HOOD SPEC SHEET
<br />16015 Shady Falls Road
<br />Elmendorf, Texas 78112
<br />Telephone: 210-635-8100
<br />Facsimile: 210-635-8101
<br />www.intertek-etlsemko.com
<br />September 29, 2009
<br />Project No. 3189370
<br />Keith Ta
<br />Great Sun Corporation
<br />505 South Lander St
<br />Settle, WA 98134
<br />Phone: (206) 683-1414
<br />E-mail: ktaa_greatsuncorp.com
<br />Subject: UL 710 Evaluation of GSH-4 Series Exhaust Hood
<br />Dear Mr. Ta,
<br />This letter concludes and represents the results of the evaluation and tests of the above referenced
<br />equipment to the requirements contained in the following standards:
<br />UL 710, Standard for Safety for Exhaust Hoods for Commercial Cooking Equipment, Fifth
<br />Edition, Dated December 28, 1995 with revisions through and including February 2, 2007.
<br />This investigation was conducted on the Model GSH-4-10 exhaust hood we received on September
<br />22, 2009 and evaluated on September 28, 2009 at the Intertek Testing Laboratory in Elmendorf,
<br />Texas. The exhaust hood with integral air supply plenum tested in accordance with UL710 was
<br />constructed of and supported by stainless steel not less than Type 304 0.043-in (No. 18 MSG) in
<br />thickness and stainless steel not less than 0.037-in (20 MSG) in thickness. All seams and joints of the
<br />hood enclosure that directed and captured grease -laden vapors and exhaust gases were liquid -tight,
<br />and continuously welded. Internal hood joints, seams, filter support frames and appurtenances
<br />attached inside the hood are to be sealed or otherwise made grease tight. The hood was provided
<br />with grease baffle filters that were tested and approved UL1046 Listed grease filters. The lighting��
<br />fixtures incorporated in hood were UL 1571 Listed Incandescent Light Fixtures.
<br />9Tle
<br />We are happy to inform you that your exhaust hood is compliant to the standard listed above. The test
<br />�tesrro-
<br />methods used to establish conformance were taken directly from the UL 710 standard and are listed
<br />below:
<br />,KT E9TFk
<br />Test Method
<br />UL 710
<br />Compliant/Non-
<br />Compliant
<br />Temperature Test
<br />Clause 30
<br />Compliant
<br />Cooking Smoke and Flare -Up Test
<br />Clause 31
<br />Compliant
<br />CE
<br />The results of the Temperature Test indicated that maximum temperature rise attained by an exhaust
<br />hood part during the test was well below the applicable values indicated in Column 1 of Table 30.1 of
<br />the standard. To this effect, the exhaust hood met the conditions of acceptance for the temperature
<br />test. The results of the Cooking Smoke and Flare -Up test were instrumental in establishing the hood
<br />ratings listed below in Tables 1 and 2 below, for total capture and containment for the exhaust hood:
<br />Page 1 of 7
<br />nm
<br />This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are \�
<br />limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, BEAK
<br />expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of Approved
<br />the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations
<br />and test results in this report are relevant only the sample tested. This report by itself does not imply that the material, product or service is or has ever been under an
<br />Intertek certification program.
<br />Letter Report 3189370SAT-001
<br />Great Sun Corporation
<br />www gristwuncotp.Ew.
<br />Ul LISTED
<br />Gs GREAT SUN CORP. �-_-� �IN,1 MAKEUPAIR
<br />UL LISTED
<br />RlSleur5nl Equipment 5uppbh, 6 Mfpl F41Sfrti6prY GA GALVANIZE
<br />545 S. LlOdrr St. 54mw, WA �{t]4 W
<br />tY W UP DUCT
<br />fEXHAUST
<br />FAN
<br />Intertek Testing Services NA, Inc. SD 12.1.2 (6/19/08) Informative
<br />Issue Date: 9/29/2009
<br />Revised: NA
<br />S0 GA
<br />FLASHING
<br />8"
<br />Q GA UNSTRUT
<br />'7
<br />3,,l THREADED
<br />STEEL RX
<br />aL !$TED
<br />.,'�.. �. ,"
<br />IFRONT SUPPORT
<br />FIREWRAP
<br />-
<br />.S
<br />1$`x16'ALIAROUND
<br />STEEL, .__
<br />CONnNUOUS TIGHT
<br />"
<br />(FRONT SUPPORT;
<br />WELDED GREASE
<br />','I
<br />DUCT (16 GA
<br />GALVANIZE STEFl1
<br />GA
<br />`I a5�1
<br />14' -4' 14'
<br />=11111111ilm-
<br />FRONT VIEW
<br />SCALE: Y, =1'
<br />Installation Schematic (cont.)
