a
<br /> Panel D(EXIST)42 kAIC PANEL SCHEDULE jPR.1E.1 PSKC-EVERETT
<br /> DETAIL NOTES:
<br /> 120/208V,3Ph,4W. 1 ODA Bus M.L.O. SURFACE MOUNTED 10-May-21 Uj
<br /> Ckt. Description/ Load Load C.B. C.B. C.B. C.B. Load Load Description/ Ckt. 6 a-
<br /> No. Location (VAD Type Amp Pole Phase Amp Pole VA Type Location No. D CUTOVER(E)SPLIT SYSTEM AIR CONDITION IN(E)SERVER ROOM TO PANEL D z
<br /> AS SHOWN.PROVIDE(N)CIRCUIT BREAKER TO MATCH EXISTING TYPE AND
<br /> 1 UPS 1,200 R 30 2 A 30 2 1,400 G SPLIT SYSTEM PJC(EXIST) 2 < STYLE.PROVIDE CONDUIT AND#10 COPPER WIRE AS NECESSARY. U
<br /> 3 - 1,200 R - - IS - - 1,400 G (RECONNECT EXIST FEEDERS) 4 to�.
<br /> 5 UPS 1,200 R 30 2 C 30 2 SPARE 6 Q7!E
<br /> 7 - 1,200 R - - A - - - a 15 2
<br /> 9 GENERAL REC. 360 R 20 1 B 20 1 SPARE 10
<br /> 11 GENERAL REC. 360 R 20 1 C 20 1 SPARE 12
<br /> 13 SERVER REC. 1,500 R 20 1 A 20 1 SPARE 14
<br /> 15 SERVER REC. 1,500 R 20 1 B 20 1 SPARE 16
<br /> 17 SERVER REC. 1,500 R 20 1 C 20 1 SPARE 18
<br /> 19 SERVER LTG 256 L 20 1 A 20 1 SPARE 20
<br /> 21 SPARE 20 1 B 20 1 SPARE 22
<br /> 23 SPARE 20 1 C 20 1 SPARE 24
<br /> 25 SPARE 20 1 A 20 1 SPARE 26
<br /> 27 SPARE 20 1 B SPACE 28
<br /> 29 SPARE 20 1 C SPACE 30 2727 Oakes Ave.
<br /> 31 SPARE 20 1 A SPACE 32 Suite 100
<br /> 33 SPARE 20 1 B SPACE 34 O Everett,WA 98201
<br /> 35 SPARE 20 1 C SPACE 36
<br /> 37 SPD 30 3 A SPACE 38 W REVISIONS
<br /> y
<br /> 39 - - - B SPACE 40 t0 X
<br /> 41 - - - C SPACE 42 y In MO I,-'-
<br /> �+
<br /> 00
<br /> Total Connected Load: Ph A 5,556 VA 46 A
<br /> Total Connected Load: Ph B 4,460 VA 37 A O
<br /> Total Connected Load: Ph C 3,060 VA 26 A
<br /> Total Connected Load: 13.1 KVA Total Demand Load: 13.1 KVA U) D C
<br /> 36.3 AMPS 36.5 AMPS r o
<br /> Connected Subfed Total Demand Demand
<br /> G General(Non-Continuous) Loads 2 800 Loads(S) Loads 2 80 Factor 0 M
<br /> Load 2 80 A. q
<br /> L Lighting 256 256 125% 320 M 1r7 r: d WAS''/tiOC�
<br /> R Receptacles-to 10 KVA 10,020 10,000 100% 10,000 Accessories:
<br /> ver 10 KVA 20 50% 10 O\ y g n
<br /> K Kitchen 0 0 100% 0 W '"'a� m
<br /> H Heating 0 0 100% 0
<br /> M Motors 0 0 100% 0
<br /> LM Largest
<br /> WH Water Heatterr 0 0 125% 0 _. , e�IONAL ENC�
<br /> C Continuous General Load 0 0 125% 0
<br /> 13,076 VA 0 VA 13,076 VA 13,130 VA
<br /> NOTES:
<br /> BOLD TYPE INDICATES LOAD NEW TO THIS PANEL
<br /> Panel H(EXIST)42kAIC PANEL SCHEDULE JPR.el PSKC-EVERETT
<br /> 120/208V,3Ph,4W. 100A Bus M.L.O. SURFACE MOUNTED 10-May-21
<br /> Ckt. Description/ Load Load C.B. C.B. C-B. C.B. Load Load Description/ Ckt.
