<br /> ELECTRICAL SPECIFICATIONS:
<br /> PART 1 -GENERAL 2.3 RACEWAY AND BOXES CONNECTIONS TO VIBRATING OR ROTATING EQUIPMENT. t g b architect s
<br /> x 1.1 GENERAL CONDITIONS A. RIGID STEEL CONDUIT,ZINC COATED;ANSI C80.1:ALL FITTINGS SHALL BE SCREW D. ALL RIGID STEEL CONDUIT INSTALLED IN CONTACT WITH EARTH SHALL BE PVC
<br /> THREAD TYPE,COUPLINGS,LOCKNUTS, BUSHINGS,ETC.SHALL BE HOT DIPPED COATED OR OTHERWISE PROTECTED WITH A BITUMASTIC MATERIAL
<br /> A. THE WORK UNDER THIS DIVISION INCLUDES FURNISHING ALL PERMITS,MATERIALS, GALVANIZED.
<br /> EQUIPMENT, LABOR,SUPERVISION,TOOLS,EXPENSES,TRAVEL,AND ITEMS NECESSARY E. MINIMUM SIZE OF CONDUIT SHALL BE CODE SIZE FOR THE NUMBER AND SIZE OF
<br /> FOR THE CONSTRUCTION,INSTALLATION,CONNECTION,TESTING AND OPERATION OF ALL B. ELECTRICAL METALLIC TUBING,ZINC COATED:ANSI C80.3:COUPLINGS AND CONDUCTORS UNLESS A LARGER SIZE IS INDICATED ON THE PLANS. t 425.778.1530 21911 76th Ave W.Ste 210
<br /> ELECTRICAL WORK FOR THIS PROJECT,AS INTENDED BY THE CONTRACT DOCUMENTS. CONNECTORS SHALL BE STEEL GALVANIZED,COMPRESSION TYPE WITH GLAND SEALING f barchitecls.com 425.774.7803 Edmonds WA 98026
<br /> t
<br /> B. THE GENERAL CONDITIONS,SUPPLEMENTARY CONDITIONSRINGS.ONS AND SPECIAL CONDITIONS F. WHERE PENETRATIONS ARE MADE THROUGH PARTITIONS,PROVIDE SEALING MATERIAL info @ 9
<br /> ARE A PART OF THIS CONTRACT AND APPLY TO THIS SECTION AS FULLY AS IF REPEATED C. FLEXIBLE METAL CONDUIT: UL 1:FLEXIBLE METAL CONDUIT SHALL BE GALVANIZED TO MAINTAIN THE FIRE RATING OF THE PARTITION.FOR EXTERIOR WALLS PROVIDE www.tgbarchitects.com
<br /> HEREIN. STEEL OR ALUMINUM.WHERE EXPOSED TO DAMP OR WET LOCATIONS FLEXIBLE CONDUIT SLEEVES AND SEALING TO PREVENT WATER AND MOISTURE PENETRATION AND TO
<br /> SHALL BE LIQUID-TIGHT WITH OUTER SUITABLE LIQUID-TIGHT FITTINGS LISTED FOR THE PREVENT VARMINT AND INSECT INTRUSION.
<br /> 1.2 CODES AND REGULATIONS PURPOSE.
<br /> 3.3 INSTALLATION OF CONDUCTORS AND EQUIPMENT CONNECTIONS
<br /> A. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH APPLICABLE D. OUTLET AND JUNCTION BOXES:OUTLET AND JUNCTION BOXES SHALL BE
<br /> REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION AND THE UTILITY FURNISHING GALVANIZED,ONE-PIECE PRESSED OR WELDED STEEL,KNOCKOUT TYPE EXCEPT AS A ALL WIRING SHALL BE INSTALLED IN CONDUIT,WIREWAYS,OR GUTTERS EXCEPT
<br /> SERVICES FOR THE SPECIFIC FACILITY LOCATION. OTHERWISE NOTED OR SPECIFIED. WHERE OTHER RACEWAY SYSTEMS ARE SPECIFICALLY CALLED FOR.
<br /> B. CODES GOVERNING THIS WORK INCLUDE BUT ARE NOT LIMBED TO THE LATEST E. PROVIDE FIRE-STOPPING WHERE CONDUIT PASSES THROUGH A RATED ASSEMBLY.
