Laserfiche WebLink
PLUMBING SPECIFICATIONS - <br /> 0 <br /> PLUMBING WORK,GENERAL B. FIRE SPRINKLER SYSTEM MATERIALS = <br /> A. GENERAL REQUIREMENTS <br /> 1. CONTRACT REQUIREMENTS: COMPLY WITH BIDDING AND CONTRACT REQUIREMENTS AS OUTLINED BY THE INDUSTRIES MODEL 30N,COMBINATION SPRING AND DOUBLE DEFLECTION NEOPRENE HANGER,DEFLECTION 1. APPROVED MANUFACTURERS: VIK CORP.,STAR SPRINKLER CORP.,RELIABLE AUTOMATIC SPRINKLER <br /> OWNER AND ARCHITECT. AS RECOMMENDED BY MANUFACTURER. VIBRATION ISOLATORS FOR BASE MOUNTED EQUIPMENT SHALL BE CO., LL FIRE PROTECTION S SY YSTEMS CO.,"AUTOMATIC"SPRINKLER CORP.OF AMERICA,CENTRAL <br /> EQUAL TO MASON INDUSTRIES MODEL SLF,DEFLECTION AS RECOMMENDED BY MANUFACTURER. SPRINKKLERLER CORP.,GLOBE FIRE EQUIPMENT CO.,MICHIGAN. o <br /> 2. WORK INCLUDED: THIS SECTION APPLIES TO ALL MECHANICAL WORK NORMALLY SPECIFIED UNDER 2. GENERAL COMPONENTS: ALL REQUIRED COMPONENTS,INCLUDING VALVES,FLOW SWITCHES,TAMPER Z <br /> DIVISIONS 22 AND 23. PROVIDE ALL MATERIALS,LABOR,EQUIPMENT,TOOLS,FIELD DESIGN,SHOP C. EQUIPMENT AND PIPING IDENTIFICATION SWITCHES,HANGERS,FIRINGS,AND OTHER ACCESSORIES,SHALL MEET NFPA STANDARDS,AND SHALL <br /> DRAWINGS,HOISTING,SCAFFOLDING,SUPERVISION AND OVERHEAD FOR THE CONSTRUCTION,INSTALLATION, HAVE UL AND FM LISTING WHERE SUCH LISTING IS AVAILABLE. t V <br /> CONNECTION,TESTING AND OPERATION OF ALL MECHANICAL WORK AS SHOWN AND SPECIFIED. THE WORD 1. NAMEPLATES: PROVIDE NAMEPLATE FOR EACH PIECE OF EQUIPMENT,INCLUDING EQUIPMENT NUMBER AND U N <br /> "PROVIDE"USED HEREINAFTER MEANS TO FURNISH AND INSTALL. ALL WORK AND MATERIALS REQUIRED ANY SPECIAL INSTRUCTION FOR ITS USE;LAMINATED BLACK AND WHITE PLASTIC WITH LETTERING CUT 3. PIPE ASTM-135 OR ASTM A-53,STAMPED ON PIPE. SCHEDULE 40 BLACK STEEL,WITH THREADED y <br /> FOR COMPLETE FUNCTIONING SYSTEMS ARE NOT OUTLINED HERE,BUT SHALL BE PROVIDED AS PART OF THROUGH TO WHITE BACKGROUND. MINIMUM SIZE 3"X 1'. OR GROOVED FITTINGS;SCHEDULE 10 ACCEPTABLE FOR ROLL-GROOVED ONLY. THREADED FITTINGS � L) <br /> THIS WORK. OZ. <br /> 2. PIPE IDENTIFICATION: ALL PIPING IN SERVICEABLE LOCATIONS INCLUDING ABOVE LAY-IN CEILINGS)SHALL THROUGH 2",ANSI 816.4 BLACK. OVER 2'GROOVE FITTINGS,ANSI/ASTM A47,MCTAUUC STYLE 75, <br /> 3. CODES: COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES OF THE LOCAL AND STATE CODE BE IDENTIFIED WITH SEMI-RIGID PLASTIC OR ADHESIVE IDENTIFICATION MARKERS. MARKERS SHALL 750,77,OR FM APPROVED EQUAL FITTINGS. m Q �w <br /> ENFORCING AGENCIES. OBTAIN PERMITS,APPROVALS,AND INSPECTIONS,AND PAY ALL COSTS AND FEES CONFORM TO ANSI A13.1,'SCHEME FOR THE IDENTIFICATION OF PIPING SYSTEMS". LOCATE MARKERS 4. SPRINKLER HEADS: WHERE INSTALLED IN SUSPENDED CEILINGS,SPRINKLER HEADS SHALL BE CHROME fw <br /> FOR PERMITS,REVIEWS,AND INSPECTIONS. ADJACENT TO EACH VALVE,AT MINIMUM 30'CENTERS WITH AT LEAST ONE MARKER BETWEEN ANY TWO PLATED RECESSED PENDANT TYPE WITH CHROME ESCUTCHEONS. TEMPERATURE RATINGS AND W? <br /> LL�8 <br /> 4. ABBREVIATIONS: WHERE ABBREVIATIONS ARE USED IN THE SPECIFICATIONS AND ON THE DRAWINGS,THE PARTITIONS. PROVIDE DIRECTION OF FLOW ARROWS AT MARKERS. RESPONSE TIME AS REQUIRED BY AUTHORITIES. HEADS SHALL MATCH EXISTING HEADS IN THE �z _T <br /> BUILDING,TO THE EXTENT POSSIBLE. PROVIDE SPARE HEADS,NOT LESS THAN TWO OF EACH TYPE, <br /> COMMON INDUSTRY DEFINITION SHALL APPLY UNLESS INDICATED OTHERWISE. THE TERM A/E SHALL Uwj�� <br /> / D. MISCELLANEOUS MATERIALS AND ACCESSORIES OR MORE AS REQUIRED BY NFPA. I <br /> REFER TO THE PROJECT ARCHITECT AND MECHANICAL CONSULTING ENGINEER AS IF ONE ORGANIZATION. <br /> 1. DIELECTRIC UNIONS: PROVIDE AT EACH PIPE CONNECTION BETWEEN DISSIMILAR METALS. 2 INCHES AND DOMESTIC WATER AND DRAINAGE <br /> 5. SUBMITTALS: SUBMIT PRODUCT DATA AND SHOP DRAWINGS FOR ALL SIGNIFICANT MATERIALS,EQUIPMENT, SMALLER,250 PSIG AT 180 DEG.F.,ANSI B16.39. OVER 2"USE FLANGE FITTINGS,ANSI 816.42(IRON) <br /> AND FIXTURES TO THE A/E FOR REVIEW. ALLOW REASONABLE TIME FOR REVIEW AND RETURN PRIOR TO OR ANSI B16.24(BRONZE),WATTS 3000 SERIES,EPCO OR EQUIVALENT. A PIPING SYSTEMS <br /> ORDERING. PDF(ELECTRONIC)SUBMITTALS AREA ACCEPTABLE,IF PAPER COPIES ARE SUBMITTED ASSUME 1. DOMESTIC WATER PIPING: TYPE L COPPER WATER TUBE,HARD DRAWN,ASTM B 88. WROUGHT <br /> OWNER AND A/E WILL RETAIN A TOTAL OF THREE COPIES OF SUBMITTALS. 2. FIRE SEALING AT RATED WALLS AND FLOORS: PROVIDE UL LISTED FIRE RATED PUTTY AT ALL PIPE COPPER SOLDER FITTINGS AND SCREWED ADAPTERS,ANSI 816.22.J. SOLDER;95 PERCENT TIN,5 2727 Oakes Ave. <br /> PENETRATIONS OF RATED WALLS AND FLOORS. PUTTY SHALL BE INSTALLED STRICTLY PER MANUFACTURER PERCENT ANTIMONY SOLDER,ASTM B 32,95TA Suite 100 <br /> 6. SAFETY MEASURES: PROVIDE A SAFE ENVIRONMENT TO PROTECT EMPLOYEES AND ALL OTHERS FROM INSTRUCTIONS WITH SLEEVES WHERE REQUIRED. OVERALL INSTALLATION SHALL MEET CODE Everett,WA 98201 <br /> INJURY. COMPLY WITH LOCAL,STATE AND FEDERAL SAFETY AND HEALTH REGULATIONS FOR REQUIREMENTS. PIPE INSULATION SHALL NOT BE CONTINUOUS THROUGH FIRE RATED WALLS OR FLOORS. 2. DOMESTIC PIPING INSULATION: PREFORMED GLASS FIBER WITH VAPOR BARRIER JACKET AND A FLAME <br /> CONSTRUCTION. SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50,THICKNESS PER THE REVISIONS <br /> 3. MOTORS: UNLESS OTHERWISE SPECIFIED,ALL ELECTRIC MOTORS FURNISHED SHALL CONFORM WITH THE CURRENT ENERGY CODE. EXTERIOR EXPOSED PIPING SHALL BE COVERED WITH.015 IN THICK <br /> B. PERFORMANCE OF WORK REQUIREMENTS OF NEMA MG1 "MOTORS AND GENERATORS." PROVIDE MINIMUM MOTOR EFFICIENCIES AS ALUMINUM JACKET WITH TWO-INCH LAPS AND BANDED WITH 3/8"STAINLESS STEEL BANDS AT 9"ON <br /> REQUIRED BY THE ENERGY CODE. CENTER. SEAL LAPS WITH SILICONE SEALANT. <br /> 1. COORDINATION: COORDINATE MECHANICAL WORK WITH ALL OTHER TRADES AND TAKE ALL MEASUREMENTS <br /> NECESSARY TO ENSURE PROPER INSTALLATION OF MECHANICAL WORK PRIOR TO START OF FABRICATION. 