Laserfiche WebLink
THESE OUTLINE SPECIFICATIONS IN CONJUNCTION WITH THE SPRINT STANDARD CONSTRUCTION SPECIFICATIONS, INCLUDING CONTRACT DOCUMENTS AND THE CONSTRUCTION DRAWINGS \) EL <br /> DESCRIBE THE WORK TO BE PERFORMED BY THE CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR MEETING THE REQUIREMENTS OF SPRINT'S "STANDARD CONSTRUCTION <br /> SPECIFICATIONS FOR WIRELESS SITES" IN REGARDS TO ALL WORK COMPLETED. Sprint i <br /> SECTION 11 800 — INSTALLATION OF MULTIMODAL BASE <br /> STATIONS (MMBS) AND RELATED EQUIPMENT SUPPORTING DEVICES: HUBS AND BOXES: 6580 SPRINT PARKWAY <br /> OVERLAND PARK, KS 66251 z <br /> A. INSTALL SUPPORTING DEVICES TO FASTEN ELECTRICAL COMPONENTS SECURELY AND A. AT ENTRANCES TO CABINETS OR OTHER EQUIPMENT NOT �, z <br /> SUMMARY: PERMANENTLY IN ACCORDANCE WITH NEC. HAVING INTEGRAL THREADED HUBS PROVIDE METALLIC o <br /> THREADED HUBS OF THE SIZE AND CONFIGURATION REQUIRED. <br /> A. THIS SECTION SPECIFIES MMBS CABINETS, POWER CABINETS, AND INTERNAL EQUIPMENT B. COORDINATE WITH THE BUILDING STRUCTURAL SYSTEM AND WITH OTHER TRADES. HUB SHALL INCLUDE LOCKNUT AND NEOPRENE 0—RING SEAL. z <br /> INCLUDING BY NOT LIMITED TO RECTIFIERS, POWER DISTRIBUTION UNITS, BASE BAND PROVIDE IMPACT RESISTANT 105 DEGREE C PLASTIC BUSHINGS L <br /> UNITS, SURGE ARRESTORS, BATTERIES, AND SIMILAR EQUIPMENT FURNISHED BY THE C. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, FASTEN ELECTRICAL ITEMS AND TO PROTECT CABLE INSULATION. ~ <br /> COMPANY FOR INSTALLATION BY THE CONTRACTOR (OFCI). THEIR SUPPORTING HARDWARE SECURELY TO THE STRUCTURE IN ACCORDANCE WITH <br /> THE FOLLOWING: B. CABLE TERMINATION FITTINGS FOR CONDUIT W I R E L E S S <br /> B. CONTRACTOR SHALL PROVIDE AND INSTALL ALL MISCELLANEOUS MATERIALS AND PROVIDE 540 W. MADISON ST. u`n <br /> D. ENSURE THAT THE LOAD APPLIED BY ANY FASTENER DOES NOT EXCEED 25 SUITE 1600 <br /> ALL LABOR REQUIRED FOR INSTALLATION EQUIPMENT IN EXISTING CABINET OR NEW 1. CABLE TERMINATORS FOR RGS CONDUITS SHALL BE TYPE o <br /> CABINET AS SHOWN ON DRAWINGS AND AS REQUIRE BY THE APPLICABLE INSTALLATION PERCENT OF THE PROOF TEST LOAD. CRC BY 0—Z/GEDNEY OR EQUAL BY ROX TEC. CHICAGO, IL 60661 D- <br /> MOPS. E. USE VIBRATION AND SHOCK—RESISTANT FASTENERS FOR ATTACHMENTS TO CONCRETE FULLEI�TON <br /> SLABS 2. CABLE TERMINATORS FOR LFMC SHALL BE ETCO - CL2075; <br /> . w <br /> C. COMPLY WITH MANUFACTURERS INSTALLATION AND START-UP REQUIREMENTS OR MADE FOR THE PURPOSE PRODUCTS BY ROXTEC. l <br /> DC CIRCUIT BREAKER LABELING C. EXTERIOR PULL BOXES AND PULL BOXES IN INTERIOR 9600 W.BRYN MAWR AVE.,SUITE 200 0 <br /> ELECTRICAL IDENTIFICATION: INDUSTRIAL AREAS SHALL BE PLATED CAST ALLOY, HEAVY