<br />FIRE WRAP SPEC SHEET
<br />U Morgan U Morgan U Morgan U Morgan
<br />CAdvanced Materials F/Rf({�gS'TfR C Advanced Materials Affl"S'7ER- C Advanced Materials FIR"ER C Advanced Materials
<br />Datasheet Code US: 714-236
<br />© 2014 Thermal Ceramics is a business of Morgan Advanced Materials
<br />ICC
<br />U C Fs
<br />L �
<br />Q U
<br />OL
<br />LISTED
<br />�Commonry rearreato test method CA Scton wasp is CDPH standard Method forme Testing
<br />and Evaluation of Volatile Omanic Chemical Emissions from Indoor sources Using Environmental
<br />Chambers Version 1.1,Felf
<br />Grease Duct Enclosure System
<br />Air Ventilation Duct Enclosure System
<br />Product Data & Installation Guide
<br />1. Product Description
<br />Thermal Ceramics FireMaster® FastWrap XL is a flexible
<br />blanket composed of high temperature fibers classified for
<br />applications to 2192°F (1200°C) and fully encapsulated in
<br />a durable glass fiber reinforced foil facing for easy handling
<br />and installation. Thermal Ceramics FastWrap XL is UL and
<br />ULC Listed for Land 2 hour fire resistive enclosure
<br />protection, zero clearance for kitchen exhaust ducts,
<br />electrical circuit protection, and as a component in UL
<br />firestop designs for fire resistance rated floors, ceilings, and
<br />walls. The core fibers in FastWrap XL are manufactured
<br />using Thermal Ceramics patented Superwool® fiber which is
<br />an alkaline -earth silicate wool with low biopersistence and
<br />therefore increased safety for installers. FastWrap XL is
<br />under UL's Follow -Up Service Program to ensure the
<br />consistent quality essential to this life -safety application.
<br />Product Features
<br />• Thin and Lightweight at 1-1/2" (38mm) thick,
<br />6 pcf (96 kg/ri density
<br />• Contours easily to complex duct designs
<br />• Grease duct installation UL and ULC Listed with butt
<br />joints at all seams on both layers
<br />• Fully foil encapsulated for fast and clean installation
<br />• Contains 2192°F (1200°C) rated fibers
<br />• Microbial Resistance validated by UL Environment
<br />• Good sound absorption
<br />• Compliant to IMC, NFPA 96, UMC, CMC, CNBC
<br />2. Applications
<br />• 2 hour enclosure and firestop system stem for kitchen
<br />exhates duct
<br />• Zero clearance to combustibles
<br />• 1 2 and 3 hour enclosure and firestop system stem for
<br />hazardous exhaust ducts, pressurization ducts, clothes
<br />dryer exhaust ducts, trash and linen chutes, and other
<br />fire rated HVAC ducts
<br />• 1 hour electrical circuit Y
<br />inte rit protection
<br />9
<br />• Engineered and tested solutions for fire protection of
<br />structural steel and storage vessels per ASTM El 19,
<br />ISO 834, and UL1709
<br />3. Specifications - Division 23 07 00 (or 15080)
<br />CSI Spec and AutoCAD available online,
<br />www.arcat.com/sd/clients/thermcer.html.
<br />Thermal Ceramics FireMaster FastWrap XL is a flexible
<br />high temperature insulation rated to 2192°F (1200°C)
<br />that is fully encapsulated in FSP facing. The duct
<br />enclosure system shall be listed by UL and /or ULC per
<br />ASTM E 2336, CAN/ULC S144 and ISO 6944 for
<br />1-, 2- and 3-hour rating and zero clearance to
<br />combustibles, and tested per ASTM E84 for a flame/
<br />smoke rating less than 25/50. Insulation shall have a
<br />nominal thickness of 1-1/2 inches (38 mm) and density
<br />of 6 Ibs/ff3 (96 kg/hrl Insulation shall have a R-Value of
<br />7.3 at 75°F. Installation shall be in strict accordance to
<br />manufacturers published installation instructions, UL or
<br />ULC Listings, and shop drawings. FastDoorTM XL shall
<br />be used for duct access where specified Or as required
<br />by code.