4. INTERCONNECTING WIRING: PROVIDE ANY NECESSARY INTERCONNECTING WIRING BETWEEN INDIVIDUAL 3. CONDENSATE DRAIN PIPING AND FITTINGS: SEAMLESS TYPE L COPPER WITH 95-5 SOLDER. INSULATE <br /> THIS CONTRACTOR SHALL CREATE BUILDING INFORMATION MODELS(BIM)AND/OR LARGE-SCALE DETAIL COMPONENTS AND ACCESSORIES FURNISHED WITH MECHANICAL EQUIPMENT PACKAGES(UNLESS THAT CONDENSATE DRAIN PIPING WITH 1/2"INCH THICK ARMSTRONG'ARMAFLIX'OR EQUAL <br /> DRAWINGS WHERE NECESSARY TO COORDINATE WORK IN TIGHT AREAS. THE CONTRACT DRAWINGS DO NOT WIRING IS SPECIFICALLY CALLED FOR ON THE ELECTRICAL DRAWINGS). WIRING AND WIRING ACCESSORIES <br /> ATTEMPT TO SHOW EXACT LOCATIONS OF DUCTWORK,PIPING,FIXTURES,AND EQUIPMENT,OR ALL SHALL BE IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS(AND/OR THE SPECIFICATIONS ON THE 4. SMALL VALVES(2"AND SMALLER): BALL VALVES FED.SPEC.WW-V-35,250-PSIG BRONZE OR <br /> TRANSITIONS AND OFFSETS THAT WILL BE NECESSARY FOR INSTALLATION. ALL NECESSARY TRANSITIONS ELECTRICAL DRAWINGS)AND LOCAL ELECTRICAL CODE. WIRING SHALL BE IN CONDUIT OR RACEWAY. BRASS BODY,BALL AND STEM,SOLDER ENDS OR SCREWED,TEFLON SEAT AND SEAL. CHECK VALVES <br /> AND OFFSETS SHALL BE PROVIDED AS PART OF THIS WORK WITHOUT ADDED COMPENSATION. WIRING SHALL BE PROVIDED AT THE EXPENSES OF THE SUBCONTRACTOR FURNISHING THE EQUIPMENT AND OTHER VALVES SHALL BE OF EQUAL QUALITY AND SAME MANUFACTURER OF BALL VALVES AND <br /> 2. CONTINUITY OF SERVICE: ANY SYSTEMS OR SERVICES WITHIN EXISTING OCCUPIED BUILDINGS SHALL BE PACKAGE. SHALL HAVE NOT LESS THAN 125-PSIG RATING.GATE VALVES(ALLOWED ONLY WHERE INDICATED)MSS <br /> MAINTAINED WITH MINIMUM INTERRUPTION. COORDINATE ANY NEEDED INTERRUPTIONS WITH THE OWNER. SP80, 125-PSIG BRONZE,SCREWED OR SOLDER END,UNION BONNET,RISING STEM,SOLID BRONZE <br /> EXECUTION OF WORK DISC. PROVIDE SHUT-OFF VALVES AT ALL EQUIPMENT CONNECTIONS. <br /> ANY OVERTIME WORK REQUIRED BY THIS PROJECT TO MAINTAIN EXISTING BUILDINGS IN CONTINUOUS E. <br /> SERVICE,WITHOUT REDUCING THEIR EFFICIENCY,SHALL BE INCLUDED AS A PART OF THIS CONTRACT. 5. ROOF DRAIN,WASTE AND VENT PIPING: ASTM A74 STANDARD WEIGHT HUBLESS CAST IRON PIPE,CISPI Ql�W <br /> 1. INSTALLATION,GENERAL: FOLLOW MANUFACTURER'S INSTRUCTIONS AND UTILIZE GOOD INDUSTRY PRACTICE N`9 <br /> .� of esg7Ll'� <br /> 3. DEMOLITION: PROVIDE MECHANICAL SYSTEM DEMOLITION IN AREAS OF EXISTING BUILDINGS TO WHEN INSTALLING ALL WORK. USE ONLY SKILLED TRADESPEOPLE WITH QUALIFIED SUPERVISION. ALL 301. COUPLINGS;NEOPRENE SLEEVE GASKET,STAINLESS STEEL SHIELD AND BANDS. FITTINGS SHALL <br /> ACCOMMODATE INSTALLATION OF NEW WORK. EXISTING PIPING,VALVES,AND DUCTWORK,WHERE INDICATED WORK SHALL BE LEFT NEAT AND CLEAN. BE STANDARD WEIGHT CAST IRON SOIL PIPE FITTINGS,ANSI A712.5.1 AND ASTM A74. HUBLESS CAST �e <br /> IRON FITTINGS,CISPI 301. <br /> ON THE DRAWINGS,MAY BE REUSED IN THEIR ORIGINAL LOCATION. DO NOT REUSE EXISTING PIPING, <br /> VALVES,OR DUCTWORK ONCE THEY ARE REMOVED,UNLESS WRITTEN PERMISSION IS