My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
1605 EDGEMOOR LN 2025-04-25
>
Address Records
>
EDGEMOOR LN
>
1605
>
1605 EDGEMOOR LN 2025-04-25
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/25/2025 3:15:49 PM
Creation date
3/21/2025 9:56:04 AM
Metadata
Fields
Template:
Address Document
Street Name
EDGEMOOR LN
Street Number
1605
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
87
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Structural: <br /> 1. Please consider biaxial bending on the PT columns and lateral action on the immediate <br /> connections according to the appropriate tributary seismic weight. At a minimum, the inertial <br /> force due to the weight of the 5%x 15 and half the weight of the columns will not be resolved by <br /> the deck diaphragm, ledger connection and existing shear wall system internal to the building. <br /> Additionally, the Simpson Wood Construction Connectors Catalogue does not provide a lateral <br /> capacity for the CCQ column caps nor the CBSQ column bases provided between the GL beam and <br /> the columns. Please provide rationale for your assumptions at these joints for the lateral design. <br /> 2. Detail 4/SC6 does not include dimensions for concrete cover. Please provide the appropriate <br /> concrete cover to the reinforcement within the pilaster. Also, it is recommended that (3) #3 <br /> transverse ties are placed in the first 5" of the concrete pilaster foundation below the timber <br /> columns. Though no anchor bolts are present, confinement reinforcement should be considered <br /> —see Section 10.7.6.1.6 ACI 318-14 for basis of rationale. <br /> In order for the processing of your application to continue, it will be necessary to provide the Building <br /> Division with two new sets of revised construction documents reflecting the corrections requested. <br /> Please include a response letter which indicates how the corrections were resolved. <br /> All required submittals must be of sufficient detail and information to ensure that the proposed structure <br /> will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Benjamin Monk, PE <br /> Building Plans Reviewer I City of Everett Public Works <br /> 3200 Cedar Street © 425.257.8810 O rhammer@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov <br />
The URL can be used to link to this page
Your browser does not support the video tag.