Laserfiche WebLink
The rating isn't significant in this case,the gasketing is. <br /> Thanks,Tony <br /> Tony Lee <br /> MIBuilding Official I Permit Services <br /> 425.257.8812 13200 Cedar Street, 2"d Floor, Everett,WA 98201 <br /> EVERETT everettwa.gov/permits I Facebook I Twitter <br /> From: MacKenzie, Katie<kmackenzie@glumac.com> <br /> Sent:Thursday,July 7, 2022 10:27 AM <br /> To:Tony Lee<TLee@everettwa.gov> <br /> Subject: [EXTERNAL] Building A-Generator Exhaust <br /> CAUTION:This email originated from outside of the organization. Do not click links or open attachments unless you <br /> recognize the sender and know the content is safe. <br /> Hi Tony, <br /> I hope this message finds you well.We have a question regarding the project Everett Riverfront Building A(B2003-013), <br /> vested under 2015 building code.The project team is having difficulty locating the building's generator exhaust outlet in <br /> such a way that is completely compliant with the code/NFPA. <br /> In IMC 2015 with WA state amendments,section 501.3.1,ducts conveying explosive or flammable vapors,fumes or <br /> dusts shall remain "30 feet(9144 mm)from the property line;10 feet(3048 mm)from operable openings into the <br /> building; 6 feet(1829 mm)from exterior walls and roofs;30 feet(9144 mm)from combustible walls and operable <br /> openings into the building which are in the direction of the exhaust discharge;10 feet(3048 mm) above adjoining <br /> grade.". Please see attached diagrammatic detail that outlines all NFPA requirements for generators when located <br /> within a building. <br /> Our proposed engine exhaust outlet is compliant of the above criteria,with the exception of one double door located <br /> south-east of the outlet.See below for a visual description of the situation below(color coded for showing proposed <br /> relocation of systems).The double door in question is outlined in purple.The red circle defines the engine exhaust's 10 <br /> foot clearance requirement for operable openings into the building.This double-door is normally closed,and leads to a <br /> back-of-house electrical room.The windows within the 10 foot clearance are non-operable.We have looked at all other <br /> options and have concluded that this is the optimal location of the generator exhaust outlet. Given this information,are <br /> we able to get a code exemption for this double door? <br /> 64---/—;?) <br />