EXISTING PANEL 2N2B (NORMAL BRANCH) <br />(NEW WORK) <br />SECOND FLOOR <br />VOLTAGE. 208Y/120V, 3 PH, 4 W <br />TYPE: PANELBOARD <br />ENCLOSURE: NEMA1 <br />MOUNTING. SURFACE <br />FEEDERBRANCH CIRCUIT DEVICES. <br />BOLTONCIRCUIT BREAKERS <br />FULL AIC RATING: 10,000A <br />SERIES AIC RATING. 22,000A <br />ELECTRICAL LOAD <br />CALCULATION <br />CONN. <br />EXIST. <br />LOAD <br />NEW <br />VA <br />TOTAL <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD VA <br />Lighting <br />Gen. Purpose Oullets(First lO KVA) <br />Gen. Purpose OWets(Remalnder) <br />Special Purpose Outlets <br />Mechanical Equipment <br />Kitchen Equipment & Appliances <br />Miscellaneous <br />25%Largest Motor <br />23250 <br />10000.0 <br />54800 <br />5250.0 <br />0.0 <br />00 <br />0.0 <br />Oo <br />0.0 <br />00 <br />a0 <br />0,0 <br />0.0 <br />0.0 <br />2325.0 <br />10000.0 <br />54800 <br />5250.0 <br />0.0 <br />00 <br />0.0 <br />1.25 <br />1.00 <br />050 <br />1.00 <br />1.00 <br />100 <br />1.00 <br />2906.3 <br />10000.0 <br />27400 <br />5250.0 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />BUSSING: MAN UFACTURER'SSTANDAR <br />CONTINUOUS RATING: 225 A <br />FULLAICRATING: 22,000A <br />SERIES AIC RATING. NONE <br />SPECIAL PROVISIONS'. <br />MASTER NAMEPLATE <br />GROUND BAR <br />PROVIDE HANDLE TIES FOR ALL <br />MULTI -WIRE BRANCH CIRCUITS <br />MAIN: LUGS ONLY <br />LOCATION. TOP <br />TOTAL LOAD <br />TOTALAMPS <br />23055.0 <br />640 <br />0.0 <br />00 <br />23055.0 <br />64.0 <br />20896.3 <br />500 <br />CONN. FEEDER/BRANCHCIRCUIT <br />LOAD A DESCRIPTION <br />` <br />BKR <br />AMP/P <br />CKT <br />NO <br />BUS CKT BKR <br />PHASE NO AMP/P <br />FEEDERBRANCH CIRCUIT <br />DESCRIPTION <br />"LOAD <br />CONN. <br />A <br />MAIN LUGS <br />200.0 <br />LTG- ROOM 200, 201, 202,203 <br />20/1 <br />1 <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />2 <br />2011 <br />LTG- PATIENT ROOM 217 <br />200.0 <br />200o <br />LTG- ROOM 204, 205, 206, 207 <br />20/1 <br />3 <br />4 <br />2011 <br />LTG- PATIENT ROOM 217 <br />200.0 <br />200o <br />LTG- ROOM 208, 209, 210,211 <br />20/1 <br />5 <br />6 <br />2011 <br />LTG- PATIENT ROOM 218 <br />200.0 <br />150.0 <br />LTG- ROOM 212A, 212B, 213 <br />2011 <br />7 <br />8 <br />20/1 <br />LTG- PATIENT ROOM 218 <br />2020. <br />1500 <br />LTG- ROOM 214, 215, 216 <br />20/1 <br />9 <br />10 <br />2011 <br />LTG- PATIENT ROOM 219 <br />2000 <br />150.0 <br />LTG- ROOM 217, 218, 219 <br />20/1 <br />11 <br />12 <br />2011 <br />LTG- PATIENT ROOM 219 <br />200.0 <br />75.0 <br />LTG- WAITING ROOMS <br />20/1 <br />13 <br />14 <br />2011 <br />SPARE <br />0.0 <br />1800 <br />OUTLET -ROOFTOP <br />20/1 <br />15 <br />16 <br />20/1 <br />SPARE <br />00 <br />180.0 <br />OUTLET -ROOFTOP <br />20/1 <br />17 <br />18 <br />2011 <br />SPARE <br />0.0 <br />720o <br />OUTLETS - CORRIDORS <br />20/1 <br />19 <br />20 <br />2011 <br />OUTLETS- RESTROOM/ACTIVITY <br />1 <br />360.0 <br />720o <br />OUTLETS - CORRIDORS <br />26SI <br />21 <br />22 <br />2011 <br />OUTLETS - TOILET(ACTMRY <br />1080.0 <br />720.0 <br />OUTLETS -CORRIDORS <br />2011 <br />23 <br />24 <br />2011 <br />OUTLETS- VOLUNTEERANAITING <br />1080.0 <br />5400 <br />OUTLETS-PHARNIACY/MED <br />20/1 <br />25 <br />26 <br />2011 <br />SPARE OLD REFRIG <br />00 <br />180.0 <br />OUTLET -ROOF 4TH FLOOR BYPSE#6 FAN <br />20/1 <br />27 <br />28 <br />2011 <br />SPARE OLD MICROWAVE <br />0.0 <br />0.0 <br />SPARE <br />20/1 <br />29 <br />30 <br />2011 <br />SPARE OLD DISHWASHER <br />0.0 <br />00 <br />SPARE <br />20/1 <br />31 <br />32 <br />20/1 <br />OUTLET - LOUNGE AREA <br />5400 <br />0.0 <br />SPARE <br />20/1 <br />33 <br />34 <br />2011 <br />SPARE OLD INSTA-HO <br />0.0 <br />Oo <br />SPARE <br />20/1 <br />35 <br />36 <br />2011 <br />OUTLET -WAITING ROOM <br />900.0 <br />Oo <br />SPARE <br />20/1 <br />37 <br />38 <br />2011 <br />SPARE <br />0.0 <br />0.0 <br />SPACE <br />39 <br />40 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />41 <br />42 <br />SPACE <br />a <br />SUB -FEED LUGS <br />PANEL 2N2C <br />4880.0 <br />5280.0 <br />33]0 0 <br />NOTES: <br />(1) MODIFIED EXISTING CROUTON EXISTING CIRCUIT BREAKER <br />(2) NEWCIRCUITCONNECTED TO EXISTING SPARE CIRCUIT BREAKER. <br />(3) ALL OTHER CIRCUITS ARE EXISTING TO REMAIN. <br />(4) EXISTING LOADS ARE CALCULATED FROM ORIGINAL CONSTRUCTION DOCUMENTS AND VERIFIED BY FIELD OBSERVATION. <br />(5) NO LOAD IS ADDED TOTHISPANEL. THEREFORE NO UPSTREAM LOADS ARE CALCULATED. <br />EXISTING PANEL 4Y2 (CRITICAL BRANCH) (NEW WORK) SECOND FLOOR <br />VOLTAGE. 480YY2]]V, 3 PH, 4W <br />TYPE: PANELBOARD <br />ENCLOSURE: NEMA1 <br />MOUNTING: SURFACE <br />FEEDER/BRANCH CIRCUIT DEVICES: <br />BOLT -ON CIRCUIT BREAKERS <br />FULL AIC RATING: 14,000A <br />SERIES AIC RATING'. 65,000A <br />ELECTRICAL LOAD <br />CALCULATION <br />CONN. <br />EXIST. <br />LOAD <br />NEW <br />A <br />TOTAL <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD (VA) <br />Lighting <br />Gen. Purpose Dull -(First 10 KVA) <br />Gen. Purpose Outlets Remainder <br />rp <br />Special Purpose Outlets <br />Mechanical Equipment <br />Kitchen Equipment&Appliances <br />Miscellaneous <br />25% Largest Motor <br />0.0 <br />00 <br />00 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />00 <br />0o <br />0.0 <br />00 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />1.25 <br />1.00 <br />0.50 <br />1.00 <br />1.00 <br />100 <br />1.00 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />BUSSING: MANUFACTURER'S STANDARI <br />CONTINUOUS RATING: 225 A <br />FULL AIC RATING: 65,000A <br />SERIESAICRATING NONE <br />SPECAL PROVISIONS'. <br />MASTERNAMEPIATE <br />GROUND BAR <br />MAIN: LUGS ONLY <br />LOCATION: BOTTOM <br />TOTAL LOAD <br />TOTALAMPS <br />00 <br />0.0 <br />00 <br />0.0 <br />00 <br />0.0 <br />16 <br />0.0 <br />CONN. <br />LOAD (VA <br />FEEDERBRANCHCIRCUIT <br />DESCRIPTION E <br />BKR <br />AMPIP <br />CKT <br />NO <br />BUS <br />(PHASE) <br />CKT <br />NO <br />BKR <br />BKR <br />FEEDERBRANCH CIRCUIT <br />DESCRIPTION 1E <br />CONN. <br />LOAD (VA) <br />0.0 <br />LTG -ICU/CCU DEPT. <br />20/1 <br />1 <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />2 <br />2011 <br />LTG- ROOM 200,201,202,203 <br />0.0 <br />0o <br />LTG - ICU/CCU DEPT. <br />2011 <br />3 <br />4 <br />20/1 <br />LTG- ROOM 204,205,206,207 <br />0.0 <br />0.0 <br />SPARE <br />20/1 <br />5 <br />6 <br />20/1 <br />LTG- ROOM 208,209,210,211 <br />0.0 <br />0.0 <br />SPARE (1) <br />20/1 <br />7 <br />8 <br />2011 <br />LTG- ROOM 212A, 2126,213, 214 <br />0.0 <br />0.0 <br />SPACE <br />9 <br />10 <br />2011 <br />LTG -ROOM 216216,217 <br />0.0 <br />00 <br />SPACE <br />11 <br />12 <br />20/1 <br />LTG -ROOM 218, 219 <br />00 <br />0.0 <br />SPACE <br />13 <br />14 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />15 <br />16 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />17 <br />18 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />19 <br />20 <br />SPACE <br />00 <br />0.0 <br />SPACE <br />21 <br />22 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />23 <br />24 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />25 <br />26 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />27 <br />28 <br />SPACE <br />00 <br />0.0 <br />SPACE <br />29 <br />30 <br />SPACE <br />0.0 <br />0o <br />SPACE <br />31 <br />32 <br />SPACE <br />0.0 <br />0o <br />SPACE <br />33 <br />34 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />35 <br />36 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />37 <br />38 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />39 <br />40 <br />SPACE <br />00 <br />00 <br />SPACE <br />41 <br />42 <br />SPACE <br />00 <br />MAIN LUGS <br />NOTES: <br />(1) EXISTING CIRCUIT REMOVED AND CIRCUIT BREAKER MADE SPARE <br />(2) ALL OTHER CIRCUITS ARE EXISTING TO REMAIN. <br />(3) NO LOAD IS ADDED TO THIS PANEL. THEREFORE NO EXISTING LOAD IS CALCULATED AND NO UPSTREAM LOADS ARE CALCULATED. <br />EXISTING PANEL 2N213 (NORMAL BRANCH) <br />(EXISTING CONDITIONS) <br />SECOND FLOOR <br />VOLTAGE: 20BY/12OV, 3 PH, 4W <br />TYPE: PANELBOARD <br />ENCLOSURE. NEMA1 <br />MOUNTING: SURFACE <br />FEEDER/BRANCH CIRCUIT DEVICES. <br />BOLTONCIRCUIT BREAKERS <br />FULL AIC RATING. 10,000A <br />SERIES AIC RATING: 22000A <br />ELECTRICAL LOAD <br />CALCULATION <br />CONN.LOAD <br />EXIST <br />NEW <br />A <br />TOTAL <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD VA <br />Lighting <br />Gen. Purpose OWets(Fust 10 KVA) <br />Gen. Purpose Outlets (Remainder) <br />Special Purpose Outlets <br />Mechanical Equipment <br />Kitchen Eguipment&Appliarees <br />Miscellaneous <br />25% Largest Motor <br />2325.0 <br />100000 <br />5480.0 <br />5250o <br />0.0 <br />0.0 <br />00 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />2325.0 <br />100000 <br />5480.0 <br />5250.0 <br />00 <br />0.0 <br />0.0 <br />1.25 <br />100 <br />0,50 <br />1,00 <br />100 <br />1.00 <br />1,00 <br />2906.3 <br />100000 <br />2740.0 <br />5250.0 <br />00 <br />0.0 <br />0.0 <br />0.0 <br />BUSSING: MA NUFACTURER'S STANDAR <br />CONTINUOUS RATING: 225A <br />FULLAICRATING 22,000A <br />SERIESAICRATING: NONE <br />S PEC AL P ROVISIONS: <br />MASTERNAMEPLATE <br />GROUND BAR <br />PROVIDE HANDLE TIES FOR ALL <br />MULTTWIRE BRANCH CIRCUITS <br />MAIN: LUGS ONLY <br />LOCATION: TOP <br />TOTAL LOAD <br />TOTALAMPS <br />23055.0 <br />64o <br />0.0 <br />0.0 <br />23055.0 <br />64.0 <br />20896.3 <br />58.0 <br />CONN. FEEDER/BRANCHCIRCUIr <br />LOAD A DESCRIPTION O1E <br />BKR <br />-AM <br />CKT <br />NO <br />BUS CKT BKR <br />PHASE NO AMP, <br />FEEDER/BRANCH CIRCUIT <br />DESCRIPTION <br />1e <br />CONN. <br />LOAD VA <br />MAIN LUGS <br />2000 <br />LTG- ROOM200201202203 <br />2011 <br />1 <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />2 <br />20/1 <br />LTG - PATIENT ROOM 217 <br />2000 <br />200.0 <br />LTG - ROOM 204, 205, 2' 207 <br />2011 <br />3 <br />4 <br />2011 <br />LTG - PATIENT ROOM 217 <br />2000. <br />200.0 <br />LTG - ROOM 208, 209, 210 211 <br />20/1 <br />5 <br />6 <br />20/1 <br />LTG - PATIENT ROOM 218 <br />2000. <br />1500 <br />LTG- ROOM 212A, 212B, 213 <br />20/1 <br />7 <br />8 <br />20/1 <br />LTG -PATIENT ROOM 218 <br />2000 <br />150.0 <br />LTG - ROOM 214, 215, 216 <br />20/1 <br />9 <br />10 <br />20/1 <br />LTG - PATIENT ROOM 219 <br />2000. <br />150.0 <br />LTG - ROOM 217, 218, 219 <br />2011 <br />11 <br />12 <br />2011 <br />LTG - PATIENT ROOM 219 <br />2000. <br />75.0 <br />LTG -WAITING ROOMS <br />20/1 <br />13 <br />14 <br />20/1 <br />SPARE <br />0.0 <br />1800 <br />OUTLET - ROOFTOP <br />2011 <br />15 <br />16 <br />20/1 <br />SPARE <br />00 <br />180.0 <br />OUTLET - ROOFTOP <br />20/1 <br />17 <br />18 <br />20/1 <br />SPARE <br />0.0 <br />720.0 <br />OUTLETS - CORRIDORS <br />20/1 <br />19 <br />20 <br />20/1 <br />OUTLETS -RESTROOM <br />360.0 <br />7200 <br />OUTLETS -CORRIDORS <br />20/1 <br />21 <br />22 <br />20/1 <br />OUTLETS- RESTROOM, CLASSROOM <br />10800 <br />720.0 <br />OUTLETS - CORRIDORS <br />20/1 <br />23 <br />24 <br />20/1 <br />OUTLETS- VOLUNTEERANAITING <br />1080.0 <br />540.0 <br />OUTLETS -PHARMACY/MED <br />20/1 <br />25 <br />26 <br />2011 <br />SPARE OLD REFRIG <br />0.0 <br />180.0 <br />OUTLET- ROOF 4TH FLOOR BY PS E#6 FAN <br />20/1 <br />27 <br />28 <br />20/1 <br />SPARE OLD MICROWAVE <br />0.0 <br />00 <br />SPARE <br />2011 <br />29 <br />30 <br />20/1 <br />SPARE OLD DISHWASHER <br />00 <br />0.0 <br />SPARE <br />20/1 <br />31 <br />32 <br />20/1 <br />OUTLET - LOUNGE AREA <br />540.0 <br />0.0 <br />SPARE <br />20/1 <br />33 <br />34 <br />20/1 <br />SPARE OLD INSTA-HO <br />0.0 <br />00 <br />SPARE <br />20/1 <br />35 <br />36 <br />20/1 <br />OUTLET -WAITING ROOM <br />9000 <br />0.0 <br />SPARE <br />20/1 <br />37 <br />38 <br />20/1 <br />SPARE <br />0.0 <br />0.0 <br />SPACE <br />39 <br />40 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />41 <br />42 <br />SPACE <br />0.0 <br />SUB-FEED LUGS <br />PANEL2N2C <br />48800 <br />5280.0 <br />3370.0 <br />EXISTING PANEL 4Y2 (CRITICAL BRANCH) (EXISTING CONDITIONS) <br />SECOND FLOOR <br />VOLTAGE. 48DY1277V, 3 PH, 4W <br />TYPE: PANELBOARD <br />ENCLOSURE: NEMA1 <br />MOUNTING: SURFACE <br />FEEDER/BRANCH CIRCUIT DEVICES: <br />BOLT -ON CIRCUIT BREAKERS <br />FULL AIC RATING: 14,000A <br />SERIES AIC RATING'. 