EXISTING PANEL 4N1 (NORMAL BRANCH) (NEW WORK) FIRST FLOOR <br />VOLTAGE: 48013 PH, 4 W <br />TYPE: PANELBOARD <br />ENCLOSURE: NEMA1 <br />SURFACE <br />FEEDER/BRANCH CIRCUIT DEVICES: <br />BOLT -ON CIRCUIT BREAKERS <br />FULLAIC RATING '. 14,000A <br />SERIES AIC RATING: 65,000A <br />ELECTRICAL LOAD <br />CALCULATION <br />CONN. <br />EXIST. <br />LOAD <br />NEW <br />A <br />TOTAL <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD (VA) <br />Lighting <br />Pure... <br />Gen. Puose 0.1..(First lO KVA) <br />Gen, Purpose Outlets (Remainder) <br />Special Purpose Outlets <br />Mechanical Equipment <br />Kitchen Equipment &Appliances <br />Miscellaneous <br />25%Largest Motor <br />14202.0 <br />9720.0 <br />0.0 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />50.0 <br />280.0 <br />1340.0 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />14252.0 <br />10000.0 <br />1340.0 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />1.25 <br />1.00 <br />0.50 <br />1.00 <br />1.00 <br />100 <br />1.00 <br />178101.0 <br />1.000.0 <br />670.0 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />BUSSING'. MANUFACTURER'S STANDARI <br />CONTINUOUS RATING: 225 A <br />FULLAICRATING: 55,000A <br />SERIESAICRATING'. NONE <br />SPECIAL PROVISIONS: <br />MASTER NAMEPLATE <br />GROUND BAR <br />MAIN: LUGS ONLY <br />LOCATION. BOTTOM <br />TOTAL LOAD <br />TOTAL AMPS <br />239220 <br />28.8 <br />16700 <br />2.0 <br />255920 <br />30.8 <br />284850 <br />34.3 <br />CONN. <br />LOAD (VA) <br />FEEDER/BRA NCHCIRCUIT <br />DESCRIPTION E <br />BKR <br />AMP/P <br />CKT <br />NO <br />BUS <br />(PHASE) <br />CKT <br />NO <br />BKR <br />AMP/P <br />FEE DERIBRANCH CIRCUIT <br />DESCRIPTION -' <br />CONN. <br />LOAD (VAj <br />727.0 <br />LTG- CORRIDOR 2ND FLOOR 1 <br />2011 <br />1 <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />2 <br />2011 <br />LTG-SURGERYHALLWAY <br />13]6.0 <br />1204.0 <br />LTG- CORRIDOR 2ND FLOOR NORTH <br />2O11 <br />3 <br />4 <br />2011 <br />LTG-OFFICES/DR LOUNGE <br />516.0 <br />7242.0 <br />7174.0 <br />PANEL 2N2S-SECOND FLOOR <br />70/2 <br />1 <br />5 <br />7 <br />6 <br />20/1 <br />LTG - STAFF LOUNGE/STOR <br />344.0 <br />8 <br />20/1 <br />LTG - SURGERYHALLWAY <br />1505.0 <br />00 <br />SPACE <br />9 <br />10 <br />20/1 <br />LTG -STERILE CORE <br />8600 <br />00 <br />SPACE <br />11 <br />12 <br />20/1 <br />LTG- SURGERYCENTRAL AREA <br />17200 <br />0.0 <br />SPACE <br />13 <br />14 <br />20/1 <br />LTG - HOLD/CORR.ILOBBY <br />1204.0 <br />0.0 <br />SPACE <br />15 <br />16 <br />20/1 <br />LTG - OFFICE/ADMINNJAIFING <br />1075.0 <br />00 <br />SPACE <br />17 <br />18 <br />2011 <br />LTG - MAIN LOBBY <br />6450 <br />00 <br />SPACE <br />19 <br />20 <br />SPACE <br />00 <br />0.0 <br />SPACE <br />21 <br />22 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />23 <br />24 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />25 <br />26 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />27 <br />28 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />29 <br />30 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />31 <br />32 <br />SPACE <br />00 <br />0.0 <br />SPACE <br />33 <br />34 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />35 <br />36 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />37 <br />38 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />39 <br />40 <br />SPACE <br />00 <br />0.0 <br />SPACE <br />41 <br />42 <br />SPACE <br />0.0 <br />MAIN LUGS <br />NOTES: <br />(1) MODIFIED EXISTING CIRCUIT ON EXISTING CIRCUIT BREAKER <br />(2) ALL OTHER CIRCUITS ARE EXISTING TO REMAIN. <br />(3) EXISTING LOADS ARE CALCULATED FROM ORIGINAL CONSTRUCTION DOCUMENTS AND VERIFIED BYFIELD OBSERVATION. <br />(4) THE WORK IN THIS PROJECT RESULTS IN NO LOAD INCREASE TO THIS PANEL. THEREFORE NO UPSTREAM LOADS ARE CALCULATED. <br />EXISTING TRANSFORMER T2N2S (NORMAL BRANCH) <br />KVA: 37.5 PHASE: 1 <br />TYPE: DRY <br />ELECTRICAL LOAD <br />CONN. <br />LOAD (VA) <br />DEMAND <br />DEMAND <br />ENCLOSURE: NEMA1 <br />CALCULATION <br />EXIST. <br />NEW <br />I TOTAL <br />IFACTOR <br />LOAD (VA) <br />Llghtl ng <br />3076.0 <br />0.0 <br />3076.0 <br />1.25 <br />3845.0 <br />PRIMARY: 480V <br />MOUNTING: FLOOR <br />SECONDARY 120/240V <br />Gen. Purpose Oullets(First 10 KVA) <br />97200 <br />2800 <br />10000.0 <br />100 <br />100000 <br />TAPS'. 2@2.5%FCAN <br />WINDINGS'. MANUFACTURER'S <br />Gen. Purpose Outlets(RemaindeO <br />0.0 <br />1340.0 <br />1340.0 <br />0.50 <br />670.0 <br />492.5%FCBN <br />STANDARD <br />Special Purpose Outlets <br />0.0 <br />0.0 <br />0.0 <br />1.00 <br />0.0 <br />Mechanical Equipment <br />00 <br />0.0 <br />0.0 <br />1.00 <br />0.0 <br />COOLING. CA <br />SPECIAL PROVISIONS. <br />Kitchen Equipment & Appliances <br />0.0 <br />0.0 <br />0.0 <br />1.00 <br />0.0 <br />Miscellaneous <br />0.0 <br />0.0 <br />0.0 <br />1.00 <br />0.0 <br />INSULATION: CLASS 220 <br />ELECTROSTATIC SHIELD <br />25%Largest Motor <br />0.0 <br />DEPT. OF ENERGYCOMPLIANT <br />TOTAL LOAD <br />12796.0 <br />1620.0 <br />14416.0 <br />14515.0 <br />TEMP. RISE'. 150C(40C AMBIENT) <br />TOTALAMPS(PRIMARV) <br />26.7 <br />34 <br />30.0 <br />30.2 <br />TOTALAMPS (SECONDARY) <br />53.3 <br />68 <br />60A <br />60.5 <br />EXISTING PANEL 2N2S (NORMAL BRANCH) <br />(NEW WORK) <br />SECOND FLOOR <br />VOLTAGE: 12011 PH 3W <br />TYPE: PANELBOARD <br />ENCLOSURE: NEMA1 <br />MOUNTING: SURFACE <br />FEED ER/BRANCH CIRCUIT DEVICES: <br />BOLT -ON CIRCUIT BREAKERS <br />FULLAIC RATING '. 10,000A <br />SERIES AIC RATING: 22,000A <br />ELECTRICAL LOAD <br />CALCULATION <br />CONNN <br />EXIST. <br />LOAD <br />NEW <br />A <br />TOTAL <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD IVA) <br />Lighting <br />Gen. Pupose Outlets(First 10 KVA) <br />Gen. Purpose CIE.