<br /> ADOPTED EDITION OF THE FOLLOWING: B. INSTALL WIRING ONLY AFTER RACEWAY INSTALLATION HAS BEEN COMPLETED
<br /> NFPA 70(NATIONAL FIRE PROTECTION ASSOCIATION)NATIONAL ELECTRICAL CODE 2.4 WIRING DEVICES(PROVIDE DEVICES PER DRAWINGS) CLEANED AND DRIED. EVIDENCE
<br /> (NEC)AS AMMENDED BY WASHINGTON CRIES(2020 WCEC) BDI BASED
<br /> NFPA 72(NATIONAL FIRE PROTECTION ASSOCIATION)NATIONAL FIRE ALARM AND A. RECEPTACLES: C. PULLING LUBRICANTS APPROVED BY THE WIRE OR CABLE MANUFACTURE MAY BE DESIGN
<br /> SIGNALING CODE 1. PROVIDE 20 AMP RECEPTACLES IN ALL CONVENIENCE AND DEDICATED LOCATIONS. UTILIZED.
<br /> NFPA 101 (NATIONAL FIRE PROTECTION ASSOCIATION) LIFE SAFETY CODE PLUG TAIL ACCEPTABLE. SERVICES
<br /> ki
<br /> .....,,.,.,,..,..o.
<br /> CITY OF RENTON ORDINANCES AND REGULATIONS 2. RECEPTACLES COVERS TO BE STAINLESS STEEL TYPE OR AS APPROVED BY D. MAKE ALL CONNECTIONS AND SPLICES REQUIRED FOR COMPLETE AND OPERABLE
<br /> WSEC-2018 COMMERCIAL OWNER. ELECTRICAL INSTALLATION.CONNECTIONS AND SPLICES SHALL BE MADE ONLY IN
<br /> 3. GROUND PIN/NEUTRAL LOCATION TO BE CONSISTENT WITH FACILITY IN ALL JUNCTION, PULL OR OUTLET BOXES OR IN WIREWAYS,SWITCHBOARDS AND PANELBOARDS
<br /> 1.3 STANDARDS RENOVATION OR EXPANSION PROJECTS,AND FOR NEW PROJECTS SHALL BE GROUND PIN HAVING CODE SIZED GUTTER SPACE OR CROSS-SECTIONAL AREA. WIRES/8 AND
<br /> DOWN. SMALLER CONNECTIONS SHALL BE MADE WITH SPRING TYPE CONNECTORS;WIRES#6 AND
<br /> A. ELECTRICAL MATERIAL AND EQUIPMENT SHALL BE UNDERWRITERS LABORATORIES 4. HEAVY DUTY SPECIFICATION GRADE. LARGER,CONNECTIONS SHALL BE MADE WITH SPLIT-BOLT OR COMPRESSION TYPE
<br /> LISTED AND INSTALLED IN ACCORDANCE WITH THE LISTING AND LABELING OF THE 5. TAMPER PROOF IN PUBLIC AREAS. SOLDERLESS CONNECTORS,INSULATED AND TAPED.
<br /> EQUIPMENT. B. SWITCH COVER PLATES TO BE STAINLESS STEEL TYPE OR AS APPROVED BY
<br /> OWNER. E. UPON COMPLETION OF WORK, UPDATED ALL PANEL DIRECTORIES WITH CORRECT
<br /> B. INSTALLATION SHALL CONFORM TO THE NECA(NATIONAL ELECTRICAL CONTRACTORS CIRCUIT INFORMATION. PROVIDE PRINTED CIRCUIT DIRECTORIES IN PANELS AFFECTED BY
<br /> ASSOCIATION)STANDARD OF INSTALLATION. C. CIRCUITING: THE PROJECT. PEN AND INK CHANGES TO THE EXISTING DIRECTORIES ARE NOT M.
