Laserfiche WebLink
FACP Battery Load & Back-up Calculation <br />Fire Alarm Control Panel <br />Control Panel: <br />Location'. <br />FACP Type'. <br />Line# Oty. <br />Fire Alarm Control Panel <br />Electrical Rom <br />NFW-50(FACP) <br />Part#. Descripton. <br />Each Each <br />Standby Narm <br />Total <br />Standby <br />Total <br />Alarm <br />1 1 <br />2 1 <br />3 1 <br />4 1 <br />5 3 <br />6 1 <br />7 1 <br />8 1 <br />9 4 <br />10 1 <br />11 0 <br />12 1 <br />NFW-50X <br />FCM-1 <br />NP-200 <br />NOT-BG12LX <br />NDM-Too <br />P2WL <br />P2WL <br />P2WL <br />SWL <br />SWL <br />SVVL <br />P2RK <br />FACP <br />CONTROL MODULE <br />SMOKE DETECTOR <br />P[ULL STATION <br />DUAL MONITOR MODULE <br />15CD HORN STROBE <br />75CD HORN STROBE <br />95CD HORN STROBE <br />15CD STROBE <br />75CD STROBE <br />110CD STROBE <br />OUTDOOR HORN STROBE <br />0.1410 0.4570 <br />0,1410 <br />0.4570 <br />0.0DD4 0.0000 <br />0,0004 <br />0,0000 <br />0.0DD3 0,0000 <br />0.0003 <br />0,0000 <br />0.OD03 0.0000 <br />0.0003 <br />0.0000 <br />0.0DD8 0,0000 <br />0.0024 <br />0,0000 <br />0.ODD0 0.0830 <br />0,0000 <br />0.0830 <br />0.ODD0 0.1560 <br />0,0000 <br />0,1560 <br />0.0DD0 0.1770 <br />0.0000 <br />0.1770 <br />0.0DD0 0.0600 <br />0.0000 <br />0,2400 <br />0.0DD0 0.1360 <br />0.0000 <br />0,1360 <br />0.0000 0.1790 <br />0.0000 <br />0.0000 <br />0.ODD0 0.1680 <br />0,0000 <br />0,1680 <br />13 1 <br />PDC1024 <br />10"BELL <br />0.0DD0 0.0200 <br />0.0000 <br />0.0200 <br />14 1 <br />N-ANN-80 <br />REMOTE ANNUNCIATOR <br />0.0370 0.0400 <br />0.0370 <br />0.0400 <br />0,0000 <br />0,0000 <br />SOUTH FORK BAKERY T.I. <br />0.0000 <br />0.0000 <br />1 <br />1 <br />P2WL <br />15CD HORN STROBE <br />0.0000 0,0830 <br />0.0000 <br />0,0830 <br />2 <br />2 <br />P2WL <br />75CD HORN STROBE <br />0.0DD0 0,1560 <br />0.0000 <br />0,3120 <br />3 <br />1 <br />SWL <br />"CD STROBE <br />0.0DD0 0.0600 <br />0.0000 <br />0,0600 <br />4 <br />1 <br />SWL <br />75CD STROBE <br />0.0DDD 0,1360 <br />0.0000 <br />0,1360 <br />0.0000 <br />0,0000 <br />0.0000 <br />0.0000 <br />Total Current Drawl <br />0.1814 <br />2.0680 <br />BATTERY LOAD CALC for Fire Alarm Control PaneIFACP max P.S. Re1ng: 2.700 <br />Hours Standby 24 TotalStandby Current 0.1814 <br />Mines Alarm 5 Total Alarm Currentl 2.0680 <br />Backup Generator? No <br />Voice Evacucalon7 No Spare Circuit Capacity: 20% <br />Miliery7 No Spare Salary Load Factor: 20% <br />MAXIMUM CHARGER CAPACITY IS: 18AM <br />Total Arms Required: 2.068 % Used: <br />Total Amp Hours Required(AH): <br />Total Airy Minutes Required (AH):I <br />Minimun Baltary Size Needed (Al ): <br />Spare Beltary Capa6, Required: <br />Actoal Balery Size Required (AH): <br />Existing Be Supplied:= <br />77% <br />4.4 <br />0.2 <br />4.5 <br />0.9 <br />5.4 <br />18.0 <br />NOTE: SHADED DEVICES ARE EXISTING SHELL & CORE DEVICES. <br />SOUTH FORK BAKERY TENANT IMPROVEMENT <br />PORT OF EVERETT WPC - FISHERMAN'S HARBOR <br />COMMERCIAL DEVELOPMENT - PARCEL A8 <br />FIRE ALARM SYSTEM TENANT IMPROVEMENT <br />NAC Circuit Load, Voltage Drop Calculations <br />FACP <br />APB Nam: FACP <br />Sandby: Alarm <br />Circuit ldenitars: <br />Ouput#1 Oulcut#2 <br />NAC Sync NAC Sync <br />N1 N2 <br />Auz <br />Power <br />Total City <br />Loodw ELECTRICAL ROOM <br />P.S. Typo: NfW50 (FACP) <br />0.1410 0.4570 <br />Pert#: D ' ton: <br />P2WL Wall Horn wl Strobe setat 15od <br />0.0000 0.0830 <br />2 <br />r 2 <br />P2WL Wal Hom wl Strobe setat75od <br />0.0000 0.1560 <br />3 <br />3 <br />P2WL Wall Horn wl Strobe setat95od <br />0.0000 0.1770 <br />1 <br />1 <br />SWL Well Strobe setatl5.d <br />0.0000 0.0600 <br />5 <br />5 <br />SWL Wall Slob! as 2175cd <br />0.0000 0.1360 <br />2 <br />2 <br />SW� Well Slob. aetat 110cd <br />0.0000 0.1790 <br />0 <br />0 <br />P2RK Well Hornwl Strobe setat75od,WP <br />0.0000 0.1680 <br />1 <br />1 <br /># Devices per Circuit <br />Total Standby Circuit Calculated Amps (3): <br />Total Alarm Circuit Calculated Amps (1): <br />Wire Gauge Used (awg): <br />Circuit Lengti (I1): <br />Estaeted Voltage Drop (do): <br />Eslmaed EOL Voltage (do): <br />Calculated Voltage Drop %: <br />13 <br />1 <br />0 <br />0 <br />0 <br />14 <br />0.000 <br />(Low <br />0.000 <br />0.000 <br />0.0000 <br />0.1410 <br />1.383 <br />0.168 <br />0.000 <br />0.000 <br />0.0000 <br />0.4570 <br />16AWG <br />16ANG <br />16AWG <br />16AWG <br />14AWG <br />Total <br />Ape <br />Required <br />1.551 <br />390 <br />50 <br />4.42 <br />0,07 <br />0.00 <br />0,00 <br />770,00 <br />19.58 <br />23.93 <br />24.00 <br />24.00 <br />24.00 <br />18.4% <br />0.3% <br />0.0% <br />00% <br />0.0% <br />1) Current Draw Measurement based on: UL1971, 16-33V, DC, High db & Temporal Paten <br />2) Some OutloorNrP Devices have tie same Measured Current Draw as the Indoor Devices and may not Iced separately above. <br />