(Remarder) <br />Special Purpose Outlets <br />Mechanical Equipment <br />Kitchen Equipment &Appliances <br />Miscellaneous <br />25%Largest Motor <br />3076.0 <br />97200 <br />00 <br />0.0 <br />0.0 <br />00 <br />00 <br />0.0 <br />2800 <br />13400 <br />0.0 <br />0.0 <br />00 <br />00 <br />3076.0 <br />100000 <br />13400 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />1.25 <br />100 <br />050 <br />1.00 <br />1.00 <br />1.00 <br />1.00 <br />3845.0 <br />100000 <br />6700 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />BUSSING'. MANUFACTURER'S STANDAR <br />CONTINUOUS RATING: 225 A <br />FULLAll RATING. 22,000A <br />SERIESAICRATING. NONE <br />SPECIAL PROVISIONS: <br />MASTER NAMEPLATE <br />GROUND BAR <br />SUITABLE FOR USE AS <br />ENTRANCE EQUIPMENT <br />SERVICE <br />MAIN: CIRCUIT BREAKER <br />CONTIN UOUS RATING. 150 A <br />FULLAICRATING: 22,000A <br />SERIESAICRATING'. NONE <br />LOCATION. BOTTOM <br />TOTAL LOAD <br />TOTAL AMPS <br />127:6.0 <br />33 <br />1620.0 <br />68 <br />14416.0 <br />60.1 <br />14515.0 <br />605 <br />CONN <br />LOAD A <br />FEEDER/BRANCHCIRCUIT <br />DESCRIPTION NrnE <br />BKR <br />AMP/P <br />CKT <br />NO <br />BUS <br />PHASE <br />CKT <br />NO <br />BKR <br />AMP/P <br />FEEDER/BRANCHCIRCUIT <br />DESCRIPTION <br />NOTE <br />CONN. <br />LOAD VA <br />180.0 <br />OUTLETS - HALL (1) <br />2011 <br />1 <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />2 <br />2011 <br />OUTLETS - THERAPY <br />M <br />540.0 <br />360.0 <br />OUTLETS - HALL (1) <br />2011 <br />3 <br />4 <br />20/1 <br />OUTLETS - THERAPY M <br />360.0 <br />180.0 <br />OUTLETSHALL1 <br />2011 <br />5 <br />6 <br />2011 <br />OUTLETS -THERAPY 1 <br />360.0 <br />7200. <br />OUTLETS- CONSULT, OFFICE, BREAK <br />2011 <br />7 <br />8 <br />_2V <br />OUTLETS - WAITING, CONSULT <br />540.0 <br />1260.0 <br />OUTLETS- CONSULT, OFFICE, BREAK, THERAPY <br />2011 <br />9 <br />10 <br />20/1 <br />OUTLETS - HALL. CONSULT <br />720.0 <br />7200. <br />OUTLETS-CONSULT, OFFICE,THERAPY <br />2011 <br />11 <br />12 <br />20/1 <br />OUTLETS - WAITING, CONSULT <br />1080.0 <br />10800 <br />OUTLETS -RECEPTION <br />2011 <br />13 <br />14 <br />2011 <br />OUTLETS -WORKROOM <br />3600 <br />540.0 <br />OUTLETS -RECEPTION <br />20/1 <br />15 <br />16 <br />20/1 <br />OUTLETS- CONSULT, WORKROOM <br />720.0 <br />180.0 <br />OUTLETS- NOURISHMENT COUNTER <br />2W <br />17 <br />18 <br />20/1 <br />OUTLETS TOILET, CONSULT <br />720.0 <br />180.0 <br />OUTLETS- NOURISHMENT COUNTER <br />20/1 <br />19 <br />20 <br />20/1 <br />SPARE <br />0.0 <br />1800 <br />OUTLETS-NOURISHMENTCOUNTER <br />20/1 <br />21 <br />22 <br />2011 <br />SPARE <br />00 <br />180.0 <br />OUTLETS -NOURISHMENT COUNTER <br />2011 <br />23 <br />24 <br />20/1 <br />SPARE <br />6.0 <br />180.0 <br />OUTLETS- U.C. REFRIGERATOR <br />2011 <br />25 <br />26 <br />2011 <br />SPARE <br />0.0 <br />0.0 <br />SPARE <br />2011 <br />27 <br />28 <br />20/1 <br />LTG- BEHAVIORAL HEALTH 1 <br />1286.0 <br />0.0 <br />SPARE <br />20/1 <br />29 <br />30 <br />20/1 <br />LTG- BEHAVIORAL HEALTH 1 <br />814.0 <br />0.0 <br />SPACE <br />31 <br />32 <br />20/1 <br />SPARE <br />0.0 <br />00 <br />SPACE <br />33 <br />34 <br />2011 <br />SPARE <br />00 <br />00 <br />SPACE <br />35 <br />36 <br />2011 <br />SPARE <br />00 <br />0.0 <br />SPACE <br />37 <br />38 <br />20/1 <br />LIFES <br />488.0 <br />0.0 <br />SPACE <br />39 <br />40 <br />20/1 <br />LIFES <br />488.0 <br />00 <br />SPACE <br />41 <br />42 <br />2011 <br />SPARE <br />00 <br />MAIN CIRCUIT BREAKER <br />NOTES: <br />(1) MODIFIED EXISTING CIRCUIT ON EXISTING CIRCUIT BREAKER <br />(2) NEW CIRCUIT CONNECTED TO EXISTING SPARE CIRCUIT BREAKER. <br />(3) ALL OTHER CI <br />RCUIFS ARE EXISTING TO REMAIN. <br />(4) EXISTING LOADS ARE CALCULATED FROM ORIGINAL CONSTRUCTION DOCUMENTS AND VERIFIED BY FIELD OBSERVATION. <br />(5) THE WORK IN THIS PROJECT RESULTS INA NET LOAD DECREASE TO THIS PANEL. THEREFORE NO UPSTREAM LOADS ARE CALCULATED. <br />EXISTING PANEL 4N1 (NORMAL BRANCH) (EXISTING CONDITIONS) <br />FIRST FLOOR <br />VOLTAGE: 480Y/277V, 3 PH, 4 W <br />TYPE: PANELBOARD <br />ENCLOSURE. NEMA1 <br />MOUNTING: SURFACE <br />FEEDERIBRANCH CIRCUITDEVICES: <br />BOLT -ON CIRCUIT BREAKERS <br />FULLAICRATING. 14,000A <br />SERIES AIC RATING: 65,n00A <br />ELECTRICAL LOAD <br />CALCULATION <br />CONN.LOAD <br />EXIST. <br />NEW <br />VA <br />TOTAL <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD VA <br />Lighting <br />Gen. Puose Outets(FmNtl0 KVA) <br />Hurt, <br />Gen. Purpose Outlets(Remainder) <br />Special Purpose Outlets <br />Mechanical Equipment <br />Kitchen Equipment & Appliances <br />Miscellaneous <br />25%Largest Molar <br />14234.0 <br />1n0000 <br />1520.0 <br />0.0 <br />00 <br />0.0 <br />00 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />14234.01 <br />100000 <br />1520.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />1.25 <br />100 <br />0.50 <br />1.00 <br />100 <br />1.00 <br />1.00 <br />17792.5 <br />100000 <br />760.0 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />0.0 <br />BUSSING'. MANUFACTURER'S STANDAR <br />CONTINUOUS RATING: 225 A <br />FULLAICRATING: 85,000A <br />SERIESAICRATING'. NONE <br />SPECIAL PROVISIONS: <br />MASTER NAMEPLATE <br />GROUND BAR <br />MAIN: LUGS ONLY <br />LOCATION. BOTTOM <br />TOTAL LOAD <br />TOTALAMPS <br />25754.0 <br />310 <br />0.0 <br />00 <br />25754.0 <br />310 <br />28552.5 <br />343 <br />CONN. <br />LOAD A <br />FEEDER/BRANCHCIRCUIT <br />DESCRIPTION <br />BKR <br />AMP/P <br />CKT <br />NO <br />BUS <br />toHASE <br />CKT <br />NO <br />BKR <br />AMP/P <br />FEEDER/BRANCH CIRCUIT <br />DESCRIPTION s <br />CONN. <br />LOAD VA <br />709.0 <br />LTG- CORRIDOR2ND FLOOR <br />20/1 <br />1 <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />2 <br />20/1 <br />LTG - SURGERY HALLWAY <br />1376.0 <br />12040 <br />LTG- CORRIDOR 2ND FLOOR NORTH <br />20/1 <br />3 <br />4 <br />20/1 <br />LTG- OFFICES/DR LOUNGE <br />5180 <br />7082.0 <br />7534.0 <br />PANEL 2N2S-SECOND FLOOR <br />70/2 <br />1 <br />5 <br />7 <br />6 <br />20/1 <br />LTG- STAFF LOUNGE/STOR <br />344.0 <br />8 <br />20/1 <br />LTG - SURGERY HALLWAY <br />1505.0 <br />00 <br />SPACE <br />9 <br />10 <br />20/1 <br />LTG-STERILECORE <br />8600 <br />0.0 <br />SPACE <br />11 <br />12 <br />20/1 <br />LTG- SURGERYCENTRAL AREA <br />1720.0 <br />0.0 <br />SPACE <br />13 <br />14 <br />20/1 <br />LTG-HOLD/CORR./LOBBV <br />1204.0 <br />00 <br />SPACE <br />15 <br />16 <br />20/1 <br />LTG-OFFICE/ADMIN/WAIFING <br />10750 <br />0.0 <br />SPACE <br />17 <br />18 <br />20/1 <br />LTG - MAIN LOBBY <br />645.0 <br />0.0 <br />SPACE <br />19 <br />20 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />21 <br />22 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />23 <br />24 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />25 <br />26 <br />SPACE <br />00 <br />0.0 <br />SPACE <br />27 <br />28 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />29 <br />30 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />31 <br />32 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />33 <br />34 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />35 <br />36 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />37 <br />38 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />39 <br />40 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />41 <br />42 <br />SPACE <br />0.0 <br />MAIN LUGS <br />EXISTING PANEL 2N2S (NORMAL BRANCH) <br />(EXISTING CONDITIONS) <br />SECOND FLOOR <br />VOLTAGE: 120240V,I PH, 3W <br />TYPE: PANELBOARD <br />ENCLOSURE: NEMA1 <br />MOUNTING. SURFACE <br />FEEDERNBRANCH CIRCUIT DEVICES: <br />BOLT -ON CIRCUIT BREAKERS <br />FULLAICRATING'. 10,000A <br />SERIES All RATING. 22,000A <br />ELECTRICAL LOAD <br />CALCULATION <br />CONN. <br />EXIST, <br />LOAD <br />NEW <br />VA <br />I TOTAL <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD VA <br />Lighting <br />Gen Purpose Outlels(Firsi KVA) <br />Gen Puryose0utlels(Remainder) <br />Special Purpose Outlets <br />Mechanical Equipment <br />Kitchen Equipment & Appliances <br />Miscellaneous <br />25%Largest Motor <br />30760 <br />10000.0 <br />15200 <br />00 <br />0.0 <br />00 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />30760 <br />10000.0 <br />1520.0 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />125 <br />1.00 <br />0.50 <br />1.00 <br />1.00 <br />100 <br />1.00 <br />38450 <br />10000.0 <br />760.0 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />BUSSING'. MANUFACTURER'S STANDARL <br />CONTINUOUS RATING. 