511.9.3 All other active components shall be checked to determine that <br /> they are operating within the manufacturer's specifications for the intended <br /> purpose. <br /> 511.10 Five year signal strength testing. <br /> 511.10.1 In addition to the annual test, the building owner shall perform a <br /> radio coverage test a minimum of once every five years to ensure that the <br /> radio system continues to meet the signal strength requirements of the <br /> original acceptance test. The signal levels established in Section 511.4 and <br /> the procedures established in Section 511.8 shall apply to such tests. The <br /> results of the five-year test will be provided to SERS and the Fire Code <br /> Official by certified mail. Test records shall also be retained on the <br /> inspected premises by the building owner. <br /> 511.10.2 The building owner shall notify the SERS System Manager in <br /> writing two weeks in advance of the initial, annual, and five-year tests. <br /> 511.11 Qualifications of testing personnel.Tests shall be conducted, <br /> documented and signed by a person in possession of a current FCC license, or a <br /> current technician certification issued by the Associated Public-Safety <br /> Communications Officials International (APCO), the Personal Communications <br /> Industry Association (PCIA), or a technician employed by SERS. <br /> 511.12 Field testing. Public safety personnel, after providing reasonable notice <br /> to the building owner or his representative, shall have the right to enter onto the <br /> property to conduct ad-hoc field testing to be certain that the required level of <br /> radio coverage is present. <br /> Section 5: Section 7 of Ordinance No. 2985-07 (EMC 16.03.070), is hereby amended by <br /> the addition of the following new subsection"E": <br /> E. Subsection 903.2.10 of the IFC, entitled "Windowless stories in all occupancies," <br /> is hereby amended by the addition of the following language at the end of Section <br /> 903.2.10: "This requirement applies retroactively to existing buildings." <br /> Section 6: Section 8 of Ordinance No. 2985-07 (EMC 16.03.080), which reads as <br /> follows: <br /> AMENDMENTS TO THE IFC CHAPTER 10, MEANS OF EGRESS <br /> A. Subsection 1018.1 of the IFC, entitled "Minimum number of exits," is hereby <br /> amended by the addition of the following new subsection 1018.1.3: <br /> 22 <br />