OBTAINED FROM 2. CONCEALMENT: PIPING AND DUCTWORK SHALL BE CONCEALED WITHIN BUILDING CONSTRUCTION,UNLESS B. PLUMBING ACCESSORIES AND EQUIPMENT: <br /> OWNER. REMOVE ALL UNUSED PIPING AND DUCTWORK LOCATED IN REMODEL AREAS OF EXISTING SPECIFICALLY INDICATED OTHERWISE WHERE PIPING IS INDICATED TO BE EXPOSED TO VIEW IN FINISHED <br /> BUILDINGS. SPACES OR CABINETS,PROVIDE CHROME ESCUTCHEONS WHERE THE PIPING PENETRATES THE WALL,FLOOR <br /> OR CEILING CONSTRUCTION 1. REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLIES: REDUCED PRESSURE TYPE BACK-FLOW Igyp1 <br /> 4. CUTTING AND PATCHING: PROVIDE ALL CUTTING OF BUILDING CONSTRUCTION,AS REQUIRED FOR THIS PREVENTER;3/4"TO 2"SIZE;BRONZE CONSTRUCTION WITH ISOLATING BALL VALVES,STRAINER AND <br /> WORK. KEEP CUTTING TO A MINIMUM,AND USE SAW CUTTING TO MAINTAIN NEAT,EVEN OPENINGS. 3. WATER SEALING AT FLOORS: PROVIDE WATER TIGHT SEALING AT EACH FLOOR PENETRATION INCLUDING AIR GAP DRAIN FITTING. HERSEY MODEL FRPII,WATTS 909 SERIES OR APPROVED EQUIVALENT. S�pplP4 <br /> UNLESS PATCHING IS INCLUDED UNDER OTHER DIVISIONS OF THIS SPECIFICATION,PROVIDE PATCHING AT PIPING WITHIN WALL CAVITIES. PROVIDE WATER SLEEVES SEALED TO THE FLOOR CONSTRUCTION AND PROVIDE CERTIFICATION OF BACKFLOW PREVENTER BY STATE CERTIFIED SPECIALIST,INCLUDE WITH <br /> ALL CUTTING LOCATIONS. All PATCHING SHALL CONFORM TO SPECIFICATIONS FOR THE NEW GENERAL PROJECTING NOT LESS THAN 1.5"ABOVE FLOOR WHERE INSULATED PIPING PENETRATES THE FLOOR. THE MAINTENANCE MANUALS. <br /> CONSTRUCTION WORK. FINISH TO MATCH EXISTING WORK. INTENT IS TO MINIMIZE PASSAGE OF WATER DURING A SIGNIFICANT WATER LEAKAGE EVENT. SEALING IS p, PRESSURE REDUCING VALVES: 2 INCH AND SMALLER,COMPLETE WITH INTEGRAL STRAINER,PRESSURE <br /> REQUIRED FOR CONCRETE FLOORS,BUT NOT REQUIRED FOR OTHER FLOOR SYSTEMS WHERE THE GAUGE,AND INTEGRAL THERMAL EXPANSION AN BY-PASS,BRONZE CONSTRUCTION WITH STAINLESS STEEL <br /> C. PROJECT COMPLETION CONSTRUCTION ITSELF,AT THE PIPE PENETRATION,ALLOWS SIGNIFICANT WATER SEEPAGE(PLANKED WOOD STRAINER. WATTS AL HE OR EQUIVALENT. <br /> FLOOR FOR EXAMPLE). Q <br /> 1. RECORD DRAWINGS(AS-BU CORRECTIONS AND CHANGES MADE DURING THE PROGRESS OF THE 3. STRAINERS: 2-1/2 INCHES AND SMALLER,BRONZE,Y-PATTERN,THREADED ENDS,20-MESH <br /> WORK SHALL BE NEATLY RECORDED LE ACTUALLY INSTALLED FOR AS-BUILT RECORDS. FURNISH ONE 4. COORDINATION WITH OTHER TRADES: COMPLETE DRAWINGS AND SPECIFICATIONS OF ALL TRADES WILL STAINLESS STEEL SCREEN;250 PSI AT 210 F. z J <br /> CLEAN SET TO THE A/E UPON COMPLETION OF THE PROJECT. BE FURNISHED OR WILL BE AVAILABLE FOR INSPECTION IN THE CONSTRUCTION OFFICE AT THE <br /> JOBSITE. CAREFULLY CHECK THESE DRAWINGS AND SPECIFICATIONS BEFORE INSTALLING ANY WORK. 4. FLOOR DRAINS: SMITH 2O05,DOUBLE DRAINAGE,ADJUSTABLE STRAINER HEAD FLOOR DRAIN,DUCO O Q <br /> 2. OPERATION AND MAINTENANCE MANUALS: PROVIDE(3)FINISHED COPIES OF MECHANICAL OPERATION AND IN ALL CASES,CONSIDER THE WORK