<br /> 1. CONVENIENCE DUPLEX RECEPTACLES-MAXIMUM OF SIX PER 20A CIRCUIT. ACCEPTABLE. b�F W IJ
<br /> 1.4 SUBMITTALS o
<br /> 2. HOMERUN CONDUIT-MAXIMUM 4 CIRCUITS. ��� r'�'A✓
<br /> A. ELECTRONIC COPIES, IN.PDF FORMAT,OF MATERIALS LIST,SHOP DRAWINGS AND 3. POWER AND LIGHTING SHALL NOT BE ON THE SAME CIRCUITS(EXCEPT 3.4 GROUNDING
<br /> DATA SHEETS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW.SUBMITTALS SHALL UNDER-CABINET LIGHTING).
<br /> BE MADE,AND FAVORABLE REVIEW SECURED BEFORE MATERIAL AND EQUIPMENT IS 4. 480/277V BRANCH CIRCUIT WIRING SHALL BE IN SEPARATE CONDUITS FROM A PERMANENTLY AND EFFECTIVELY GROUND ALL CONDUIT,BOXES,ENCLOSURES AND
<br /> INSTALLED. 208/120V CIRCUIT WIRING. EQUIPMENT TO COMPLY WITH NEC 250 AND ALL APPLICABLE CODES AND REGULATIONS. 51724
<br /> B. MATERIALS LIST SHALL INCLUDE: DEVICES, DISCONNECTS, LIGHT FIXTURES,LIGHTING 2.5 FUSIBLE SWITCHES B. PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR IN ALL RACEWAYS ZON3AIL'�s� '�
<br /> CONTROL DEVICES AND OTHER ITEMS SPECIFIED OR CALLED FOR ON THE DRAWING.THE SIZED IN ACCORDANCE WITH NEC TABLE 250.122 WHETHER SPECIFICALLY CALLED FOR 0710812024
<br /> LIST SHALL INCLUDE MANUFACTURE,TYPE AND SUCH OTHER DESCRIPTIVE DATA AS MAY A. TYPE GD,GENERAL DUTY,SINGLE THROW, 100 A AND SMALLER: UL 98 AND ON THE PLANS OR NOT.
<br /> BE REQUIRED TO DETERMINE THE ACCEPTABILITY OF EACH ITEM. NEMA KS 1,HORSEPOWER RATED,WITH CARTRIDGE FUSE INTERIORS,LOCKABLE HANDLE
<br /> WITH CAPABILITY TO ACCEPT TWO PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED 3.5 PROTECTION OF PREMISES
<br /> C. SHOP DRAWINGS AND DATA SHEETS FOR EQUIPMENT AND SYSTEMS SHALL BE POSITION.
<br /> SUBMITTED WHERE REQUIRED IN THE SPECIFICATIONS FOR THOSE ITEMS.INCLUDE A. CONTRACTOR SHALL CLEW WORK AREA AND REMOVE ALL CONSTRUCTION DEBRIS
<br /> INFORMATION ON EACH COMPONENT,WIRING DIAGRAMS,LAYOUTS,DIMENSIONS AND B. TYPE HD,HEAVY DUTY,SINGLE THROW, LARGER THAN 100 AMP: UL 98 AND
<br /> SUFFICIENT OTHER DATA TO ESTABLISH COMPLIANCE WITH THE SPECIFICATIONS AND NEMA KS 1,HORSEPOWER RATED,WITH CLIPS OR BOLT PADS TO ACCOMMODATE FUSES, DAILY PRIOR TO LEAVING THE PREMISES.
<br /> ACCEPTABILITY OF THE EQUIPMENT OR SYSTEM. LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT THREE PADLOCKS,AND INTERLOCKED
<br /> WITH COVER IN CLOSED POSITION. B. THE CONTRACTOR SHALL PROTECT ALL EXISTING SURFACES, MATERIALS,EQUIPMENT
<br /> D. SHOP DRAWINGS SHALL BE SUBMITTED IN EITHER HALF OR FULL SIZE AS AND PROPERTY FROM DAMAGE AS RESULT OF CONSTRUCTION ACTIVITIES. DAMAGED
<br /> FOLLOWS: C. ACCESSORIES: SURFACES,MATERIALS,EQUIPMENT AND PROPERTY SHALL BE REPAIRED TO EXISTING
<br /> 1. CLASS R FUSE KIT: PROVIDES REJECTION OF OTHER FUSE TYPES WHEN CLASS R CONDITIONS AT NO COST TO THE OWNER.