<br />MAKE UP
<br />I AIR
<br />4'x4"PT
<br />SL EEPFPS
<br />UL LISTED
<br />DUCT aANDurG
<br />UL LISTED
<br />fTHERMAFLE?t)
<br />C-KM FLEXIBLE
<br />INSULATED AIR DUCT
<br />L SUSPEWED'r CEIMG
<br />STAINLESS STEEL WALL
<br />wl UL LISTED
<br />I' RQXUI. FIRE PAD
<br />Letter Report 3189370SAT-001
<br />Great Sun Corporation
<br />TABLE 1: Minimum Size Exhaust Hood Rating
<br />Issue Date: 9/29/2009
<br />Revised: NA
<br />Minimum
<br />Maximum
<br />Hood
<br />Hood
<br />Hood
<br />Exhaust
<br />Appliance
<br />Side/Rear/Front
<br />Cooking
<br />Cooking
<br />Hood Model
<br />Width
<br />Length
<br />Height
<br />Collar
<br />Temperature
<br />CFM/ft
<br />Clearance (in)
<br />Surface
<br />Surface
<br />(in)
<br />(in)
<br />(in)
<br />(in)
<br />(OF)
<br />Distance
<br />Distance
<br />(in)
<br />(in)
<br />GSH-4 Series
<br />48
<br />216
<br />20
<br />18 x 18
<br />400
<br />200
<br />10; 6; 9
<br />24
<br />45
<br />GSH-4 Series
<br />48
<br />216
<br />20
<br />18 x 18
<br />600
<br />200
<br />10; 6; 9
<br />24
<br />45
<br />GSH-4 Series
<br />48
<br />216
<br />20
<br />18 x 18
<br />700
<br />200
<br />10; 6; 9
<br />24
<br />45
<br />TABLE 2: Maximum Size Exhaust Hood Rating
<br />Minimum
<br />Maximum
<br />Hood
<br />Hood
<br />Hood
<br />Exhaust
<br />Appliance
<br />Side/Rear/Front
<br />Cooking
<br />Cooking
<br />Hood Model
<br />Width
<br />Length
<br />Height
<br />Collar
<br />Temperature
<br />CFM/ft
<br />Clearance (in)
<br />Surface
<br />Surface
<br />(in)
<br />(in)
<br />(in)
<br />(in)
<br />(OF)
<br />Distance
<br />Distance
<br />(in)
<br />(in)
<br />GSH-4 Series
<br />48
<br />216
<br />20
<br />18 x 18
<br />400
<br />300
<br />0; 6; 6
<br />24
<br />45
<br />GSH-4 Series
<br />48
<br />216
<br />20
<br />18 x 18
<br />600
<br />300
<br />6; 6; 9
<br />24
<br />45
<br />GSH-4 Series
<br />48
<br />216
<br />20
<br />18 x 18
<br />700
<br />300
<br />6; 6; 9
<br />24
<br />45
<br />As per the compliant results mentioned, the Listing Report No. 3189370SAT-001 will now updated to
<br />include hood ratings, and recognition for similarly constructed hood models between 48-in to 216-in
<br />long, 48-in wide, 20-in high. The Certification Listing Report No. 3189370SAT-001 will be finalized as
<br />soon as we receive the pending information that is required for the report.
<br />If there are any questions regarding the results contained in this report, or any of the other services
<br />offered by Intertek, please do not hesitate to contact us.
<br />For your convenience, photos of the testing that was conducted have been included in the following
<br />pages of this letter report.
<br />We appreciate all of your cooperation and effort with regards to providing us with the necessary
<br />information to test your hood. We look forward to working with you again in the near future for any and
<br />all of your testing needs.
<br />Thank you,
<br />Jason De La Cruz
<br />Intertek CKV Engineer
<br />Completed by:
<br />Jason De La Cruz
<br />Reviewed by:
<br />Cory Machado
<br />Title:
<br />Intertek CVK Engineer
<br />Title:
<br />Senior Project Engineer
<br />Signature:
<br />Signature
<br />Date
<br />09/29/2009
<br />Date:
<br />09/29/2009
<br />Intertek Testing Services NA, Inc.
<br />Letter Report 3189370SAT-001
<br />Great Sun Corporation
<br />Product Photographs
<br />UL 710 - Great Sun Corp. - September 28, 2009
<br />Photo 1 -1Oft. Hood Assembly
<br />Page 2 of 7
<br />SD 12.1.2 (6/19/08) Informative
<br />Issue Date: 9/29/2009
<br />Revised: NA
<br />Photo 2 -1 Oft. Hood Assembly - Typical Cooking Smoke and Flare -Up Test
<br />Letter Report 3189370SAT-001
<br />Great Sun Corporation
<br />w ww.grealsuncorp.tam
<br />cs GREAT SUN CORP.
<br />Restaurant Equipment. Supplies, 3 Metal Fabn catkin
<br />505 S. Lander St. 1 Seattle.. WA 88134
<br />FIREWRAP
<br />ALL AROUND
<br />CONTINUOUS TIGHT
<br />WELDED 16 GA.