<br />4. Physical Characteristics
<br />Units/
<br />Wt./
<br />Product
<br />Unit
<br />Size
<br />Ctn.
<br />Ctn.
<br />FastWrap XL
<br />Roll
<br />1-12" x 24" x 25'
<br />1
<br />37.51Its.
<br />FastWrap XL
<br />Roll
<br />1-12" x 48" x 25'
<br />1
<br />75 lbs.
<br />5. Performance Specifications
<br />Reference Standard
<br />Standard No.
<br />Performance
<br />Grease Duct Enclosure
<br />ASTM E2336
<br />Pass
<br />System
<br />Section 16.1 -
<br />Non -Combustibility
<br />ASTM E136
<br />Pass
<br />Section 16.2-Fire Resistance
<br />ASTM Ell 9
<br />Pass
<br />(wall)
<br />Section 16.3 - Durability Test
<br />ASTM C518
<br />Pass
<br />Section 16.4- Internal Fire
<br />ASTM E2336
<br />Pass
<br />Test
<br />Section 16.5 - Fire Engulfment
<br />ASTM E814/
<br />(duct)
<br />E11.9
<br />Pass
<br />ULC Grease Duct Test
<br />pass
<br />Protocol
<br />Standard Methods of Fire
<br />Resistance Tests- Grease
<br />CAN/ULCPass
<br />5144
<br />Duct Assemblies
<br />Grease Duct Clearances
<br />UL 1978
<br />Pass
<br />Air Ventilation Duct Enclosure
<br />ISO 6944
<br />Pass
<br />Surface Burning
<br />ASTM E84
<br />Q5/50
<br />Characteristics
<br />Thermal Resistance
<br />ASTM C518
<br />7.3 per layer
<br />(R-value @ 75*F)
<br />Mold Growth
<br />ASTM C1338
<br />ULE Validated
<br />Low VOCs
<br />CA Standard
<br />ULE Validated
<br />01350
<br />6. Listings/Building Code Reports
<br />Listed Uses
<br />Agency
<br />Listing
<br />Layers
<br />Grease Duct Enclosure per
<br />UL
<br />G18
<br />ASTM E2336 and AC101 (2006,
<br />2
<br />2009, 2012 IMC, NFPA 96,
<br />ICC-ES
<br />ESR 2213
<br />UMC, CMC)
<br />ULC Grease Duct Test Protocol
<br />ULC
<br />FRD 4, 7*
<br />2
<br />and CAN/ULC S144*
<br />Grease Duct Insulation
<br />OPL
<br />TC/BI 120-01
<br />1
<br />(2003 IMC)
<br />Through Penetration FireStop
<br />UL
<br />ULC
<br />System per ASTM E814,
<br />See Figure 2
<br />1 or 2
<br />UL 1479
<br />UL
<br />HNLJ.V1,
<br />1- or 2-hour Ventilation Duct
<br />19,29
<br />Enclosure per ISO 6944-1985
<br />1
<br />FRD 3, 5
<br />ULC
<br />,
<br />6,18
<br />3-hour Ventilation Duct
<br />UL
<br />HNLJ.V2
<br />2
<br />per er ISO 6944-1985
<br />Electrical Circuit Protective.
<br />UL
<br />FHIT.S
<br />2
<br />System
<br />7. Storage
<br />g
<br />Thermal Ceramics FastWrapXL must be stored in a dry
<br />Y
<br />warehouse environment on pallets. Pallets should not be
<br />stacked.
<br />8. Installation
<br />Thermal Ceramics FastWrap XL shall be installed by a
<br />qualified contractor in accordance with manufacturer's
<br />instructions and laboratory design listings.