OF ALL OTHER TRADES AND COORDINATE WORK WITH THAT OF BEST ARRANGEMENT OF ALL EQUIPMENT,PIPING,CONDUIT,DUCTS,AND OTHER RELATED ITEMS CAN BE THE SHEET METAL,PIPING,PLUMBING,ELECTRICAL,AND SITE-WORK SUBCONTRACTORS,SO THAT THE COATED CAST IRON BODY,FLASHING COLLAR,NICKEL BRONZE STRAINER WITH 1/4"HOLES. PROVIDE I <br /> MAINTENANCE MANUALS,FOR WORK UNDER THIS PROJECT. ARRANGE INFORMATION CONTAINED IN THE SQUARE STRAINER IN AREAS WITH TILE FLOORS AND ROUND STRAINERS IN OTHER LOCATIONS. WHERE Li <br /> MANUALS IN AN ORDERLY ARRANGEMENT(8Y SPECIFICATION SECTION),SEPARATED BY TABS. PROVIDE OBTAINED. FUNNEL DRAINS ARE INDICATED,ADD SMITH 3590 ROUGH BRONZE FUNNEL REMOVE STRAINER WITHIN I <br /> EQUIPMENT MANUFACTURER,MODEL NUMBER,SIZE,CAPACITY,PERFORMANCE DATA,SCHEDULE OF ROUTINE FUNNEL,AS REQUIRED,TO ELIMINATE SPLASHING. Li = <br /> MAINTENANCE,SUPPLIERS LISTS,UST OF REPLACEMENT PARTS,AND INCLUDE ANY SHOP DRAWINGS. PLUMBING INSULATION <br /> 5. EQUIPMENT,GENERAL: PROVIDE ALL EQUIPMENT CONSISTENT WITH THE CAPACITY,MANUFACTURER, V� II <br /> 3. OWNER INSTRUCTION: CONTRACTOR SHALL INSTRUCT THE OWNER IN THE USE AND OPERATION OF ALL A GENERAL MODEL NUMBER,AND ACCESSORIES AS SPECIFIED OR INDICATED ON THE DRAWING SCHEDULES AND J <br /> SYSTEMS INSTALLED UNDER THIS CONTRACT. OBTAIN OWNER'S WRITTEN ACCEPTANCE THAT THEY HAVE 1. MANUFACTURERS: MANVILLE,OWENS-CORNING,CERTAINTEED,OR KNAUF. INSTALL IN ACCORDANCE NOTES. EQUIPMENT SUPPLIERS SHALL VERIFY THAT MODEL NUMBERS ARE CONSISTENT WITH CAPACITY, ` <br /> BEEN ADEQUATELY TRAINED. WITH MANUFACTURER'S INSTRUCTIONS. FEATURES,AND ACCESSORIES CALLED FOR AND IDENTIFY ANY CONFLICTS PRIOR TO SUBMITTING v <br /> QUOTATIONS TO CONTRACTORS. ALL EQUIPMENT WITH ELECTRICAL COMPONENTS SHALL HAVE UL <br /> 4. GUARANTEE: GUARANTEE MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR AFTER THE DATE 2. INSULATION THICKNESS: REFER TO INSULATION REQUIREMENTS ON THE DRAWINGS FOR SYSTEMS TO LISTING AS REQUIRED BY THE ELECTRICAL INSPECTOR. ALTERNATE MANUFACTURERS WILL BE <br /> OF SUBSTANTIAL COMPLETION. REFER TO ADDITIONAL REQUIREMENTS OUTLINED BY ARCHITECT AND BE INSULATED AND THICKNESS OF INSULATION. CONSIDERED;HOWEVER,A/E FINAL APPROVAL OF EQUALITY OF ALTERNATE MANUFACTURER MODES IS O <br /> OWNER. BASIC MATERIALS AND METHODS(APPLIES TO ALL WORK) REQUIRED. ACCEPTABLE ALTERNATE MANUFACTURERS INCLUDE BELL AND GOSSE T,AMTROL,TACO,AO ' ` <br /> B. INSULATION MATERIALS SMITH,STATE,OR AS INDICATED OR PRIOR-APPROVED OTHERWISE. ALTERNATE MANUFACTURERS WITH v <br /> 1.1. WORK INCLUDED: THIS SECTION APPLIES TO ALL MECHANICAL WORK NORMALLY SPECIFIED UNDER PRIOR APPROVAL ARE STILL RESPONSIBLE FOR MEETING OR EXCEEDING THE QUALITY AND FEATURES <br /> DIVISIONS 21,22 AND 23,AND REPRESENTS REQUIREMENTS IN ADDITION TO THE REQUIREMENTS 1. INDOOR PIPE INSULATION: FIBERGLASS PIPE INSULATION WITH ALL-SERVICE(VAPOR BARRIER)JACKET OF THE SPECIFIED ITEMS. Q Q <br /> SEATED OTHER SECTIONS. THESE SPECIFICATIONS