<br /> 1. HALF SIZE SHALL BE 15 INCHES BY 21 INCHES MINIMUM. MINIMUM HALF SIZE FUSES ARE SPECIFIED.
<br /> FONT HEGHT SHALL BE 1/16 INCH. WIDTH SHALL BE PROPORTIONAL NO LESS THAN 2.6 NONFUSIBLE SWITCHES 3.6 TESTING OF ELECTRICAL SYSTEMS
<br /> 70 PERCENT OF THE HEIGHT.
<br /> 2. FULL SIZE SHALL BE 30 INCHES BY 42 INCHES MINIMUM. MINIMUM FULL-SIZE A. TYPE GD,GENERAL DUTY,SINGLE THROW, 100 A AND SMALLER: UL 98 AND
<br /> PERCENT OF A EQUIPMENT INSTALLED OR MODIFIED UNDER THIS SECTION SHALL BE INSPECTED
<br /> FONT PERCENT
<br /> OF THE HEIGHT.SHALL 1/8 INCH. WIDTH SHALL BE PROPORTIONAL NO LESS THAN 70 NEMA KS 1,HORSEPOWER RATED,LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT TWO AND TESTED FOR PROPER OPERATION IN ACCORDANCE WITH APPLICABLE NETA
<br /> PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED POSITION. ACCEPTANCE TESTING STANDARDS.
<br /> E. PROVIDE PRODUCT DATA AND SHOP DRAWINGS FOR THE FOLLOWING: B. TYPE HD,HEAVY DUTY,SINGLE THROW, LARGER THAN 100 AMP. UL 98 AND B. SYSTEMS SHALL BE TESTED FOR SHORT CIRCUITS,OPEN CIRCUITS,PHASE
<br /> 1. WIRING DEVICES NEMA KS 1,HORSEPOWER RATED,LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT THREE ROTATION AND SHALL BE FREE FROM MECHANICAL AND ELECTRICAL DEFECTS.
<br /> 2. DISCONNECTS PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED POSITION.
<br /> 1.5 SUBSTITUTIONS C. THE CONTRACTOR SHALL CORRECT DEFICIENCIES AND PROVIDE RETESTING AT NO
<br /> C. TYPE HD,HEAVY DUTY,DOUBLE THROW, 1200 A AND SMALLER: UL 98 AND EXPENSE TO THE OWNER AND ENGINEER UNTIL THE EQUIPMENT AND SYSTEM IS PROVIDENCE
<br /> A. NO SUBSTITUTIONS ARE ALLOWED.ALTERNATIVE MANUFACTURERS WILL BE NEMA KS 1,HORSEPOWER RATED,LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT THREE SATISFACTORY TO THE OWNER AND THE ENGINEER.
<br /> CONSIDERED FOR ELECTRICAL EQUIPMENT SPECIFIED AND SHOWN HEREIN.THE SPECIFIED PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED POSITION.
<br /> MANUFACTURERS EQUIPMENT SETS THE LEVEL OF QUALITY FOR THE WORK. 2.7 ENCLOSURES GENERAL NOTES: CT SIMULATOR
<br /> WORK AND EQUIPMENT NOT MEETING THE LEVEL OF QUALITY SHALL BE REJECTED. THE A. ENCLOSED SWITCHES AND CIRCUIT BREAKERS: NEMA AB 1,NEMA KS 1,NEMA 1. COMPLY WITH NEC AS ADOPTED AND AMENDED BY LOCAL AHJ.
<br /> ENGINEER HAS DISCRETION TO ACCEPT OR REJECT THE ALTERNATIVE MANUFACTURER'S 250,AND UL 50,TO COMPLY WITH ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION.
<br /> EQUIPMENT. 1. INDOOR,DRY AND CLEAN LOCATIONS: NEMA 250,TYPE 1. 2. ALL EXISTING WORK IS BASED ON RECORD DRAWINGS AND HAS NOT BEEN FIELD
<br /> 1.6 PERMITS AND DRAWINGS 2. OUTDOOR LOCATIONS: NEMA 250,TYPE 3R. VERIFIED IN FULL.THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
<br /> 3. WASH-DOWN AREAS: NEMA 250,TYPE 4X,STAINLESS STEEL. INFORMATION RELEVANT FOR THE SCOPE OF THIS PROJECT.