<br />Materials and Equipment
<br />• Thermal Ceramics FastWrap XL blanket
<br />• Aluminum foil tape
<br />• Glass filament reinforced tape (optional)
<br />• Carbon steel or stainless steel banding material,
<br />minimum 1/2" (1 3mm) wide, minimum 0.015" (0.4mm)
<br />thick, with steel banding clips
<br />• Hand banding tensioner and crimping tool
<br />• Minimum 12 gage (3mm) steel insulation pins; steel
<br />speed clips, minimum 1-1/2" (38mm) square or
<br />1-1/2" (38mm) diameter, Or equivalent sized cup -head
<br />pins;
<br />in Capacitor discharge stud gun
<br />• Thermal Ceramics FastDoorTM XL
<br />• An approved firestop sealant
<br />www.morganthermalceramics.com www.morganthermalceramics.com
<br />12:2014 Page 1 of 8 12:2014. Page 2 of 8
<br />11 Morgan U Morgan
<br />CAdvanced Materials FIR"ffifk C Advanced Materials F/R"M
<br />Grease and HVAC Duct Enclosure System
<br />1 or 2 Hour Shaft Alternative / Zero Clearance to Combustibles
<br />Butt Joint / Butt Joint Typical 3
<br />TWO LAYER INSTALLATION (Grease Duct perASTM E2336 and CAN/ULCS144)
<br />Telescope Wrap. Option Butt Joint Option Checkerboard Wrap Option
<br />SINGLE LAYER INSTALLATION OPTIONS (2-Hour rated HVAC Duct per UL HNLJ V-19)
<br />LEGEND
<br />1
<br />Two Layers of XL Insulation forASTM E2336 and CANAILC S144 Grease Duct Enclosures
<br />One Layer of XL Insulation for 2-Hour Air Ventilation Duct Enclosures
<br />2
<br />Steel banding minimum 1/2" 13 wide by 0.015" 0.4 thick.
<br />3
<br />Tight bull joints (no overlap) at perimeter and longitudinal joints, both layers for grease ducts
<br />4
<br />Min. 3" 75 overlap on perimeter and between adjacent blankets
<br />5
<br />Optional 6" XL collar
<br />6
<br />Hangers - size dependent weight of assembly see datasheet Section G
<br />7
<br />Trapeze Supports - sizedependent on weight of assembly (see datasheet Section G)
<br />8
<br />Steel Rectangular or Round Duct size., gage and construction dependent per Listed Desi n
<br />The Integrity of Thermal �eamlrs ductsysems Isllmlted fo me quality N me Installation
<br />XL001-to
<br />www.morganthermaIceramics.com
<br />12:2014 Page 5 of 8
<br />Commercial Kitchen Grease Duct Enclosure System
<br />Air Ventilation Duct Enclosure System
<br />Through Penetration Firestop Systems
<br />XL Insulation continuous through rated wall assembly
<br />XL insulation terminated on both sitles of the
<br />rated wall assembly
<br />XL Insulation continuous through rated Floor/ceiling assembly
<br />XL insulation terminated at the top and botto
<br />surface of the Floor/ceiling assembly
<br />Firestop Designs per ASTM E814/ UL 1479 - Consult UL / ULC Directories for System Details
<br />UL Listing
<br />F- & T-Ratio
<br />1 Floor/Wall
<br />2 Penetrant
<br />3 Enclosure Per
<br />4 Termination
<br />5 Firestop Sealant Details
<br />C-AJ-7012
<br />2-hour
<br />Concrele/CMLI
<br />84x24; 26 Ga Duct
<br />V19: FRD3; 5, 18
<br />wrap through
<br />1n in; STI; Tremco
<br />C-AJ-7014
<br />3-hour
<br />Cancrete/CMU
<br />84x24; 26 Ga Duct
<br />V2',
<br />wrap through
<br />1/2 in; STI; Tremco
<br />C-AJ-7019
<br />1 or 2-hour
<br />Concrete/CMU
<br />84x24; 26 Ga Duct
<br />V19; FRD3, 5, 18
<br />terminate at
<br />1/4 in; STI; Tremco
<br />C-AJ-7021
<br />2-hour
<br />Concrete/CMU
<br />49x24; 16 Ga Duct
<br />G1B; FRD4; 7
<br />terminate at
<br />1/4 in; STI; Tremco