DO NOT COVER ALL ITEMS THAT WILL BE SHALL BE PROVIDED FOR ALL PIPING SYSTEMS,EXCEPT REFRIGERANT PIPING. FIRINGS SHALL BE <br /> REQUIRED FOR COMPLETE AND WORKING SYSTEMS. WHERE MATERIALS OR EQUIPMENT NEEDED FOR MITERED SECTIONS OF INSULATION WITH THE SAME THICKNESS AS ADJACENT PIPE INSULATION WITH PLUMBING FIXTURES <br /> THIS PROJECT ARE NOT COVERED IN THESE SPECIFICATIONS,PROVIDE THE E INDUSTRY <br /> AND EQUIPMENT FACTORY-PREMOLDED,ONE-PIECE,UL LISTED(25/50)PVC FIRING COVERS. INSTALLATION MUST <br /> OF A QUALITY EQUAL E E BETTER THAN THAT GENERALLY UTILIZED BY THE INDUSTRY FOR SIMILAR REFLECT CAREFUL WORKMANSHIP,AND BE NEAT IN APPEARANCE.VAPOR BARRIER SHALL BE SEALED A. PLUMBING FIXTURE ACCESSORIES <br /> PROJECTS IN THE SAME GEOGRAPHIC AREA AT ALL JOINTS ON COLD PIPING. 1. CONCEAL CARRIERS: PROVIDE CAST IRON OR STEEL CARRIERS FOR ALL WAIL-HUNG FIXTURES WITH LiJ L,J <br /> CONCEALED FIXTURE CARRIERS CONSTRUCTED FOR THE PARTICULAR FIXTURE,HEAVY DUTY ` <br /> D. SUPPORT AND HANGERS 2. OUTDOOR PIPE INSULATION: INSULATION AND FITTINGS SAME AS SPECIFIED FOR INDOOR PIPE CONSTRUCTION WITH SECURE ANCHORING TO CONCRETE FLOOR. SMITH,WADE,ZURN,OR APPROVED. V M <br /> INSULATION. PROVIDE METAL JACKETS OF 0.016"ALUMINUM WITH INTEGRAL VAPOR RETARDER, BACK LUG OF WATER CLOSET CARRIERS SHALL BE ANCHORED TO FLOOR. <br /> 1. SUPPORT MECHANICAL SYSTEMS: EACH PIECE OF EQUIPMENT SHALL BE SUPPORTED(FROM ABOVE SELF-SEALING,WATERTIGHT METAL BANDS FOR BUR JOINTS. SEAL JOINTS WITH ALUMINUM PIGMENTED Z <br /> OR BELOW))IN NOT LESS THAN FOUR CORNERS FROM THE BUILDING STRUCTURE. PIPING AND DUCTWORK VAPOR RETARDER MASTIC,FOSTER 60-65,OR APPROVED EQUIVALENT. 2. DRAINS AND TRAPS: PROVIDE GRID STRAINER DRAINS FOR ALL LAVATORIES UNLESS INDICATED L,J <br /> SHALL BE SUPPORTED AT INTERVALS SPECIFIED,WITH EACH SYSTEM SUPPORTED INDEPENDENTLY FROM OTHERWISE. PROVIDE BASKET STRAINER DRAINS FOR ALL SINKS UNLESS INDICATED OTHERWISE. <br /> THE BUILDING STRUCTURE. PROVIDE TRAPS AND TAILPIECES AT ALL FIXTURES UNLESS TRAP IS INTEGRAL WITH FIXTURE. Q <br /> 3. ROOF DRAIN BODY INSULATION: FLEXIBLE FIBERGLASS BLANKET CONFORMING i0 ASTM C 553,TYPE I, <br /> Fy <br /> 2. SEISMIC BRACING: PROVIDE COMPLETE SEISMIC BRACING FOR ALL NEW PIPING,DUCTWORK,TERMINAL AND NOMINAL DENSITY NOT LESS THAN 1 LB.PER CUBIC FOOT,COVERED WITH 8-OUNCE CANVAS 3. STOPS: PROVIDE CHROME STOPS AT EACH WATER CONNECTION TO EACH FIXTURE,EXCEPT WHERE A LJ_ <br /> UNITS AND EQUIPMENT AS REQUIRED BY THE CURRENT IBC WITH ALL LOCAL AMENDMENTS AN ASCE/SCI AND VAPOR RETARDER CEMENT. FAUCET OR CONTROL HAS INTEGRAL STOPS.STOPS SHALL BE A LOOSE KEY PATTERN WITH SHIELD; \ O <br /> 7-10(THE CURRENT CODE). BRACING MAY BE PER GUIDELINES ESTABLISHED BY RESTRAINT FIRE PROTECTION CHICAGO,BRIDGEPORT BRASS,BRASS CRAFT(SPEEDWAY),TELEDYNE,OR EQUIVALENT. <br /> MANUFACTURERS SUCH AS;MASON INDUSTRIES AND I.SAT PROVIDED THEY MEET THE CURRENT CODE.ALL BRACING SHALL BE DESIGNED A AN ID MANUFACTURED BY MASON,LSAT,OR PRIOR-APPROVED A 4. CAULKING: PROVIDE SILICONE SEALER BETWEEN THE TOP AND THE SIDES OF PLUMBING FIXTURES O O <br /> AND ADJACENT WALL SURFACES;GENERAL ELECTRIC N0.SCS202. APPLY PER MANUFACTURER'S <br /> 0 <br /> GENERAL CTRIC <br /> ALTERNATE. 