Laserfiche WebLink
➢ The Fire Alarm System will have backup power sources of two 12vdc, 18amp batteries wired in series <br />for 24vdc operation, capable of meeting/exceeding the 60 hr standby period followed by 5 minutes of <br />alarm at maximum system load. <br />➢ Copies of Fire Marshal approved, stamped, signed drawings along with a complete user's manual will be <br />left with the Store Manager for their reference and all future annual inspections. Store personnel will be <br />provided training on proper use of the Fire Alarm System by the installation contractor. <br />➢ A complete zone list/device address chart will be provided. An NFPA Record of Completion will be <br />submitted. As -Built (Record) drawings will be generated upon completion of a successful final <br />inspection and copies will be provided to the customer and kept on file with ADT Security Services. <br />AT Home # 334 <br />8-18-2022 <br />