<br />C-AJ-7095
<br />2-hour
<br />Concrete/CMU
<br />39x39; 22 Ga Duct
<br />V19; FRD3, 5, 18
<br />wrap through
<br />1/4 in; STI Hill; Rectorseal; Tremco
<br />C-AJ-7098
<br />2-hour
<br />Cancrete/CMU
<br />49x24; 16 Ga Duct
<br />G1B; FRD4; 7
<br />wrap through
<br />1/4 in; STI; Hilti; Rectorseal; Tremco
<br />F-C-7036
<br />1 or 2-hour
<br />Wood/Gyp Floor
<br />24x12; 16 Ga Duct
<br />G1B; FRD4; 7
<br />wrap through
<br />1/4 in; STI; Hill; Rectorseal; Tremco
<br />F-C-7055
<br />1-hour
<br />VikodiGyp Floor
<br />4 Dla; 30 Ga Duct
<br />V29; Iii
<br />wrap through
<br />1/4 In; STI
<br />W-J-7086
<br />2-hour
<br />Cancrete/CMU Wall
<br />100100; 26 Ga Duct
<br />V19; FRD3;5; 18
<br />terminate at
<br />1/4 in; STI
<br />W-L-7121
<br />1 or 2-hour
<br />Wall
<br />30116 Ga Duct
<br />G1B; FRD4; 7
<br />wrapthrough
<br />1/4 in; STI; Hilti; Rectorseal; Tremco
<br />W-L-7145
<br />1 or 2-hour
<br />Wall
<br />I 100126Ga Duct
<br />I V19; FRD3; 5; 18
<br />1 terminate at
<br />5/8 in; STI
<br />The integrity of marmal Ceramics dud systems is im11ed,"the quality oithe installation.
<br />,tno35
<br />www.morganthermaIceramics.com
<br />13 2014 Page of 8
<br />General
<br />Cut edges of the blanket shall be taped with aluminum foil
<br />tape to prevent exposed edges Of the insulation absorbing
<br />grease and moisture in the event of a compromised grease
<br />duct joint or condensation. Overlaps and/or tightly butted
<br />joints are used to block heat transfer in the event of duct
<br />deformation resulting from thermal expansion. Filament
<br />tape is suggested to hold the blanket in place until steel
<br />banding or pinning is installed to permanently secure the
<br />blanket.
<br />A. Installation on Grease Duct per ASTM E2336 and
<br />CANMLC S144 (Figure 1)
<br />System requires two layers of insulation applied directly to
<br />the duct with tight butt joints at all seams on both layers.
<br />The first layer of insulation is cut to a length sufficient to
<br />wraparound the duct and provide a tight butt oint where
<br />p 9 1
<br />the blanket ends meet. layer
<br />Adjacent blankets on the first la
<br />1 Y
<br />are butted tightly together with longitudinal seams offset
<br />9 Y o9 9
<br />minimum 6" The second ) 150mm . layer of insulation is
<br />(
<br />installed in the same method as the first layer, with seams
<br />between layers offset a minimum of 6" (150mm). Banding
<br />and/or pinning per Section D is used to permanently
<br />secure the insulation to the duct.
<br />B. Installation on HVAC Duct per ISO 6944 (Figure 1)
<br />System requires one layer of insulation applied directly to
<br />the duct with 3" (75mm) overlaps at all seams. The
<br />insulation is cut to a length sufficient to wrap around the
<br />duct and provide a 3" (75mm) overlap where the blanket
<br />ends meet. Adjacent blankets are installed to provide a
<br />minimum overlap of 3" (75mm). Banding and/or pinning per
<br />Section D is used to permanently secure the insulation to
<br />the duct.
<br />C. 2 & 3 Sided Wrap Installation (Figure 4)
<br />When space does not allow for a complete wrap applied to
<br />the duct on all four sides, the FastWrap XL is approved for 2
<br />Or 3 sided installations with mechanical attachment to a rated
<br />concrete or CMU assembly. (See Figure 4 for installation
<br />details.)