3. CONNECTIONS TO THE BUILDING STRUCTURE: PROVIDE ALL NECESSARY CONNECTIONS 1. WORK INCLUDED: DESIGN AND PROVIDE ALTERATIONS TO,AND EXTENSION OF,THE EXISTING FIRE RECOMMENDATIONS TO FORM A SMOOTH,UNOBTRUSIVE JOINT/ L-` <br /> TO THE BUILDING STRUCTURE FOR SEISMIC RESTRAINTS AID SUPPORTS. WHERE CONCRETE STRUCTURE PROTECTION SYSTEM,TO ACCOMMODATE THE NEW SPACE LAYOUT AND INSTALL ALL WORK IN <br /> IS PRESENT,REVIEW THE USE OF CONCRETE ANCHORS WITH THE ARCHITECT,OWNER,AND GENERAL ACCORDANCE NFPA 13,ALL OTHER APPLICABLE CODES,STANDARDS,AND REGULATIONS,AND AS <br /> CONTRACTOR,AND VERIFY THAT THERE ARE NO POSE-TENSIONED SLABS OR OTHER CONDITIONS THAT REQUIRED BY THE AUTHORITY HAVING JURISDICTION. WORK SHALL INCLUDE ALTERATIONS TO THE 5. EXPOSED PLUMBING: IN GENERAL,ALL PIPING SHALL BE CONCEALED UNLESS INDICATED OTHERWISE. <br /> NEED TO BE TAKEN INTO ACCOUNT IN SETTING OF ANCHORS. UTILIZE MCCULLOUGH"KWIK-BOLT", EXISTING FIRE SPRINKLER PIPING AS NEEDED TO MAKE REASONABLE CLEARANCE FOR NEW WORK BY ANY PIPING THAT MUST BE EXPOSED WITHIN CABINETS OR OTHERWISE,DUE TO CONNECTIONS <br /> PHILLIPS SELF-DRILLING ANCHORS,GREGORY'BULLDOG,"OMARK"DRILL ANCHORS',OR OTHER APPROVED OTHER TRADES. REQUIRED FOR FIXTURES AND EQUIPMENT,SHALL BE PAINTED SILVER. ALL EXPOSED ITEMS, <br /> ANCHOR TO ATTACH TO CONCRETE STRUCTURES. WHERE BUILDING STRUCTURE IS WOOD OR STEEL, INCLUDING STOPS,TRAPS,ETC.,SHALL BE CHROME PLATED. <br /> OBTAIN ARCHITECT APPROVAL OF HARDWARE AND METHODS TO BE UTILIZED FOR ATTACHMENT TO THE 2. SYSTEM TYPE: PROVIDE WET-PIPE SPRINKLER PROTECTION FOR ALL HEATED AREAS. WHERE B. PLUMBING FIXTURES 242095 <br /> STRUCTURE. SPRINKLER COURAGE OF UNHEATED AREAS IN AND AROUND THE BUILDING IS REQUIRED,PROVIDE <br /> EITHER A DRY-PIPE SYSTEM OR DRY-SPRINKLER COVERAGE FROM THE NET SYSTEM. IF A DRY-PIPE 1. GENERAL: PROVIDE THE PLUMBING FIXTURES AS ON THE DRAWINGS. PROVIDE THE oenw"er CEI <br /> 4. ADDITIONAL FRAMING: PROVIDE STEEL FRAMING MEMBERS TO TRANSFER LOAD FROM SUPPORT POINTS AT FIRE SPRINKLER SYSTEM IS PROVIDED,REVIEW THE ELECTRICAL DRAWINGS TO DETERMINE EXTENT OF MANUFACTURER AND MODEL NUMBERS AS INDICATED;HOWEVER,CONTRACTOR SHALL VERIFY MODEL <br /> HANGERS TO LOCATIONS WHERE CONNECTIONS CAN BE MADE TO THE BUILDING STRUCTURE. FRAMING ADDITIONAL POWER AND ALARM SERVICES REQUIRED,AND PAY ELECTRICAL COSTS ASSOCIATED WITH NUMBERS OF FIXTURES,AMFLUSH VALVES,FAUCETS,ETC.,FIT ER,CONTRACTOR <br /> ETHER PROPERLY. ALTERNATE "E�Kea eY ON <br /> MEMBERS SHALL BE 12-GAUGE MINIMUM, 1-3/8"X 1-5/8"MINIMUM CROSS-SECTION SIZE;UNISTRUT, THESE SERVICES. <br /> POWERSTRUT,OR OTHER APPROVED. SELECT MEMBER SIZE AND TYPE,AS APPROPRIATE FOR LOAD PER MANUFACTURERS WILL BE CONSIDERED;HOWEVER,A/E FINAL APPROVAL OF EQUALITY OF ALTERNATE <br /> MANUFACTURER GUIDELINES. 