225 A <br />FULLAICRATING: 22,000A <br />SERIESAICRATING'. NONE <br />SPECIAL PROVISIONS: <br />MASTER NAMEPLATE <br />GROUND BAR <br />SUITABLE FOR USE AS SERVICE <br />ENTRANCE EQUIPMENT <br />MAIN: CIRCUIFBREAKER <br />CONTINUOUS RATING: 150 A <br />FULLAICRATING: 22,000A <br />SERIES All RATING. NONE <br />LOCATION'. BOTTOM <br />TOTALLOAD <br />TOTALAMPS <br />14596.0 <br />608 <br />0.0 <br />00 <br />14598.0 <br />608 <br />14605.0 <br />609 <br />CONN. <br />LOAD A <br />FEEDER/BRANCH CIRCUIT <br />DESCRIPTION <br />BKR <br />AMP/P <br />CKT <br />N <br />BUS <br />toHASE) <br />CKT <br />BKR <br />MP/P <br />FEEDER/BRANCH CIRCUIT <br />DESCRIPTION <br />` <br />CONN. <br />LOAD VA <br />180.0 <br />OUTLETS - CONTROL ROOM 215 <br />20A <br />1 <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />B <br />A <br />2 <br />20/1 <br />OUTLETS - CONTROL ROOM 215 <br />360.0 <br />00 <br />SPARE <br />2011 <br />3 <br />4 <br />2011 <br />OUTLETS - ROOM 4 <br />3600 <br />180.0 <br />OUTLETS -CONTROL ROOM 215 <br />20M <br />5 <br />6 <br />20/1 <br />OUTLETS -ROOM 4, WAITING <br />360.0 <br />900.0 <br />OUTLETS - ROOMS 1, 2, 3 <br />2011 <br />7 <br />8 <br />20/1 <br />OUTLETS - WAITING <br />540.0 <br />1260.0 <br />OUTLETS - ROOMS 12,3 <br />20M <br />9 <br />10 <br />20/1 <br />OUTLETS - COPIER <br />720.0 <br />12600 <br />OUTLETS - ROOMS 123 <br />2011 <br />11 <br />12 <br />20/1 <br />OUTLETS - FILE AREA <br />10800 <br />1080.0 <br />OUTLETS - RECEPTION <br />20M <br />13 <br />14 <br />20/1 <br />OUTLETS -ROOM 5, BATHROOM <br />360.0 <br />54M <br />OUTLETSRECEPTION20/1 <br />15 <br />16 <br />20/1 <br />OUTLETS- FILE AREA 203 SLEEP ROOM 218 <br />720.0 <br />1800 <br />OUTLETS -KITCHEN <br />2011 <br />17 <br />18 <br />20/1 <br />OUTLETS- TOILET 217, SLEEP ROOM 218 <br />7200 <br />180.0 <br />OUTLET -TOASTER <br />20M <br />19 <br />20 <br />20/1 <br />SPARE <br />0.0 <br />180.0 <br />OUTLETPOPCORN2011 <br />21 <br />22 <br />20/1 <br />SPARE <br />0.0 <br />180.0 <br />OUTLETS - MICROWAVE <br />20A <br />23 <br />24 <br />20/1 <br />SPARE <br />0.0 <br />180.0 <br />OUTLETS- U.C. REFRIGERATOR <br />20M <br />25 <br />26 <br />20/1 <br />SPARE <br />0.0 <br />0.0 <br />SPARE <br />20M <br />27 <br />28 <br />20/1 <br />LTG - SLEEP LAB <br />1288.0 <br />0.0 <br />SPARE <br />20/1 <br />29 <br />30 <br />20/1 <br />LTGSLEEPLAB <br />814.0 <br />00 <br />SPACE <br />31 <br />32 <br />2011 <br />SPARE <br />0.0 <br />0.0 <br />SPACE <br />33 <br />34 <br />20/1 <br />SPARE <br />0.0 <br />0.0 <br />SPACE <br />35 <br />36 <br />2011 <br />SPARE <br />0.0 <br />0.0 <br />SPACE <br />37 <br />38 <br />20/1 <br />LIrES <br />488.0 <br />0.0 <br />SPACE <br />39 <br />40 <br />20/1 <br />LIFES <br />488.0 <br />00 <br />SPACE <br />41 <br />42 <br />20/1 <br />SPARE <br />00 <br />MAIN CIRCUIT BREAKER <br />2727 Oakes Ave. <br />Suite 100 <br />Everett, WA 98201 <br />REVISIONS <br />R. <br />,EA <br />v1P� <br />0 <br />5N <br />0 M794 <br />�' F'1018TIi4�' ti� <br />2ONAL <br />E�yG <br />U - <br />�� <br />.0 CIO <br />CIO •> <br />A <br />(L <br />U N _ <br />^1 I <br />O <br />•> O Q <br />O O O <br />IL LL CL <br />III N. 2375 <br />n- Err KL <br />-nit er SO <br />CONSTRUCTION SET <br />12-17-2024 <br />ELECTRICAL - <br />PANEL <br />SCHEDULES <br />E 6.3 <br />City of Everett Permit Services <br />EVERETT Reviewed for Permit 01/14/2025 <br />