Applications Standards and Codes <br /> Example 1: Expand notification appliance power an additional 6.0 A The FCPS-24S6 and FCPS-24S8 comply with the following stan- <br /> (FCPS-24S6)or 8.0 A(FCPS-24S8). Use up to four Class B (Style dards: <br /> Y) outputs or four Class A (Style Z) outputs (using ZNAC-4). For NFPA 72 National Fire Alarm Code <br /> example, the FACP notification appliance circuits will activate the <br /> FCPS when reverse-polarity activation occurs. Trouble conditions • UL 864 Standard for Control Units for Fire Alarm Systems (NAC <br /> on the FCPS are sensed by the FACP through the notification appli- expander mode) <br /> ance circuit. • UL 1481 Power Supplies for Fire Alarm Systems <br /> Example 2: Use the FCPS to expand auxiliary regulated 24-volt <br /> system power up to 4.0 A(FCPS-24S6)or up to 6.0 A(FCPS-24S8). Agency Listings and Approvals <br /> Both resettable and non-resettable power options are available. These listings and approvals apply to the modules specified in this <br /> Resettable outputs are created by connecting the resettable output document. In some cases, certain modules or applications may not <br /> from the FACP to one or both of the FCPS inputs. be listed by certain approval agencies,or listing may be in process. <br /> Example 3: Use addressable control modules to activate the FCPS Consult factory for latest listing status. <br /> instead of activating it through the FACP notification appliance cir- • UL Listed:S635,S674 <br /> cults. This typically allows for mounting the FCPS at greater dis- <br /> ULC Listed:S635(FCPS-24S6C&FCPS 24S8C) <br /> tances*away from the FACP while expanding system architecture in <br /> various applications. • CSFM Approved:7315-0028:0225 <br /> For example,an addressable control module is used to activate the • MEA:299-02-E <br /> FCPS, and an addressable monitor module is used to sense FCPS • FM Approved <br /> trouble conditions. Local auxiliary power output from the FCPS pro- <br /> vides power to the addressable control module. Ordering Information <br /> NOTE:Addressable FACPs are capable of locating control and monitor FCPS-24S6: 6.0 A, 120 VAC remote charger power supply. <br /> modules at distances of up to 12,500 feet(3,810 meters). Includes main printed circuit board,transformers,enclosure(15"H x <br /> 14.5"W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation <br /> Sync Follower/Generator Note instructions <br /> In some installations, it is necessary to synchronize the flash timing FCPS-24S6C: Same as above,ULC-listed <br /> of all strobes in the system for ADA compliance.Strobes accomplish FCPS-24S6R: Same as FCPS-24S6 with red enclosure <br /> this by monitoring very short timing pulses on the NAC power which <br /> are created by the FACP.When installed at the end of a NAC wire FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply. <br /> run, the FCPS-24S6/-2458 can track (i.e. "follow") the strobe syn- Includes main printed circuit board,transformers,enclosure (15"H x <br /> chronization timing pulses on the existing NAC wire run.This main- 14.5"W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation <br /> tains the overall system flash timing of the additional strobes instructions <br /> attaches to the FCPS. FCPS-24S8: 8.0 A, 120 VAC remote charger power supply. <br /> When the FCPS-24S6/-2458 is configured (via DIP switch settings) Includes main printed circuit board,transformers,enclosure(15"H x <br /> as a "sync follower," the FCPS' NAC outputs track the strobe syn- 14.5"W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation <br /> chronization pulses present at the FCPS' sync input terminal. The instructions <br /> pulses originate from an upstream FACP or other power supply. FCPS-24S8C: Same as above,ULC-listed <br /> When the FCPS-24S6/-24S8 are configured (via DIP switch set- FCPS-24S8R: Same as FCPS-24S8 with red enclosure <br /> tings)as a"sync generator,"the FCPS'sync input terminals are not <br /> used. Rather,the FCPS is the originator of the strobe synchronize- FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply. <br /> tion pulses on the FCPS' NAC outputs. In "sync generator" mode, Includes main printed circuit board,transformers,enclosure(15"H x <br /> the sync type (System Sensor, Wheelock, or Gentex) is selectable 14.5"W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation <br /> via DIP switch settings. instructions <br /> ZNAC-4: Class A(Style Y)NAC option module <br /> EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire <br /> smoke detector power <br /> BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BAT Series <br /> data sheet DN-6933) <br /> PS-1270: Battery, 12-volt,7.0 AH(two required) <br /> ISO 9001 • <br /> MIMES IMLUL1KIIwI <br /> QUALITY SYSTEMS <br /> This document is not intended to be used for installation purposes. <br /> We try to keep our product information up-to-date and accurate. <br /> We cannot cover all specific applications or anticipate all requirements. <br /> All specifications are subject to change without notice. <br /> NOTI PIER NOTIFIERSand System Sensor®are registered trademarks of Honeywell <br /> International Inc.Wheelock©is a registered trademark of Cooper Technol- �w <br /> 12 Clintonville Road ogies Company.Gentex®is a registered trademark of Centex Corpora- <br /> Northford,CT 06472 fen. ` N OT 1 F 1 E R <br /> ©2019 by Honeywell International Inc.All rights reserved.Unauthorized 203.484.7161 use of this document is strictly prohibited. by Honeywell <br /> www.notifier.com Country of Origin:USA <br />