Laserfiche WebLink
FEEDER SCHEDULE-Copper(Cu) N <br /> GENERATOR LOAD CALCULATIONS DIALYSIS BLDG LOAD CALCULATIONS GENERAL NOTES: o <br /> EQUIPMENT I Z <br /> CALLOUT FEEDER(C.) GROUNDING CONDUIT AMPACITV 1. ALL CONDUCTORS SHALL BE COPPER. <br /> - <br /> CONDUCTOR(EGC)- DIALYSIS BLDG(PEAK DEMAND) 159 KW 30 DAY PEAK DEMAND 160 KW v <br /> TABLE 250.122 to" <br /> CORPORATE BLDG IT PANEL 13 KW POWER FACTOR AT.95 168 KVA �!EO i <br /> 603 406 1N10 1. 65 25%NEC ADDER 42 KVA m Q <br /> loon 4N3 1N6 1.5" 100 DETAIL NOTES: <br /> TOTAL LOAD 210 KVA <br /> 12004 (3)4n600KCMIL 4N3/0 (3)4" 1260 TOTAL 172 KW OR 583 AMPS AT 208V,3PH D REMOVE EXISTING GROUNDING ELECTRODE SYSTEM(I.E.SYSTEM BONDING <br /> 8004 (2)4#600KCMIL 1#2/0 (2)4- s40 JUMPER)OR MODIFY EXISTING EQUIPMENT AS REQUIRED TO ACCOMMODATE NEW <br /> GROUNDING ELECTRODE SYSTEM LOCATED IN NEW MAIN DISCONNECT.FIELD <br /> VERIFY PRIOR TO BID. <br /> DPROVIDE NEW CONCRETE PADS FOR SWITCHBOARD. <br /> D PROVIDE(N)UTILITY CO PULSE OUTPUT METER(VERIFY). 2727 Oakes Ave. <br /> its 100 <br /> D INTERCEPT(E)FEEDER TO IT ROOM PANEL&RECONNECT AS REQUIRED. Everett,WA 98201 <br /> 0 <br /> R1 W ono D CONTRACTOR SHALL STUB CONDUITS THRU(E)EAST WALL OF DIALYSIS REVISIONS <br /> = ov <br /> BUILDING TO GARAGE LEVEL,INSPECT SITE BEFORE BIDDING. ,+�„+v0 v X <br /> �Mn <br /> DREPAIR ALLEY SURFACE TO MEET CITY OF EVERETT REQUIREMENTS. _ U)0 N <br /> a <br /> DPROVIDE GRS LB'S AND PENETRATE THRU WALL.WEATHERPROOF AROUND <br /> CONDUIT, 3 3 0 <br /> D LOCATE A.T.S.ON INTERIOR NORTH WALL OF(E)ELECT.ROOM,42 KAIC RATED. = q o� <br /> t` <br /> ad <br /> D DRIVE(N)GROUND RODS&CONNECT TO SWBD AS REQUIRED. V ¢ n <br /> 10 LOCATE(N)ATS ON SOUTH FACE OF(E)CONCRETE WALL. M C V3 �( A. <br /> 11 MAIN BREAKER MAY BE MOUNTED ON OTHER SIDE OF C.T.ENCLOSURE IF WALL y ��d"'q�'+q�C' <br /> SPACE IS AVAILABLE. dt O C o <br /> W a .] m T <br /> gH BLOCK HEATER-120V,60OW <br /> � A <br /> gC BATTERY CHARGER-120V,40OW eSSkONAI EN�� <br /> CP CONTROL PANEL <br /> © GROUND <br /> �N NEUTRAL <br /> (E)SWITCHBOARD"MSB" <br /> 1200A 120/208V,3PH - 65 KAIC <br /> (E)FEEDER <br /> 200KW DIESEL 1004 (N) <br /> STANDBY GENERATOR 208Y/12OV,3PH <br /> FIRST FLOOR LEVEL CTRL PN <br /> PNL 4 8 PNL D <br /> (N)MAIN SWITCHBOARD MS (N)CONCRETE PAD (7 4 (E)FEEDER TO IT 42 KAIC <br /> 11 1200A 120/208V,3P,4W _ g SEE ARCH. )800/3 )100/3 J J ROOM PANEL D <br /> 65,000AIC - TO(E) <br /> ALLEY 7 PANEL H CP 100A,3P W <br /> (N) 1200 BH BC 3/4"C,4#12 CKTS 14/16 ATS <br /> 1200 (N) 10 (E)ELECT RM (E)SERVER RM LL- O <br /> GRADE LEVEL GRADE LEVEL AT NW CORNER GARAGE LEVEL <br /> — — <br /> O 800A 3P N <br /> I / I I I I I I I I <br /> AUTOMATIC STANDBY (E)RETAINING WALL <br /> 1200A CTS M TRANSFER SWITCH L------I--- ___+�-- -----------------� 7 > <br /> 50 KAIC <br /> - ------------------ <br /> 1200A 3 -------------------------------I- -T <br /> FUSES ------------------------------- L----- ------------------ -J U W� <br /> 1"C",CONTROL WIRES 1004 GRS ELBOWS <br /> 5 AS NECESSARY <br /> X ��z _z <br /> CP r /� <br /> w GARAGE LEVEL G N v / � <br /> (E) ,2QQS - 8004 cN) (E) CORPORATE BLDG �o w <br /> REMOVE 1019 PACIFIC AVE. EVERETT <br /> —a (E)CT ENCL ' NO.AND(E)METER roe. 20056.A <br /> r-N el LRD <br /> (E) DIALYSIS BLDG IIECMEaev BA <br /> 1005 PACIFIC AVE., EVERETT <br /> 5/10/2021 <br /> ONE LINE DIAGRAM <br /> ONE—LINE <br /> NOT TO SCALE DIAGRAM <br /> E2 � 0 <br />