<br />D. Mechanical Attachment Methods
<br />1) Banding (Figure 1)- Minimum 1/2" (13mm) wide
<br />carbon steel Or stainless steel banding, 0.015" (0.4mm)
<br />thick is placed around the entire perimeter of the
<br />insulated duct on maximum 10-1/2" (270mm) centers
<br />and 1-1/2" (38mm) from each blanket edge or 1-1/2"
<br />(38mm) from each collar edge when using the butt joint
<br />U Morgan
<br />CAdvanced Materials
<br />and collar method. The banding is placed around the
<br />blanket and tightened to firmly hold the FastWrap XL in
<br />place against the duct, but not cause any cutting or
<br />damage to the blanket.
<br />2) Pinning - Pinning on all sides of the duct may be used
<br />as an alternative to banding. For ducts wider than 24"
<br />(610mm) pinning is required on the bottom of horizontal
<br />runs, or on one side of vertical runs (in addition to steel
<br />banding). When applicable, 12 Gage (0.4mm) steel pins
<br />are installed on 12" (305mm) centers along: the width of
<br />the duct and 10-1/2" (270mm) centers along the length
<br />of the duct. Pins that extend beyond the outer blanket
<br />layer shall be turned down or the excessive length cut
<br />off to prevent sharp edges. Shoot through pins (cup
<br />head pins) may be used in conjunction with steel
<br />banding to prevent blanket sag.
<br />E. Access Doors
<br />M
<br />1 FastDoor XL (Figure 3 - FastDoor XL is a UL Listed
<br />) ( 9 ) ,
<br />liquid tight duct cover panel supplied complete with a
<br />single layer insulation cover per UL Listing HNKT G18.
<br />The FastDoor XL is installed per included installation
<br />instructions. No field welding is required.
<br />2 Field Fabricated Access Doors - Each access door
<br />assembly has four threaded rods 1/4 inch (6mm) in
<br />diameter and 5" (127mm) in length, with one welded to
<br />each corner of the door opening. Hollow steel tubes,
<br />4-1/2" (114mm) long are installed outside the access
<br />cover plate and over the threaded rods. Four 12 gage
<br />(3mm) and 4-1/2" (114mm) long steel insulation pins are
<br />welded to the access cover plate to allow for installation
<br />of the three layers of FastWrap XL. One layer of
<br />FastWrap XL is cut to approximately the same size as
<br />the access panel, and impaled over the insulation pins
<br />on the panel. A second layer of FastWrap XL is cut so
<br />as to Overlap the first layer a minimum of 1-1/2" (38mm).
<br />It is essential that the first and second layer fit tightly
<br />against the surrounding wrap with no through openings.
<br />The third and outside layer should be cut to overlap the
<br />second insulation layer by minimum of 1-1/2" (38mm).
<br />Minimum 1-1/2" (38mm) round or square insulation clips
<br />are installed on the insulation pins to secure the three
<br />layers of insulation to the access cover plate. All cut
<br />edges of the insulation shall be taped with minimum 3"
<br />(75mm) wide aluminum foil tape. Wing nuts and
<br />washers are installed on the four threaded rods, and
<br />tightened against the hollow steel tubes to seal the
<br />www.morganthermalceramics.com
<br />4
<br />ASTM E 2336 Compliant Enclosure and Door System
<br />FIGURE 3
<br />1
<br />UL listed FastDoor XL accesspanel
<br />2
<br />All Thread Rods and wing nuts
<br />3
<br />Retainer Clips with threaded nut and wing bolts
<br />4
<br />Insulation layers as required by UL or ITS Listings
<br />5
<br />FastDoor XL; 1-12 inch thick single layer insulation
<br />12:2014 Page 3 of 8
<br />F/R"MR
<br />FastDoor XL1 Access Doors Sizes
<br />Available Opening Sizes
<br />Ordering Code
<br />10" x 4" Door Opening
<br />*434-6970-033-99X1
<br />10" x 6" Door Opening
<br />434-6970-034-99X1
<br />12" x 8" Door Opening
<br />434-6970-035-99X1
<br />12" x 12" Door Opening
<br />434-6970-036-99X1
<br />16" x 12" Door Opening -
<br />434-6970-037-99X1
<br />20" x 20" Door Opening
<br />434-6970-038-99X1
<br />*Special Order; Curved and SS Available
<br />www.morganthermaIceramics.com
<br />12 2014 Page 7:of 8
<br />access cover plate to the duct.
