay contact rating:2.0 A @ 30 VDC. XP6-R:Six-relay(Form-C)control module. <br /> • Cabinet dimensions:16.125"(40.958 cm)high x 14.5"(36.83 XP10-M:Ten-input monitor module. <br /> cm)wide x 5.5"(13.97 cm)deep. XPIQ: Intelligent quad transponder. <br /> SYSTEM CAPACITY COMPATIBLE DEVICES, EIA-232 Port <br /> PRN Series:80-column printer. <br /> • Total programmable input/output points:301 VS4095/S2:Printer,40 column,24 volts.Mounted in external <br /> • Intelligent detectors:99 backbox(order from Keltron, Inc.). <br /> • Addressable monitor/control modules:99 CRT-2:Video display terminal. <br /> • Programmable NAC circuits in panel:4 NAM-232: Network Interface Module to NOTI•FIRE•NETT" <br /> • Programmable software zones:99 wire or fiber models. <br /> • Programmable remote relay/annunciator points:99 COMPATIBLE DEVICES, RS-485 Port <br /> • LCD-80 annunciators per system:4 <br /> • ACS annunciators per system: 10 ACS Series: Remote Serial Annunciator/Control systems. <br /> CONTROLS AND INDICATORS LCD-80:Remote LCD display. <br /> LDM Series: Remote custom graphic driver modules. <br /> 6 LED indicators: AC Power; Fire Alarm; Pre-Alarm;Super- ACM-8R:Remote relay module. Eight Form-C relays. <br /> visory/Security;Alarm Silenced;System Trouble. NIB-96: Network Interface Board. <br /> 21 Membrane Switch Controls:Acknowledge/Step;Silence; RPT-485:Series Repeater,isolator and/or fiber-optic modem. <br /> Evacuate; System Reset; 12-key Alpha pad; 4 cursor keys; UDACT: Universal Digital Communicator. <br /> Enter. PRODUCT LINE INFORMATION <br /> LCD Display:80 characters(4 x 20)with long-life LED back- <br /> light. AFP-200:AFP-200 system.Includes main PC board with dis- <br /> play and keypad, backbox and door(gray), hardware and in- <br /> Data sheets are available for many of the compatible prod- struction manual. 120 VAC. <br /> acts listed below. AFP-200E: Same as AFP-200, but 230 VAC. <br /> COMPATIBLE INTELLIGENT DEVICES AFP-200R:Same as AFP-200,but with red backbox and door. <br /> AFP-200RE:Same as AFP-200R, but 230 VAC. <br /> FSI-851: Ion detector,replaces FSI-751. AFP-200C:Same as AFP-200, but ULC-approved version. <br /> FSI-751: Ion detector. AFP-200RC:Same as AFP-200R,but ULC-approved version. <br /> FSP-851: Photo detector, replaces FSI-751. DR-AFP200*: Replacement door,gray. <br /> FSP-751: Photo detector. DR-AFP200R*: Replacement door,red. <br /> FSP-851 T:Photo detector with 135°F(57°C)thermal element, *Add an E"to end of part number for 230 VAC labeling. <br /> replaces FSP-751 T. SBB-4X:AFP-200 backbox(no door),gray,for replacement only. <br /> FSP-751 T: Photo detector with fixed thermal element. SBB-4XR:AFP-200 backbox(no door),red,for replacement only. <br /> FST-851:Thermal detector, 135°F(57°C),replaces FST-751. CAB-AM: Heavy-duty outer enclosure. Required for marine <br /> FST-751:Thermal detector,fixed. agency approved applications. <br /> FST-851 R:Thermal detector, 135°F (57°C)with rate-of-rise, 4XTM:Plug-in Transmitter Module.Provides municipal box and <br /> replaces FST-751R. remote station connection. <br /> FST-751 R:Thermal detector,fixed and rate-of-rise. RTM-8:Plug-in Relay Transmitter Module.Provides eight Form- <br /> FST-851H: 190°F(88°C)high-temperature thermal detector. C relays, plus transmitter. <br /> FSH-751: HARSHTh photo detector,requires B710HD base, 4XMM:AmmeterNoltmeter. <br /> detector replaces HPX-751. TR-4XG:Gray Trim Ring for semi-flush mounting(TR-4XR for <br /> HPX-751: HARSH TM photo detector, requires B710HD base. red). <br /> LPX-751L:VIEW®laser detector. DP-AFP200:Full-length dead-front panel(required for Cana- <br /> FSD-751PL: Low-flow photo duct detector with housing, re- dian applications). <br /> places FSD-751P. PS Series: Batteries.The AFP-200 requires two 12-volt, 7.0 <br /> FSD-751P: Duct detector,with housing. to 18.0 AH batteries. <br /> FSD-751 RPL:Low-flow photo duct detector with housing and BAT Series:Batteries.The AFP-200 requires two 12-volt,7.0 <br /> relay, replaces FSD-751P. to 18.0 AH batteries. <br /> FSD-751RP: Duct detector,with housing and relay. APS-6R:6.0 A expansion supply(requires BB-17). <br /> B710LPBP:Standard flanged base, package of ten. BB-17:Battery box,required for batteries above 12.0 AH,or if <br /> B501 BP:Standard flangeless base, package of ten. APS-6R is used. <br /> NOTE:Remove `BP"suffix for single pack bases. CHG-120: 120 AH battery charger for use with 25 to 120 AH <br /> B710HD: Base for FSH-751 (HARSHTM)only. batteries. <br /> B224RB:Relay base. 411 Series: Digital Alarm Communicator/Transmitter. <br /> B224B1: Isolator base. VeriFire-CD: Programming kit for PC. Includes a CD with a <br /> B501 BH:Sounder base. variety of VeriFire programs(including VeriFire-200),cable, <br /> B501BHT:Sounder base with temporal sounder. and instructions. <br /> ROM-AFP200SP:Spanish language kit.Includes software IC, <br /> Page 4 of 4 - DN-3783•02/19/04 manual,and labels. <br />