Laserfiche WebLink
Vital Mechanical Service <br /> 142,MdPl�Is <br /> Renton,Washington 9605 <br /> 206-629-4826 <br /> AIR OUTLET TEST REPORT <br /> PROJECT. South fork Baking DATE: 12/1/23 <br /> LOCATION" Everret WA CONTACT.Josh Stenehjem <br /> WO Number. <br /> SYSTEM/UNIT: RTU-2 <br /> AREA: KITCHEN <br /> Unit Data Air Test Data <br /> VA Type N/A K Factor <br /> VAV Address N/A Heat Works Yes <br /> Box Inlet Size N/A Des. Fan/Heat CFM NA CFM <br /> Act. Fan/Heat CFM NA CFM <br /> Design Primary Max CFM 1,600 CFM <br /> Test Data Actual Max Primary CFM NA CFM <br /> Design Primary Min. CFM NA CFM <br /> Fan Speed NA Actual Primary Min.CFM NA CFM <br /> AHU-3/FPVAV Supply Air Outlet Summary <br /> System/Unit AREA or ROOM OUTLET I DESIGN 1PRELIMINI /o I Final Read /e PERCENT <br /> Outlet# SERVED NO. TYPE SIZE I AIRFLOW JAIRFLOW OF I AIRFLOW OF OFF <br /> CFM(L/s) I CFM(L/s)I DESIGN CFM(L/s) DESIGN DESIGN <br /> RTU-2 KITCHEN 1 CD 14" 500 450 1 90% 1 520 104°/H 4% <br /> RTU-2 KITCHEN 2 CD 14" 500 1 620 124% 550 110°/H 10% <br /> RTU-2 KITCHEN 3 CD 14" 600 1 620 103% 620 103% 3% <br /> Total: <br /> Notes: <br /> Balancer: KELLY M. <br />