Laserfiche WebLink
Vital Mechanical Service <br /> 206-629-4828-v 1-11-1, <br /> ° <br /> AIR OUTLET TEST REPORT <br /> PROJECT: South fork Baking DATE: 12/1/23 <br /> LOCATION" Everret WA CONTACT.Josh Stenehjem <br /> WO Number: <br /> SYSTEM/UNIT: RTU-1 <br /> AREA: RETAIL/DINNING <br /> Unit Data Air Test Data <br /> VA Type N/A K Factor <br /> VAV Address N/A Heat Works Yes <br /> Box Inlet Size N/A Des.Fan/Heat CFM NA CFM <br /> Act.Fan/Heat CFM NA CFM <br /> Design Primary Max CFM 3,200 CFM <br /> Test Data Actual Max Primary CFM NA CFM <br /> Design Primary Min.CFM NA CFM <br /> Fan Speed NA Actual Primary Min.CFM NA CFM <br /> AHU-31FPVAV Supply Air Outlet Summary <br /> System/Unit AREA or ROOM OUTLET I DESIGN IPRELIMINI / Final Read I / PERCENT <br /> Outlet# SERVED NO. TYPE SIZE AIRFLOW AIRFLOW OF AIRFLOW OF OFF <br /> CFM(L/s) CFM(L/s) DESIGN CFM(L/s) DESIGN DESIGN <br /> RTU-1 RETAIL 1 S-2 16X6 350 1 345 99% 345 99% 1 -1% <br /> RTU-1 RETAIL 2 S-1 12X6 100 105 105% 105 105% 1 5% <br /> RTU-1 RETAIL 3 S-1 12X6 250 240 96% 240 96% -4% <br /> RTU-1 RETAIL 4 S-1 12X6 100 100 100% 100 100% 0% <br /> RTU-1 RETAIL 5 S-1 12X6 250 250 100% 250 100% 0% <br /> RTU-1 RETAIL 6 S-1 12X6 100 102 102% 102 102% 2% <br /> RTU-1 RETAIL 7 S-1 12X6 250 250 100% 250 100% 0% <br /> RTU-1 RETAIL 8 S-4 24X8 800 805 101% 805 101% 1% <br /> RTU-1 RETAIL 9 S-3 24X8 500 490 98% 490 98% -2% <br /> RTU-1 RETAIL 10 S-3 24X8 500 480 96% 480 96% -4% <br /> Total: <br /> Notes: <br /> Balancer: KELLY M. <br />