ELECTRICAL PLAN NOTES ELECTRICAL GENERAL NOTES <br /> O FOR EACH RELOCATED EQUIPMENT,MATCH NEMA CONFIGURATION,WIRE GAUGE, AL, <br /> PROVIDE RECEPTACLE IF NOT EXISTING AND EXTEND BRANCH CIRCUITAS REQUIRED A. ANY EXISTING CONDITIONS INDICATED IN THIS SET OF DRAWINGSARE BASED ON G. WHERE THE MECHANICAL DESIGN UTILIZES A PLENUM RETURN AIR CEILING <br /> TO COMPLETE THE CONNECTION.CIRCUIT NUMBER SHALL MATCH EXISTING.DO NOT INFORMATION PROVIDED BY OTHERS AND POSSIBLE LIMITED FIELD VERIFICATION. DEISGN,ALL EQUIPMENT AND MATERIALS INSTALLED WITHIN THE PLENUM RETURN <br /> ABANDON EXISTING WORK.PROVIDE ADDITIONAL CASEWORK PENETRATIONS AS ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE CEILING MUST MEET THE FLAME SPREAD AND SMOKE DEVELOPED RATINGS OF <br /> A 10005 REQUIRED TO PROVIDE THE FINAL EQUIPMENT CONNECTION, OWNER, 26160 AND BE APPROVED FOR USE IN PLENUM RETURN CEILINGS.COORDINATED <br /> A 10007 A 10002 O RELOCATED(5)UNDER COUNTER REFRIGERATOR. B. VISIT THE PROJECT SITE,REVIEW EXISTING CONDITIONS AGAINST THE CONTRACT PLENUM CEILING LOCATIONS WITH THE MECHANICAL CONTRACTOR. W <br /> A 10022 DOCUMENTS,AND BECOME FAMILIAR WITH THE WORK PRIOR TO BIDDING AND START H.COORDINATE ALL DEVICE LOCATIONS AND CIRCUIT ROUTING WITHIN ANY 'A <br /> O3 RELOCATED GRINDER. OF WORK,SIGNING THE CONTRACT IS AN ACKNOWLEDGEMENT THAT THE SITE VISIT M ILLWORK WITH MILLWORK VENDOR PRIOR TO ROUGH-IN. v+HAS BEEN COMPLETED AND THE EXISTING CONDITIONS ARE ACCEPTED. <br /> 1 O RELOCATED(2)ESPRESSO MACHINE. I. COORDINATE THE CONNECTIONS OF ALL EQUIPMENT PROVIDED BY OTHERS WITH <br /> C. ANY EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION THROUGHOUT THE CONTRACTOR PROVIDING THE EQUIPMENT PRIORTO ROUGH-IN.THIS <br /> O RELOCATED POS. CONSTRUCTION.AUTOMATIC SMOKE DETECTORS IN THEAREA OF CONSTRUCTION INCLUDES,BUT IS NOT LIMITED TO,MECHANCIAL EQUIPMENT,KITCHEN EQUIPMENT, <br /> 7+80" <br /> SHALL BE DISCONNECTED AND TEMPORARILY REPLACED WITH HEAT DETECTORS AUDIONISUAL EQUIPMENT,FIRE SUPPRESSION SYSTEM EQUIPMENT,FIRE ALARM <br /> r2 WHEN THE SPACE IS STAFFED BY THE CONTRACTOR IN ACCORDANCEWITH THE EQUIPMENT,ETC.PROVIDE THE APPROPRIATE DISCONNECTING MEANS FOR,AND23 B RELOCATED(2)CUP LABELER. APPROVED FIRE SAFETY PROCEDURES OF THE OWNER AND THE LOCAL FIRE TO MAKE THE FINAL CONNECTION TO,ANY HARDWIRED EQUIPMENT.THE" RELOCATED(2)BLENDER MARSHAL,BUT SHALL BE REACTIVATED WHENEVER THE SPACE IS NOT OCCUPIED ELECTRICAL CONTRACTOR IS ALSO RESPONSIBLE TO PROVIDE AN APPROPRIATE oSTA RBUCKS® <br /> BY THE CONTRACTOR.AUTOMATIC SMOKE DETECTORS SHALL BE PROTECTED CORD AND PLUG FOR ANY CORD AND PLUG CONNECTED EQUIPMENT THAT IS NOT 2835 N MCCARRAN BLVD#103 <br /> RELOCATED(2)OVENS. FROM DUST AND DIRT ACCUMILATION BY REMOVING THE DEVICE FROM ITS BASE EQUIPPED WITH AN INTEGRAL CORD AND PLUG.DURING THOSE TIMES WHEN THE SYSTEM IS ALLOWED TO BE OUT OF OPERATION. SPARKS,NEVADA 89431 <br /> J. SEE PANEL SCHEDULES FOR INFORMATION ON CIRCUITS THAT ARE TO BE ROUTED <br /> RELOCATED DRIVE THRU POS. D. DEMOLISH ANY EXISTING EQUIPMENT,DEVICES,AND LUMINAIRES AS INDICATED THROUGH CONTACTORS OR RELAYS FOR CONTROL. r (775)331-8551 <br /> 10 RELOCATED FOOD CASE. AND/OR AS REQUIRED TO ALLOW FOR INSTALLATION AND CONSTRUCTION OF THE <br /> NEW WORK.REMOVE ALL EQUIPMENT,DEVICES,LUMINAIRES,CONDUITS, K. ALL LUGS,TERMINALS,ETC.IN ELECTRICAL DISTRIBUTION EQUIPMENT SHALL BE U THESE DRAWINGS AND THE PROJECT MANUAL <br /> 11 RELOCATED(2)INSTAHOT. SUPPORTS,HANGERS,ETC.THAT ARE NOT SHOWN AND ARE REQUIRED TO BE LISTED FOR A MINIMUM OF 75 DEGREE C CONDITIONS.TERMINATIONS LISTED FOR ARE CONFIDENTIAL AND SHALL REMAIN THE <br /> REMOVED IN ORDER TO COMPLETE THE NEW WORK ONLY 60 DEGREE C CONDITIONS ARE NOT PERMITTED. = SOLE PROPERTY OF STARBUCKS <br /> E. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR L. CONDUCTORS#12 AND SMALLER SHALL BE SOLID.CONDUCTORS#10 AWG AND CORPORATION,WHICH IS THE OWNER OF THE <br /> ENTIRETY.CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE DEMOLISHED LARGER ARE PERMITTED TO BE STRANDED. Ii/ COPYRIGHT IN THIS WORK.THEY SHALL NOT <br /> BE REPRODUCED(IN WHOLE IN PART), <br /> TO THE SOURCE OVERCURRENT DEVICE.RACEWAYS WHICH ARE INSTALLED IN OR ` SNARED WITH THIRD PARTIES OR <br /> USED IN ANY <br /> BELOW FLOORS OR WITHIN WALLS MAY BE ABANDONED,BUT ALL OVERHEAD OR r MANNER ON OTHER PROJECTS OR <br /> ELECTRICAL KEYED NOTES EXPOSED RACEWAYS SHALL BE REMOVED.EXPOSED RACEWAYS TO BE I_ EXTENSIONS TO THIS PROJECT WITHOUT THE <br /> ABANDONED SHALL BE REMOVED AND SHALL BE CUT OR CHISELED AT LEAST 2" PRIOR WRITTEN CONSENT OF STARBUCKS <br /> Q PROVIDE FIRE-RATED PLYWOOD BACKBOARD AND CONDUIT SLEEVE FOR INTO THE WALL OR FLOOR AND THE OPENING GROUTED SMOOTH. CORPORATION.THESE DRAWINGS AND <br /> LOW VOLTAGE CABLE,SEE DETAIL SHEET. F. MAINTAIN CONTINUITY OF EXISTING CIRCUITS AS REQUIRED TO PROVIDE POWER SPECIFICATIONS ARE INTENDED T EXPRESS <br /> ENLARGED MANAGER'S DESK AND EQUIPMENT DES <br /> TO REMAINING EQUIPMENT,DEVICES AND LUMINAIRS THAT ARE NOT BEING ENTFORAPROTOC <br /> STARBUUCKSCKS STORE(WHICH IS SUBJECT <br /> TO <br /> RACK POWER AND SYSTEMS PLAN REMOVED. 0 CHANGEATANYTIME)AND DO NOT REFLECT <br /> ACTUAL SITE CONDITIONS.NEITHER PARTY <br /> SHALL HAVE ANY OBLIGATION NOR LIABILITY TO <br /> THE OTHER(EXCEPT STATED ABOVE)UNTIL A <br /> WRITTEN AGREEMENT IS FULLY EXECUTED BY <br /> BOTH PARTIES. <br /> O STARBUCKS TEMPLATE VERSION:2023.04.24 <br /> LL ARCHITECT OF RECORD <br /> 0 � <br /> W <br /> GRAPHITE DESIGN GROUP,LLC,ARCHITECTS <br /> 0 <br /> 1807 7TH AVENUE,SUITE 700 <br /> SEATTLE,WA 98101 <br /> NI g -__Jr z (208)224-3335 <br /> 1t W <br /> A 10267 Ror SCy <br /> A 10075 E 23442 E 10267 z <br /> .-..._ <br /> 2 <br /> I� I .2 r2 O ONAL oore �o/zs/za <br /> 1 COA/'2609 <br /> �0 <br /> - <br /> ---- -- , <br /> 2 k / <br /> o 0 rn <br /> 2 2 294g4 r <br /> 2 od <br /> 8-25 <br /> - - - - - - — - - - -- - = z a o <br /> y <br /> +eo" O 8 a <br /> �0_� <br /> iti t i.2 4 2 "2 Ii F N <br /> O LL O O <br /> � e EL �aUj <br /> E 20011 + <br /> 21679 E 23419 <br /> E 23421 <br /> STORE#: 22817 <br /> 9 > PROJECT M 60007-039 <br /> ISSUE DATE: 10.2.2023 <br /> W DESIGN MANAGER: GRAPHITE <br /> QPRODUCTION DESIGNER: GRAPHITE <br /> CHECKED BY: <br /> 6" <br /> Q Revision Schedule <br /> Z <br /> !� '^ Data By Description <br /> ,V <br /> V/ <br /> W <br /> SHEET TITLE: <br /> G ENLARGED POWER AND <br /> SYSTEMS PLANS <br /> SCALE:AS SHOWN <br /> ENLARGED ENGINE POWER AND SYSTEMS PLAN ^ khmc�l SHEET NUMBER: <br /> o i y =r r-0 ry <br /> E102 <br />