<br />GALVANIZE DUCT
<br />EXISTING WALL
<br />ALL AROUND
<br />CONTINUOUS LIQUID
<br />TIGHT WELD
<br />BETWEEN DUCT AND
<br />HOOD SYSTEM
<br />3" STAINLESS STEEL
<br />(20 GA.) FLASH
<br />METAL STUD
<br />WALL FRAME
<br />5/8" TYPE "X"
<br />FIRE RATED
<br />SHEET ROCK
<br />STAINLFSS STEEL
<br />WALL w/ ROXUL
<br />AFB 1 HR FIRE. PAD
<br />Letter Report 3189370SAT-001
<br />Great Sun Corporation
<br />Product Photographs
<br />3" AIR SPACE
<br />FLOOR—,
<br />Issue Date: 9/29/2009
<br />Revised: NA
<br />MAKE UP
<br />AIR VENTS
<br />FILTER
<br />— 18 GA. STAINLESS
<br />UL LISTED—
<br />TEMPERED
<br />STEEL TYPE I
<br />GLASS GLOBE
<br />GREASE HOOD
<br />--GREASE
<br />GUTTER 3 _g
<br />6'-6"
<br />COOKING
<br />EQUIPMENT
<br />SECTION ELEVATION VIEW
<br />istallation Schematic
<br />Intertek Testing Services NA, Inc.
<br />Page 3 of 7
<br />SD 12.1.2 (6/19/08) Informative
<br />Issue Date: 9/29/2009
<br />Revised: NA
<br />Photo 3 - 4 ft. Hood - Typical Capture and Containment Test
<br />Photo 4 - 4 ft. Hood - Typical Temperature Test
<br />Letter Report 3189370SAT-001
<br />Great Sun Corporation
<br />Issue Date: 9/29/2009
<br />Revised: NA
<br />wmvgr¢atsuncorp.um TYPICAL UNISTRUT HOOD SUPPORT DETAILS
<br />Gs GREAT SUN CORP.
<br />RoMmuranl Equipment. Supp4s, 8 WWI Fabrication
<br />505 S. Lanaer S1 ; Seattli, VVA W34
<br />A
<br />MANUFACTURER WESTERN STATES
<br />FASTENING SYSTEMS
<br />PART N: 50943 No 14 NON-COMBUSTIBLE
<br />1.5" HEX. WASHER SELF DRILL SCREWS
<br />16 GA, GALVANIZED
<br />SUPPORT BRACKET
<br />12 GA. UNISTRUT
<br />SUPPORT N
<br />FLAT WASHER
<br />318" THREADED
<br />STEEL ROD
<br />16 GA. GALVANIZE DUCT
<br />DUCT TO BE CONTINUOUS
<br />TIGHT WELD BETWEEN
<br />*---- --------------
<br />-------
<br />HOOD FOR ADDED SUPPORT
<br />BRACKET
<br />WELDED
<br />ONTO HOOD
<br />(A) 1.5' METAL FASTENERS
<br />..............
<br />•:fT1;:. .
<br />BETWEEN HOOD 8
<br />SUPPORT BRACKET
<br />3' ND. 10 METAL FASTENERS
<br />BETWEEN WALL STUD d
<br />SUPPORT BRACKET
<br />OM CENTER OFF FRAMG S'%WS
<br />2G GA. STAINLESS
<br />(B! 16 GA GALVANIZE
<br />.........
<br />,�r'�Y��
<br />STEEL TYPE 1
<br />SUPPORT BRACKET
<br />y
<br />;��;• .'
<br />GREASE HOOD
<br />3' STAINLESS
<br />STEEL FLASHING —"
<br />-------------------------
<br />Installation Schematic (cont.)
<br />Page 4 of 7
<br />Intertek Testing Services NA, Inc. SD 12.1.2 (6/19/08) Informative
<br />OFAITEIM
<br />DESIG N STUDIO
<br />9031 21 ST AVE SW
<br />SEATTLE, WA 98106
<br />TEL. 206.322.4323
<br />FAX. 206.322.9177
<br />E-MAI L:I NFO@CATCHSTUD I0. COM
<br />WWW.CATCHSTUDIO.COM
<br />PROJECT TITLE:
<br />HINUT
<br />MOC
<br />EVERETT
<br />8417 EVERGREEN WAY
<br />EVERETT, WA 98208
<br />SHEET TITLE:
<br />SPECSHEET
<br />PERMIT:
<br />DATE:
<br />CATCH DESIGN STUDIO
<br />DRAWN: NOS NARIN
<br />SCALE: AS NOTED
<br />NATIVE FILE:
<br />DATE: 01/05/2024
<br />SHEET#
<br />Page 5 of 7
<br />Intertek Testing Services NA, Inc. SD 12.1.2 (6/19/08) Informative
<br />Page 6 of 7
<br />Intertek Testing Services NA, Inc. SD 12.1.2 (6/19/08) Informative
<br />Page 7 of 7
<br />Intertek Testing Services NA, Inc. SD 12.1.2 (6/19/08) Informative