<br />F. Through Penetration Firestop System (Figure 2) -
<br />When the duct penetrates a fire rated assembly an
<br />approved fire stop system must be employed. Figure 2
<br />provides a complete list of UL / ULC firestop design
<br />listings which can be found in the Certifications Directory
<br />at vwAM.ul.com for US systems and www.ulc.ca for
<br />Canadian systems. Prior to installing any firestop system
<br />the surfaces of all openings and penetrating items must
<br />be clean and dry. The FastWrap XL core blanket (or
<br />mineral wool where allowed b the firestop design listing)
<br />Y p 9 9)
<br />must be compressed into the annular space. The
<br />packing material must be recessed a minimum depth
<br />from the surface of the concrete or gypsum assembly.
<br />The recessed opening must be filled with a minimum
<br />thickness of an approved firestop sealant. The packing
<br />material type and compression, minimum recess
<br />p
<br />(typically 1/4" 6mm and approved firestop sealant and
<br />(21'p Y ( )) pP p
<br />thickness(typically 1/4" (6mml shall be asspecified in an
<br />approved UL / ULC firestop design listing. When there
<br />pp p 9 9
<br />is not sufficient annular space around the duct to run the
<br />FastWrap XL enclosure system continuous through the
<br />fire rated assembly, the enclosure may terminate above
<br />and belowthefloor/ceilin9 Y assembl or On either side Of
<br />a wall assembly as shown in Figure 2. When this method
<br />is used, the FastWrap XL must be mechanically attached
<br />on either side of the fire rated assembly using one of the
<br />attachment methods described in Section D, spaced a
<br />maximum of 1-1/2" (38mm) from the fire rated assembly.
<br />G. Support Hanger Systems
<br />1) Grease ducts: Trapeze support hangers shall be
<br />spaced on maximum 60 in. (1500 mm) centers. Hanger
<br />rods or straps shall be anchored with steel drop in or
<br />wedge expansion type masonry anchors. No additional
<br />protection is required for hangers and supports meeting
<br />the requirements of the Table below.
<br />Hanger Cross
<br />Maximum
<br />Trapeze Support (or
<br />Section
<br />Perimeter, in (mm)
<br />equivalent Yield Strength),
<br />n ford
<br />38 in (10 com)
<br />threaded rod
<br />148 (3759)
<br />2 (51) x 2 (51) x 1.8 (3) in angle
<br />2) HVAC ducts: Trapeze support hangers shall be spaced
<br />on maximum 60 in. (1500 mm) centers. Hanger rods or
<br />straps shall be anchored with steel drop in or wedge
<br />expansion type masonry anchors. No additional
<br />U Morgan
<br />CAdvanced Materials
<br />F/R"M
<br />protection is required for hangers and supports meeting
<br />the requirements of the Table below.
