Installation Accessories <br /> Signature Series detectors mount to North American 1-gang All detector mounting bases have wiring terminals that are acces- <br /> boxes,3-1/2 inch or 4 inch octagon boxes, and to 4 inch square sible from the"room-side"after mounting the base to the electri- <br /> electrical boxes 1-1/2 inches(38 mm)deep.They mount to Euro- cal box.The bases mount to North American 1-gang boxes and <br /> pean BESA and 1-gang boxes with 60.3 mm fixing centers. to 31/2 inch or 4 inch octagon boxes, 11/2 inches(38 mm)deep. <br /> They also mount to European BESA and 1-gang boxes with 60.3 <br /> mm fixing centers.The SIGA-SB4, SIGA-RB4, and SIGA-I134 <br /> 0.8'(20 mm) mount to North American 4 inch sq.electrical boxes in addition to <br /> the above boxes.They include the SIGA-TS4 Trim Skirt which is <br /> used to cover the"mounting ears"on the base.The SIGA-AB4G <br /> 2.0"(51 mm) mounts to a 4"sgare box only. <br /> 4.4"012 mm) <br /> Tamper-Resist Lever Arm ® SIGA-AB4G/T/LF SIGA-SB SIGA-IB SIGA-RB SIGA-LED <br /> -Break off to disable- ® Audible Base Standard Base Isolator Base Relay Base Remote LED <br /> (Located on Base) <br /> Standard Base SIGA-SB,SIGA-SB4-This is the basic mount- <br /> ing base for EDWARDS Signature Series detectors.The SIGA- <br /> Access Slot for ' LED Remote LED is supported by the Standard Base. <br /> Tamper-Resist Mechanism ` t <br /> _ Relay Base SIGA-RB,SIGA-RB4-This base includes a relay. <br /> Normally open or closed operation is selected during installation. <br /> CD The dry contact is rated for 1 amp(pilot duty)C 30 Vdc.The relay's <br /> position is supervised to avoid accidentally jarring it out of position. <br /> The SIGA-RB can be operated as a control relay if programmed <br /> Testing & Maintenance to do so at the control panel(EST3 V.2 only).The relay base does <br /> not support the SIGA-LED Remote LED. <br /> Each detector automatically identifies when it is dirty or defective Audible Base SIGA-AB4G -This base is designed for use where <br /> and causes a"dirty detector"message.The detector's sensitiv- localized or group alarm signaling is required.When the detector <br /> ity measurement can also be transmitted to the loop controller.A senses an alarm condition,the audible base emits a local alarm <br /> sensitivity report can be printed to satisfy NFPA sensitivity meas- signal.The optional SIGA-CRR Polarity Reversal Relay can be used <br /> urements which must be conducted at the end of the first year for sounding to other audible bases on the same 24 Vdc circuit. <br /> and every two years thereafter. Relay and Audible Bases operate as follows: <br /> The user-friendly maintenance program shows the current state -at system power-up or reset,the relay is de-energized <br /> of each detector and other pertinent messages. Single detectors -when a detector is installed in the base with the power <br /> may be turned off temporarily from the control panel.Availability of on,the relay energizes for four seconds,then de-energizes <br /> maintenance features is dependent on the fire alarm system used. -when a detector is removed from a base with the power on, <br /> Scheduled maintenance(Regular or Selected)for proper detec- the relay is de-energized <br /> for operation should be planned to meet the requirements of the <br /> Authority Having Jurisdiction(AHJ). Refer to current NFPA 72 and -when the detector enters the alarm state,the relay is energized. <br /> ULC CAN/ULC 536 standards. Isolator Base SIGA-IB,SIGA-I134-This base includes a built-in <br /> line fault isolator for use on Class A circuits.A detector must be <br /> installed for it to operate.The isolator base does not support the <br /> Compatibility SIGA-LED Remote LED. <br /> The SIGA-PS detectors are compatible only with the Signature The isolator operates as follows: <br /> Loop Controller. -a short on the line causes all isolators to open within 23 msec <br /> -at 10 msec intervals, beginning on one side of the Class A <br /> circuit nearest the loop controller,the isolators close to <br /> provide the next isolator down the line with power <br /> Warnings & Cautions -when the isolator next to the short closes,reopens within 10 <br /> This detector will not operate without electrical power.As fires fre- msec. <br /> quently cause power interruption,we suggest you discuss further The process repeats beginning on the other side of the loop <br /> safeguards with your fire protection specialist. controller. <br /> This detector will NOT sense fires that start in areas where smoke Remote LED SIGA-LED-The remote LED connects to the <br /> cannot reach the detector.Smoke from fires in walls, roofs,or on SIGA-SB or SIGA-SB4 Standard Base only. It features a North <br /> the opposite side of closed doors may not reach the detector to American size 1-gang plastic faceplate with a white finish and red <br /> alarm it. alarm LED. <br /> SIGA-TS4 Trim Skirt-Supplied with 4 inch bases, it can also <br /> be ordered separately to use with the other bases to help hide <br /> surface imperfections not covered by the smaller bases. <br /> Page 2 of 4 DATA SHE, E85001-0269 <br /> Not to be used for instal, I purposes. Issue 1 <br />