Laserfiche WebLink
1 <br />TERMINAL <br />UNIT SCHEDULE <br />BASIS OF <br />PIPE <br />PRIMARY AIR <br />UNIT N0. <br />SERVICE <br />DESIGN <br />BOX SIZE <br />DESIGN CFM <br />MAX SP <br />REO MBH <br />GPM <br />MIN ROWS <br />MAX PD <br />RUN-OUf TO <br />TEMP (DEG <br />REMARKS <br />COIL <br />2-25 <br />ADULT GROUP THERAPY 216, HALL, OFFICE <br />TITUS DESV <br />8 <br />650 <br />0.31 <br />25.2 <br />3 <br />2 <br />0.9 <br />3/4" <br />55 <br />1,2 <br />2-29 <br />WAITING 201, HA <br />ASHRAE 62.1 VENTILATION CALCULTION <br />ROOM NAME <br />AREA [n2] <br />OCCUPANT <br />COUNT <br />ASHRAE 62.1 OUTDOOR AIR RATE <br />DESIGN <br />OUTDOOR AIR RATE <br />DESCRIPTION <br />CFM/ <br />PERSON <br />CFM/SF <br />CALCULATED <br />0/A [CFM] <br />AIR DISTRIBUTION <br />EFFECTIVENESS <br />REQUIRED 0/A TO <br />ZONE [CFM] <br />0/A PERCENTAGE <br />TOTAL SUPPLY <br />AIRFLOW [CFM] <br />PROVIDED 0/A TO <br />ZONE [CFM] <br />201 WAKING <br />320 <br />8 <br />Reception Areas <br />5 <br />0.06 <br />59 <br />0.8 <br />74 <br />100% <br />155 <br />155 <br />202 RECEPTIONIST <br />84 <br />1 <br />Reception Areas <br />5 <br />0.06 <br />10 <br />0.8 <br />13 <br />100% <br />125 <br />125 <br />203 OFFICE <br />87 <br />2 <br />Office Space <br />5 <br />0.06 <br />15 <br />0.8 <br />19 <br />100% <br />65 <br />65 <br />fi S ce <br />05 HALL <br />342 <br />0 <br />Corridor <br />0 <br />0.06 <br />21 <br />0.8 <br />26 <br />100% <br />130 <br />130 <br />2 <br />3 <br />ice pac <br />3 <br />0 % <br />140 <br />0 <br />Breakroom <br />5 <br />0.12 <br />17 <br />0.8 <br />21 <br />100% <br />230 <br />230 <br />214 GROUP THERAPY <br />240 <br />16 <br />Conference meeting <br />5 <br />0.06 <br />94 <br />0.8 <br />118 <br />100% <br />250 <br />250 <br />16 ACTIVITY <br />519 <br />20 <br />Conference meeting <br />5 <br />0.06 <br />131 <br />0.8 <br />164 <br />100% <br />425 <br />425 <br />HEALTHCARE AIR CHANGE RATE CALCULATIONS <br />ROOM NAME <br />FUNCTION OF SPACE <br />FLOOR <br />AREA <br />SD. FT. <br />L <br />ASHRAE 170 REQUIREMENTS <br />DESIGN <br />AIRFLOW CONDITIONS <br />PRESSURE <br />RELATIONSHIP <br />OUTSIDE AIR <br />TOTAL <br />PRESSURE <br />RELATIONSHIP <br />OUTSIDE <br />AIR <br />CFM <br />SUPPLY <br />CFM <br />EXHAUST <br />CFM <br />TOTAL <br />AIR <br />CHANGES <br />AC HR <br />MIN. AIR <br />CHANGES <br />AC HR <br />MIN. AIR <br />FLOW <br />CFM <br />MIN. AIR <br />CHANGES <br />AC HR <br />MIN. AIR <br />FLOW <br />CFM <br />206 ADA RESTROOM <br />Patient Toilet Room <br />59 <br />N <br />0 <br />0 <br />10.0 <br />78 <br />N <br />0 <br />0 <br />130 <br />16.7 <br />209 CONSULT <br />Patient Room <br />155 <br />2 <br />41 <br />4.0 <br />8385 <br />85 <br />85 <br />4.1 <br />210 CONSULT <br />Patient Room <br />175 <br />- <br />2 <br />47 <br />4.0 <br />94 <br />- <br />95 <br />95 <br />95 <br />4.1 <br />1 <br />4 <br />4 <br />4 <br />208 NOURISHMENT AREA <br />Nourishment area or room <br />131 <br />1048 <br />- <br />0 <br />0 <br />2.0 <br />35170 <br />170 <br />9.7 <br />218 PATIENT TOILET <br />Patient Toilet Room <br />78 <br />624 <br />N <br />0 <br />0 <br />10.0 <br />104 <br />N <br />0 <br />0 <br />105 <br />10.1 <br />DIFFUSER AND GRILLE SCHEDULE <br />MARK <br />TYPE <br />NECK SIZE <br />NC <br />BASIS OF DESIGN <br />REMARKS <br />CD-1 <br />CEILING DIFFUSER <br />SEE PLANS <br />25 <br />TITUS MCD <br />MODULAR CORE DIFFUSER, LAY -IN <br />RG_1 <br />CEILING RETURN GRILLE, <br />SEE PLANS <br />25 <br />TINS 350FL <br />ALUMINUM, LOUVERED, 3/4' BLADE SPACING, 35 <br />ALUMINUM <br />DEFLECTION, LAY -IN <br />CEILING EXHAUST GRILLE, <br />12'X12' FACE MODULE, ALUMINUM, LOUVERED, 3/4" BLADE <br />EG-1 <br />ALUMINUM <br />SEE PLANS <br />25 <br />TITUS 350FL <br />SPACING, 35' DEFLECTION, SURFACE MOUNT <br />CEILING TRANSFER GRILLE, <br />ALUMINUM, LOUVERED, 3/4" BLADE SPACING, 35' <br />TG_1 <br />ALUMINUM <br />SEE PLANS <br />25 <br />TITUS 350FL <br />DEFLECTION, LAY -IN <br />CEILING TRANSFER GRILLE, <br />12'X12' FACE MODULE, ALUMINUM, LOUVERED, 3/4' BLADE <br />TG-2 <br />ALUMINUM <br />SEE PLANS <br />25 <br />TITUS 350FL <br />SPACING, 35' DEFLECTION, SURFACE MOUNT <br />0 <br />-c- In <br />O <br />2727 Oakes Ave. <br />Suite 100 <br />Everett, WA 98201 <br />REVISIONS <br />DOH REVISION 12/11/24 <br />D <br />easgr�J� <br />FT <br />"59941 <br />l8� <br />♦avAL <br />12/12/24 <br />z� <br />OQ <br />U LLJ <br />,W <br />V = <br />/ <br />U Q <br />� O <br />U � <br />W W <br />U m <br />W � <br />O <br />�O(� <br />LI- O <br />� LL <br />Boa 242095 <br />BRAWN � CEI <br />ON <br />PERMIT SET <br />08/22/24 <br />MECHANICAL <br />SCHEDULES <br />M0.3 <br />City of Everett Permit Services <br />EVERETT Reviewed for Permit 01/14/2025 <br />