DUTY, ROSEMONT,ILLINOIS 60018 z <br /> A. NEW DC CIRCUIT IS REQUIRED IN MMBSWEATHERPROOF, DUST PROOF, WITH GASKET, PLATED IRON TEL:847-292-0200 <br /> CABINET SHALL BE CLEARLY IDENTIFIED AS TO AX:847-292-0206 � <br /> RRU BEING SERVICED A. UPDATE AND PROVIDE TYPED CIRCUIT BREAKER SCHEDULES IN THE MOUNTING ALLOY COVER AND STAINLESS STEEL COVER SCREWS, F cOA#3151 <br /> 92-0 <br /> BRACKET, INSIDE DOORS OF AC PANEL BOARDS WITH ANY CHANGES MADE TO THE CROUSE—HINDS WAB SERIES OR EQUAL. www.FullertonEngineering.com <br /> SECTION 26 100 — BASIC ELECTRICAL REQUIREMENTS AC SYSTEM. D. CONDUIT OUTLET BODIES SHALL BE PLATED CAST ALLOY WITH DESCRIPTION DATE BY REV m <br /> B. BRANCH CIRCUITS FEEDING AVIATION OBSTRUCTION LIGHTING EQUIPMENT SHALL BE SIMILAR GASKETED COVERS. OUTLET BODIES SHALL BE OF THE 90% REVIEW 7/17/15 BE A <br /> SUMMARY: CLEARLY IDENTIFIED AS SUCH AT THE BRANCH CIRCUIT PANELBOARD. CONFIGURATION AND SIZE SUITABLE FOR THE APPLICATION. FINAL 8/06/15 AS 0 <br /> THIS SECTION SPECIFIES BASIC ELECTRICAL REQUIREMENTS FOR SYSTEMS AND COMPONENTS. PROVIDE CROUSE-HINDS FORM 8 OR EQUAL. <br /> QUALITY ASSURANCE: E. MANUFACTURER FOR BOXES AND COVERS SHALL BE HOFFMAN, o <br /> SQUARE "D", CROUSE-HINDS, COOPER, ADALET, APPLETON, <br /> A. ALL EQUIPMENT FURNISHED UNDER DIVISION 26 SHALL CARRY UL LABELS AND LISTINGS 0-Z GEDNEY, RACO, OR APPROVED EQUAL. <br /> WHERE SUCH LABELS AND LISTINGS ARE AVAILABLE IN THE INDUSTRY. Q <br /> z <br /> B. MANUFACTURERS OF EQUIPMENT SHALL HAVE A MINIMUM OF THREE YEARS EXPERIENCE w <br /> WITH THEIR EQUIPMENT INSTALLED AND OPERATING IN THE FIELD IN A USE SIMILAR TO u� <br /> THE PROPOSED USE FOR THIS PROJECT. SUPPLEMENTAL GROUNDING SYSTEM o <br /> — <br /> C. MATERIALS AND EQUIPMENT: ALL MATERIALS AND EQUIPMENT SPECIFIED IN DIVISION 26 SECTION 26 200 ELECTRICAL MATERIALS AND EQUIPMENTA. FURNISH AND INSTALL A SUPPLEMENTAL GROUNDING SYSTEM TO THE EXTENT A <br /> OF THE SAME TYPE SHALL BE OF THE SAME MANUFACTURER AND SHALL BE NEW, OF INDICATED ON THE DRAWINGS. SUPPORT SYSTEM WITH NON-MAGNETIC STAINLESS H <br /> THE BEST QUALITY AND DESIGN, AND FREE FROM DEFECTS CONDUIT: STEEL CLIPS WITH RUBBER GROMMETS. GROUNDING CONNECTORS SHALL BE TINNEDCOP C o <br /> SUPPORTING DEVICES: A. RIGID GALVANIZED STEEL (RGS) CONDUIT SHALL BE USED FOR EXTERIOR LOCATIONS SOLIDER RE ORWIRE, SICATED INSULATED ZES DCONDUCTORS EXCE TEON THEID AS OTHERWISE PROVIDE TNOTED. <br /> OR . <br /> ABOVE GROUND AND IN UNFINISHED INTERIOR LOCATIONS AND FOR ENCASED RUNS <br /> A. ALL EQUIPMENT FURNISHED UNDER DIVISION 26 SHALL CARRY UL LABELS AND LISTINGS IN CONCRETE. RIGID CONDUIT AND FITTINGS SHALL BE STEEL, COATED WITH ZINC B. SUPPLEMENTAL