FLEXHEAD Flexible Sprinkler Connections <br /> Z ANVIL <br /> MPT24BKT1 Multi-Position Tall Bracket (MPT) <br /> Installation of FlexHead Commercial Ceiling Flexible Sprinkler Drop System <br /> Recommend the use of proper PPE for installation. MPT-24- approved for limited flexibility and are <g> UL <br /> BKT1 is approved for use with the standard FlexHead°and intended for direct sprinkler connection. ApPRM ° <br /> SuperFlexTm Flexible Sprinkler Hose in accordance to NFPA The MPT bracket is set for 24"center of tile installation. (See <br /> 13, 13D, & 13R for use in wet and dry sprinkler system.The back side for additional installation configurations) <br /> Standard&SuperFlexTm Flexible sprinkler hoses are UL <br /> FlexHead® 0000 <br /> FlexHead® <br /> Standard Tall Standard Tall Elbow SuperFlex'" <br /> 2024T,2036T,2048T,2060T,2072T 2024ET,2036ET,2048ET,2060ET,2072ET 2036SF,2048SF,2072SF <br /> 1 T Bar Ceiling Grid Installation FlexHead Flexible Hose Installation <br /> The MPT bracket is designed for use on ceiling grids 2A. For threaded fitting branch connection:Apply Teflon° <br /> conforming to ASTM C 635`. tape or pipe sealant to the 1" NPT thread. Install into branch <br /> Locate the center of the ceiling tile marking, align the offset outlet.Tigthen the hose using the pipe section, never apply a <br /> screw with that marking for true center of tile installation.Insert wrench to the braided hose when installing. <br /> one bracket leg at a time,applying a downward pressure on the B. For groove connection follow the grooved coupling manufac- <br /> bracket leg and T-Bar. Screw the self tapping screw using a turer's installation instructions. <br /> #2 square head driver. Place the second leg on the T-Bar and C. For SLT connection follow GruvloV installation instructions, <br /> repeat process. (Fig. 1) "Fig 7074SLT SlideLOK®Ready for Installation Cap& Fitting <br /> Instructions". <br /> Fig.1 The FlexHead connection can be installed in any direction from <br /> the branch. Ensure the hose is allowed at least one bend per <br /> installation to allow for seismic movement. (See fiction Loss <br /> �y Chart on Page 3 for details) <br /> Fig.2 <br /> Do not wrench on braided hose <br /> 'Intended for use on ASTM C 635 intermediate or heavy duty ceilings systems installed in accordance to ASTM C 636. <br /> FP-8.18 <br />