<br /> No Location A Type Amp Pole Phase Amp Pole A Type Location No
<br /> 1 FACP 500 G 20 1 A 20 1 1,656 M EF-3 2
<br /> 3 ELECTRIC WALL HEATER 1,000 H 2C 1 B 20 1 1,656 M EF-4 4
<br /> 5 MAIN TTB REC. 360 R 20 1 C 20 1 135 M EF-5 6
<br /> 7 GENERAL REC. 900 R 20 1 A 20 1 250 WH GAS WATER HEATER&CIRC PUMP 8
<br /> 9 ELECTRIC WALL HEATER 1,000 H 20 1 B 20 1 100 G CO CONTROLLER 10
<br /> 11 SPARE 20 1 C 20 1 450 L EXTERIOR NORTH PARKING LIGHTING 13 ELEVATOR PIT LTG&REC. 308 R 20 1 A 20 1 400 G GENERATOR BATERY CHARGER 14 W
<br /> 15 ELEVATOR MACHINE ROOM REC.<G 244 R 20 1 B 20 1 600 G GENERATOR BLOCK HEATER 16
<br /> 17 PARKING GARAGE LTG 864 L 20 1 C 20 1 SPARE
<br /> 19 ELEC./RISER ROOM LTG 192 L 20 1 A 20 1 SPARE 20
<br /> 21 GENERAL REC. 360 R 20 1 B 20 1 SPARE 22 LLI
<br /> 23 STAIR LTG 256 L 20 1 C 20 1 SPARE 24
<br /> 25 EXTERIOR SITE LTG 500 L 20 1 A 20 1 SPARE 26
<br /> 27 EXTERIOR LIGHTING 332 L 20 1 B 20 1 SPARE 28 >
<br /> 29 EXTERIOR BUILDING LIGHTING 156 L 20 1 C 20 1 SPARE 30 W E]:�Q
<br /> 31 SPACE A SPACE 32
<br /> 33 SPACE B SPACE 34 L I�
<br /> 35 SPACE C SPACE 36 W
<br /> 37 SPACE A SPACE 38 \ / -Z Q
<br /> 39 SPACE B SPACE 40 �/ � �
<br /> 41 SPACE C SPACE 42
<br /> Total Connected Load: Ph A 4,706 VA 39 A
<br /> Total Connected Load- Ph B 5,292 VA 44 A
<br /> Total Connected Load_ Ph C 2,221 VA 19 A
<br /> Total Connected Load: 122 KVA Total Demand Load: 130 KVA
<br /> 33-9 AMPS 36.0 AMPS
<br /> JOB,na. 20056.A
<br /> Connected Subled Total Demand Demand -NBr LRD
<br /> Loads Loads(S) Loads Factor Load
<br /> G General(Non-Cortinuous) 1 600 1,600 100% 1,600
<br /> L Lighting 2,750 2,750 125% 3,438 caECKED BY BA
<br /> R Receptacles-to 10 KVA 2,172 2,172 100% Z172 Accessories
<br /> over 10 KVA 0 50% 0
<br /> K IOtchen 0 0 100% 0
<br /> H Heating 2,000 2,000 100% 2.000
<br /> M Motors 3,447 3,447 100% 3,447
<br /> LM Largest Motor 0 0 125% 0 5/11/2021
<br /> WH Water Heater 250 250 125% 313
<br /> C Continuous General Load 0 0 125% 0
<br /> 12,219 VA 0 VA 12219 VA 12969 VA
<br /> NOTES PANEL
<br /> BOLD TYPE INDICATES NEW ITEM SCHEDULES
<br /> E3 , 0
<br />
|