GROUNDING SYSTEM: ALL CONNECTIONS TO BE MADE WITH CAD - <br /> WHERE SUCH LABELS AND LISTINGS ARE AVAILABLE IN THE INDUSTRY. EXTERIOR AND INTERIOR BY THE HOT DIP GALVANIZING PROCESS. CONDUIT SHALL BE WELDS, EXCEPT AT EQUIPMENT USE LUGS OR OTHER AVAILABLE GROUNDING MEANS m <br /> PRODUCED TO ANSI SPECIFICATIONS C80.1, FEDERAL SPECIFICATION WW-C-581 AND AS REQUIRED BY MANUFACTURER; AT GROUND BARS USE TWO HOLE SPADES WITH <br /> B. MANUFACTURERS OF EQUIPMENT SHALL HAVE A MINIMUM OF THREE YEARS EXPERIENCE SHALL BE LISTED WITH THE UNDERWRITERS' LABORATORIES. FITTINGS SHALL BE NO OX. 5`'527 <br /> WITH THEIR EQUIPMENT INSTALLED AND OPERATING IN THE FIELD IN A USE SIMILAR TO THREADED - SET SCREW OR COMPRESSION FITTINGS WILL NOT BE ACCEPTABLE. RGS <br /> THE PROPOSED USE FOR THIS PROJECT. CONDUITS SHALL BE MANUFACTURED BY ALLIED, REPUBLIC OR WHEATLAND. C. STOLEN GROUND-BARS: IN THE EVENT OF STOLEN GROUND BARS, CONTACT SPRINT �� FCISI <br /> C. MATERIALS AND EQUIPMENT: CM FOR REPLACEMENT INSTRUCTION USING THREADED ROD KITS. SS�ONALtiN� <br /> B. UNDERGROUND CONDUIT IN CONCRETE SHALL BE POLYVI NYLCH LORI DE (PVC) <br /> ALL MATERIALS AND EQUIPMENT SPECIFIED IN DIVISION 26 OF THE SAME TYPE SHALL BE SUITABLE FOR DIRECT BURIAL AS APPLICABLE. JOINTS SHALL BE BELLED, AND FLUSH Q <br /> OF THE SAME MANUFACTURER AND SHALL BE NEW, OF THE BEST QUALITY AND DESIGN, SOLVENT WELDED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. CONDUIT <br /> AND FREE FROM DEFECTS SHALL BE CARLON ELECTRICAL PRODUCTS OR APPROVED EQUAL. SITE NAME z <br /> SUPPORTING DEVICES: C. TRANSITIONS BETWEEN PVC AND RIGID (RGS) SHALL BE MADE WITH PVC COATED EXISTING STRUCTURE: cn <br /> A. MANUFACTURED STRUCTURAL SUPPORT MATERIALS: SUBJECT TO COMPLIANCE WITH METALLIC LONG SWEEP RADIUS ELBOWS. EVERETT o <br /> REQUIREMENTS, PROVIDE PRODUCTS BY THE FOLLOWING: D. EMT OR RIGID GALVANIZED STEEL CONDUIT MAY BE USED IN FINISHED SPACES A. EXISTING EXPOSED WIRING AND ALL EXPOSED OUTLETS, RECEPTACLES, SWITCHES, BAKERVIEW APTS <br /> DEVICES, BOXES, AND OTHER EQUIPMENT THAT ARE NOT TO BE UTILIZED IN THE <br /> 1. ALLIED TUBE AND CONDUIT CONCEALED IN WALLS AND CEILINGS. EMT SHALL BE MILD STEEL, ELECTRICALLY COMPLETED PROJECT SHALL BE REMOVED OR DE-ENERGIZED AND CAPPED IN THE '-`' <br /> WELDED, ELECTRO-GALVANIZED OR HOT-DIPPED GALVANIZED AND PRODUCED TO WALL, CEILING, OR FLOOR SO THAT THEY ARE CONCEALED AND SAFE. WALL, CEILING, SI E NJVOER o <br /> 2. B-LINE SYSTEM ANSI SPECIFICATION C80.3, FEDERAL SPECIFICATION WW-C-563, AND SHALL BE UL OR FLOOR SHALL BE PATCHED TO MATCH THE ADJACENT CONSTRUCTION. CL <br /> LISTED. EMT SHALL BE MANUFACTURED BY ALLIED, REPUBLIC OR WHEATLAND, OR <br /> 