<br />Max.M Perimeter,
<br />Trapeze Support (or
<br />Hanger Cross Section
<br />in (ford)
<br />equivalent Yield Strength),
<br />n (mm)
<br />1 in x 16 gage strap
<br />100 (2540)
<br />(25 com x 1.5 gage strap)
<br />Ain (6 man) threaded rod
<br />50 (1270)
<br />1 H (38) X 134 (38} x 3a 6 (5)
<br />angle
<br />38 in (10 mural threaded
<br />150(3810)
<br />1&(38) x 1Ye(38) x 316(5)
<br />rod
<br />angle
<br />12 in (12.7 com) threaded
<br />218 (5540)
<br />2 (51) x 2 (51) x 14 (6) angle
<br />no,
<br />9. Maintenance and Repair
<br />No maintenance is required when installed in accordance
<br />with Thermal Ceramics (TC) C installation instructions. If
<br />damage is limited to the foil facing, aluminum foil tape can
<br />9 9, p
<br />be used to repair the foil facing. If an area Of blanket is
<br />p 9
<br />found to be damaged the following procedure must be in-
<br />corporated. If the damaged area is larger than 8" (203mm)
<br />x 8" (203mm) the entire wrap section must be removed and
<br />replaced according to TC installation
<br />p 9
<br />instructions. If the damaged area is small less than 8"
<br />(203mm) x 8" (203mm)), the damaged area must be cut
<br />away and replaced with a new section 1" (25mm) larger in
<br />length and width than the cut out, such that the new section
<br />can be compressed tightly into the cut out area. All cut
<br />edges of the new section must be taped and sealed with
<br />aluminum foil tape. The new section must be held in place
<br />with either pinning or banding per TC installation i
<br />restructions.
<br />10. Limitations
<br />Thermal Ceramics FireMaster FastWrap XL shall be
<br />installed in accordance with these installation
<br />instructions and appropriate laboratory design listings. The
<br />integrity of FastWrap XL systems is limited to the quality of
<br />the installation.
<br />* For personal protective equipment recommendations, please see SDS.
<br />Thermal Ceramics, FireMaster, and FastWrap are trademarks of
<br />Morgan Advanced Materials. FireMaster products are manufactured by
<br />Thermal Ceramics and are distributed by aulhorized distributors.
<br />www.morganthermalceramics.com
<br />FireMaster® FastWrap° X N
<br />12:2014 Page:4 of 8
<br />F/RF gM
<br />Commercial Kitchen Grease Duct Enclosure System
<br />Air Ventilation Duct Enclosure System
<br />1 Or 2 Or 3 Hour Shaft Alternative / Zero Clearance to Combustibles
<br />2 and 3 Sided Wrap Detail forAttaching to Walls and/or Ceilings
<br />XL005-4
<br />Note: Ducts must be independently supported per code
<br />LEGEND
<br />1
<br />Rated Concrete floor/ceiling,. or wall - with rating equal or greater than enclosure rating
<br />2
<br />Two layers: of XL Insulation for Grease Dud Enclosures (install per UL G18))
<br />One layer of XL Insulation for Air Ventilation Dud Enclosures (install per UL V19)
<br />Two layers of XL Insulation for 3-hrAir Ventilation Duct Enclosure (install per UL V2)
<br />3
<br />Concrete fastener system
<br />4
<br />3/16" (5) thick x 2" (50) -3" (75) wide bar stock. perforated 12" (305) o.c.
<br />5
<br />8" (203) maximum Air Gap
<br />6
<br />Dud
<br />7
<br />Steel banding min. 112" (13) wide by 0.015" (0,4) thick.
<br />8
<br />Banding clip
<br />The integrity of Morgan Thermal Ceramics duct systems is limited to the quality of meinstallation-
<br />www.morganthermaIceramics.com
<br />12:2014. Page 8 of 8
<br />903121 STAVE SW
<br />SEATTLE, WA 98106
<br />TEL. 206.322.4323
<br />FAX. 206.322.9177
<br />E-MAIL:INFO@CATCHSTUDIO.COM
<br />WWW.CATCHSTUDIO.COM
<br />PROJECT TITLE:
<br />MOCHINUT
<br />EVERETT
<br />8417 EVERGREEN WAY
<br />EVERETT, WA 98208
<br />SHEET TITLE:
<br />SPECSHEET
<br />PERMIT:
<br />DATE:
<br />CATCH DESIGN STUDIO
<br />DRAWN: NOS NARIN
<br />SCALE: AS NOTED
<br />NATIVE FILE:
<br />DATE: 01/05/2024
<br />SHEET#
<br />MK7
<br />
|