3. AUTHORITIES: COMPLY WITH ALL REQUIREMENTS OF THE AUTHORITIES,WHICH SHALL INCLUDE THE MANUFACTURER MODELS IS REQUIRED. ACCEPTABLE ALTERNATE FIXTURE MANUFACTURERS INCLUDE <br /> STATE FIRE MARSHAL,LOCAL BUILDING AND FIRE DEPARTMENTS,AND OWNER'S INSURANCE KOHLER,AMERICAN STANDARD,EWER,ELKAY,JUST,OR AS INDICATED OR PRIOR APPROVED <br /> 5. PIPE HANGERS: CLEVIS OR RING HANGERS WITH STEEL RODS. HANGERS FOR INSULATED PIPING SHALL ORGANIZATION. OTHERWISE. ALTERNATE MANUFACTURERS WITH PRIOR APPROVAL ARE STILL RESPONSIBLE FOR PERMIT SET <br /> BE SIZED FOR OUTSIDE INSULATION AND 6"SHIELDS SHALL BE PROVIDED AT ALL HANGERS TO PROTECT MEETING OR EXCEEDING THE QUALITY AND FEATURES OF THE SPECIFIED ITEMS. <br /> INSULATION. PIPE SUPPORT SPACING PER IMC. PROVIDE PLASTIC SEPARATION BETWEEN CLAMPS AND 4. LICENSE THE FIRE SPRINKLER CONTRACTOR SHALL BE STATE-LICENSED AND REGULARLY ENGAGED IN 08/22/24 <br /> COPPER PIPE. THE DESIGN AND INSTALLATION OF AUTOMATIC SPRINKLER SYSTEMS AND,WHERE APPLICABLE, <br /> UNDERGROUND FIRE MAINS. SHOP DRAWINGS SHALL BE STAMPED BY A STATE-LICENSED FIRE <br /> 6. HANGER RODS: HOT ROLLED STEEL ROD,ASTM A 36;SIZE TO"CODE FOR PRESSURE PIPING",ANSI B PROTECTION ENGINEER OR DESIGNER WITH A NICET LEVEL III CERTIFICATION. PLUMBING <br /> 31.1.WITH SAFETY FACTOR OF 5. MINIMUM ROD SIZE; 1"PIPE AND SMALLER(240 POUNDS)= 1/4" 5. DESIGN DRAWINGS: COORDINATE LOCATIONS OF SPRINKLER HEADS,VALVES,AND OTHER EXPOSED <br /> ROD, 1-1/4"TO 2"PIPE(TO 610 POUNDS)=3/8"ROD,2-1/2"TO 4"PIPE(TO 1,130 POUNDS)= SPECIFICATIONS <br /> ITEMS WITH ARCHITECT,THEN PREPARE COMPLETE DESIGN DRAWINGS AND SUBMIT TO THE AUTHORITIES <br /> 1/2"ROD,5'TO 8'PIPE(TO 1,810 POUNDS)=5/8"ROD. FOR APPROVAL ALSO SUBMIT AUTHORITY-APPROVED DRAWINGS TO THE A/E FOR REVIEW PRIOR TO <br /> 7. INSTALL HIGH DENSITY PRE-MOLDED PIPE INSULATION 180 DEGREES(HALF-SHELLS)ON BOTTOM HALF OF START OF WORK. <br /> PIPE AT SUPPORTS FOR PIPING GREATER THAN 1"IN DIAMETER,6"LONG FOR PIPING 6"IN SIZE OR 6. COORDINATION WITH OTHER TRADES: DURING PREPARATION OF SHOP DRAWINGS,CALL TO THE <br /> SMALLER. FOR COLD PIPE SUPPORTS USE 3.0 PCF DENSITY POLYISOCYANURATE INSULATION. HOT PIPE ATTENTION OF THE GENERAL CONTRACTOR ANY POINTS OF CONFLICT BETWEEN NEW OR EXISTING FIRE <br /> SUPPORTS SHALL BE HIGH DENSITY POLYISOCYANURATE FOR FLUIDS UP TO 300 F,OR CALCIUM SILICATE. SPRINKLER WORK AND THAT OF THE OTHER TRADES,SO THAT THE CONFLICT MAY BE PROPERLY <br /> INSULATION AT SUPPORTS SHALL HAVE SAME THICKNESS AS ADJACENT INSULATION. RESOLVED. WORK WHICH UNREASONABLY INTERFERES WITH THE WORK OF OTHER TRADES SHALL BE <br /> 8. VIBRATION ISOLATION: VIBRATION ISOLATORS FOR HANGING EQUIPMENT SHALL BE EQUAL TO MASON REMOVED AND RE-INSTALLED AT THIS SUBCONTRACTOR'S EXPENSE. IT SHALL BE UNDERSTOOD THAT NO EXTRAS TO THE CONTRACT WILL BE PERMITTED TO ACCOMPLISH THE ABOVE RESULTS. P O.//�L <br />