3. SUNISTRUT DIVERSIFIED PRODUCTS APPROVED EQUAL. FITTINGS SHALL BE METALLIC COMPRESSION. SET SCREW SE82XCO80 <br /> CONNECTIONS SHALL NOT BE ACCEPTABLE. O <br /> 4. THOMAS & BETTS AUGMENT I-A. <br /> E. LIQUID TIGHT FLEXIBLE METALLIC CONDUIT SHALL BE USED FOR FINAL CONNECTION = <br /> B. FASTENERS: TYPES, MATERIALS, AND CONSTRUCTION FEATURES AS FOLLOWS: TO EQUIPMENT. FITTINGS SHALL BE METALLIC GLAND TYPE COMPRESSION FITTINGS, CONDUIT AND CONDUCTOR INSTALLATION: WA—SNO208E14.1 <br /> MAINTAINING THE INTEGRITY OF CONDUIT SYSTEM. SET SCREW CONNECTIONS SHALL <br /> 1. EXPANSION ANCHORS: CARBON STEEL WEDGE OR SLEEVE TYPE. NOT BE ACCEPTABLE. MAXIMUM LENGTH OF FLEXIBLE CONDUIT SHALL NOT EXCEED SITE ADDRESS Q <br /> 6-FEET. LFMC SHALL BE PROTECTED AND SUPPORTED AS REQUIRE BY NEC. A. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED o <br /> 2. POWER-DRIVEN THREADED STUDS: HEAT-TREATED STEEL, DESIGNED SPECIFICALLY FOR MANUFACTURERS OF FLEXIBLE CONDUITS SHALL BE CAROL, ANACONDA METAL HOSE NON-PERFORATED STRAPS AND HANGERS. EXPLOSIVE DEVICES FOR ATTACHING z <br /> THE INTENDED SERVICE. OR UNIVERSAL METAL HOSE, OR APPROVED EQUAL. HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE LINES OF 2605 15TH ST <br /> THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP EVERETT, WA 98201 Q <br /> 3. FASTEN BY MEANS OF WOOD SCREWS ON WOOD. F. MINIMUM SIZE CONDUIT SHALL BE 3/4 INCH (21 MM). CONDUITS IN TIGHT ENVELOPES. CHANGES IN DIRECTION TO ROUTE AROUND z <br /> OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES. CONDUIT SHALL BE o <br /> 4. TOGGLE BOLTS ON HOLLOW MASONRY UNITS. INSTALLED IN A NEAT AND WORKMANLIKE MANNER, PARALLEL AND PERPENDICULAR SI I:FT NAM <br /> TO STRUCTURE WALL AND CEILING LINES. ALL CONDUIT SHALL BE FISHED TO CLEAR z <br /> 5. CONCRETE INSERTS OR EXPANSION BOLTS ON CONCRETE OR SOLID MASONRY. OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED TO PREVENT < <br /> CONCRETE, PLASTER OR DIRT FROM ENTERING. CONDUITS SHALL BE RIGIDLY SPRINT W <br /> 6. MACHINE SCREWS, WELDED THREADED STUDS, OR SPRING-TENSION CLAMPS ON CLAMPED TO BOXES BY GALVANIZED MALLEABLE IRON BUSHING ON INSIDE AND rr <br /> STEEL. GALVANIZED MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE. SPECIFICATIONS Q <br /> I <br /> 7. EXPLOSIVE DEVICES FOR ATTACHING HANGERS TO STRUCTURE SHALL NOT BE B. CONDUCTORS SHALL BE PULLED IN ACCORDANCE WITH ACCEPTED GOOD PRACTICE. z <br /> PERMITTED. SI I:FT NL,MBER <br /> s <br /> u <br /> u <br /> 8. DO NOT WELD CONDUIT, PIPE STRAPS, OR ITEMS OTHER THAN THREADED STUDS TO Ll <br /> o <br /> STEEL STRUCTURES. P 2 <br /> w <br /> 9. IN PARTITIONS OF LIGHT STEEL CONSTRUCTION, USE SHEET METAL SCREWS. <br />