65,000 A <br />ELECTRICAL LOAD <br />CALCULATION <br />CONN. <br />EXIST. <br />LOAD <br />NEW <br />A <br />TOTAL <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD (VA) <br />Lighting <br />Gen. Purpose Outlets (First 10 KVA) <br />Gen. Purpose Outlets (Remainder) <br />Special Purpose Outlets <br />Mechanical Equipment <br />Kitchen Equipment&Appliances <br />Miscellaneous <br />25% Largest Motor <br />0.0 <br />0 0 <br />00 <br />0.0 <br />0.0 <br />00 <br />00 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />00 <br />no <br />0.0 <br />0.0 <br />0.0 <br />00 <br />0.0 <br />0.0 <br />0.0 <br />1.25 <br />1.00 <br />0.50 <br />1.00 <br />1.00 <br />100 <br />1.00 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />BUSSING: MANUFACTURER'S STANDAR <br />CONTINUOUS RATING: 225 A <br />FULL AIC RATING: 65,000A <br />SERIESAICRATING NONE <br />SPECIAL PROVISIONS'. <br />MASTER NAMEPLATE <br />GROUND BAR <br />MAIN: LUGS ONLY <br />LOCATION: BOTTOM <br />TOTAL LOAD <br />TOTALAMPS <br />00 <br />0.0 <br />00 <br />0.0 <br />00 <br />0.0 <br />00 <br />0.0 <br />CONN. <br />LOAD(VA) <br />FEEDERBRANCH CIRCUIT <br />DESCRPTION a <br />BKR <br />AMP/P <br />CKT <br />NO <br />BUS <br />(PHASE) <br />CKT <br />NO <br />DESCRIPTION 1E <br />LOAD(VA) <br />0o <br />LTG-ICU/CCU DEPT. <br />2011 <br />1 <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />A <br />B <br />C <br />2 <br />LTG- ROOM 200,201,202,203 <br />0.0 <br />0o <br />LTG-ICU/CCU DEPT. <br />2011 <br />3 <br />4 <br />LTG- ROOM 204,205,206,207 <br />0.0 <br />0.0 <br />SPARE <br />20/1 <br />5 <br />6 <br />LTG- ROOM 208,209,210,211 <br />0.0 <br />0.0 <br />LTG- EQUIPMENT STORAGE&ITT ROOM <br />2011 <br />7 <br />8 <br />LTG- ROOM212A, 2128, 213,214 <br />0.0 <br />SPACE <br />9 <br />10 <br />dAMP/P <br />LTG -ROOM 215,216,217 <br />00 <br />00 <br />SPACE <br />11 <br />12 <br />LTG-ROOM218,219 <br />00 <br />0.0 <br />SPACE <br />13 <br />14 <br />0.0 <br />0.0 <br />SPACE <br />15 <br />16 <br />0.0 <br />00 <br />SPACE <br />17 <br />18 <br />00 <br />0.0 <br />SPACE <br />19 <br />20 <br />0.0 <br />0.0 <br />SPACE <br />21 <br />22 <br />SPACE <br />0.0 <br />0o <br />SPACE <br />23 <br />24 <br />SPACE <br />0.0 <br />0o <br />SPACE <br />25 <br />26 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />27 <br />28 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />29 <br />30 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />31 <br />32 <br />SPACE <br />00 <br />0.0 <br />SPACE <br />33 <br />34 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />35 <br />36 <br />SPACE <br />0.0 <br />0.0 <br />SPACE <br />37 <br />38 <br />SPACE <br />0.0 <br />00 <br />SPACE <br />39 <br />40 <br />SPACE <br />a6 <br />0.0 <br />SPACE <br />41 <br />42 <br />SPACE <br />0.0 <br />MAIN LUGS <br />2727 Oakes Ave. <br />Suite 100 <br />Everett, WA 98201 <br />REVISIONS <br />R. <br />,EA <br />v1P� <br />O <br />l <br />5N <br />0 g4794 �,1�1 ,Q' <br />� F'101BTIi4�' l�V <br />70NAL0i <br />O <br />U co <br />N N <br />Cn = <br />III Na 2375 <br />r- aY KL <br />rn ED er SO <br />CONSTRUCTION SET <br />12-17-2024 <br />ELECTRICAL - <br />PANEL <br />SCHEDULES <br />E6.4 <br />City of Everett Permit Services <br />EVERETT Reviewed for Permit 01/14/2025 <br />