<br /> A. PERMITS AND INSPECTIONS SHALL BE OBTAINED,COORDINATED AND PAID FOR BY 4. OTHER WET OR DAMP, INDOOR LOCATIONS: NEMA 250,TYPE 4.
<br /> THE ELECTRICAL CONTRACTOR. 5. INDOOR LOCATIONS SUBJECT TO DUST,FALLING DIRT,AND DRIPPING 3. ALL SCOPE NOT IDENTIFIED FOR DEMOLITION OR MODIFICATIONS IS EXISTING TO 1717 13th St
<br /> NONCORROSIVE LIQUIDS: NEMA 250,TYPE 12. REMAIN.REFER TO MECHANICAL DRAWINGS FOR DEMOLITION SCOPE OF WORK. Everett,WA 98201
<br /> B. THE CONTRACTOR SHALL PAY ALL FEES AND TAXES FOR THE TOTAL COST OF
<br /> CONSTRUCTION,INCLUDING CONTRACTOR AND OWNER FURNISHED MATERIALS AND 2.8 GROUNDING 4. ALL WORK SHALL BE DONE WITH MAXIMUM CARE EXERCISED DURING DEMOLITION
<br /> EQUIPMENT AS SHOWN AND SPECIFIED. AND MODIFICATIONS PROCESS.ANY ACCIDENTAL OR INTENTIONAL DAMAGE TO EQUIPMENT
<br /> C. THE CONTRACTOR SHALL OBTAIN AND PAY THE PLAN REVIEW FEE. A. PROVIDE COPPER GROUNDING. TO REMAIN SHALL BE REPAIRED AT NO ADDITIONAL COST TO THE OWNER. CONSTRUCTION
<br /> D. THE CONTRACTOR SHALL PAY FOR PLAN REVIEW 5. UNLESS OTHERWISE REQUESTED BY THE OWNER ALL REMOVED ELECTRICAL EQUIPMENT,DEVICES,AND MATER DOCUMENTS
<br /> REVIEW FEES AND RE-INSPECTIONS B. PROVIDE DEDICATED NEUTRAL(NO SHARED NEUTRALS)WITH ALL BRANCH CIRCUITS W-S SHALL BE DISPOSED OF BY THE ELECTRICAL
<br /> RESULTING FROM SUBSTITUTIONS. FEES DUE TO SUBSTITUTIONS SHALL BE AT NO COST IN EACH CONDUIT.USE OF MULTI-POLE BREAKERS OR BREAKER TIES IN LIEU OF CONTRACTOR.
<br /> TO THE OWNER. DEDICATED NEUTRALS IS NOT PERMITTED.
<br /> E. THE CONTRACTOR SHALL INCLUDE APPLICABLE PLAN REVIEW FEES AND 6. ALL WORK SHALL BE DONE ON DE-ENERGIZED EQUIPMENT ONLY AND ALL LOTO
<br /> RE-INSPECTION FEES IN CHANGE ORDER PROPOSALS. C. ALL CONDUITS WILL BE PROPERLY BONDED WITH INSULATED GROUND WIRE RUN (LOCK-OUT TAG OUT)PROCEDURES SHALL BE FOLLOWED AS REQUIRED PER NEC AND
<br /> WITH CONDUCTORS. OSHA.
<br /> 1.7 RECORD DRAWINGS
<br /> D. ALL PANELS AND TRANSFORMERS MUST HAVE A DEDICATED EQUIPMENT GROUNDING
<br /> A. ON A SET OF CONTRACT DRAWINGS KEPT AT THE SITE DURING CONSTRUCTION, CONDUCTOR IN ADDITION TO ELECTRODE OR BUILDING GROUNDS AS REQUIRED PER
<br /> MARK ALL WORK THAT IS INSTALLED DIFFERENTLY FROM THAT SHOWN,INCLUDE ANY CODE.
<br /> REVISED CIRCUITRY,MATERIAL OR EQUIPMENT. UPON CONCLUSION OF THE WORK,
<br /> DELIVER TO THE OWNER REPRESENTATIVE A SET OF SIGNED AND DATED"AS-BUILT' 2.9 CIRCUIT BREAKERS DRAWINGS. ELECTRICAL
<br /> 1.8 WARRANTY A. CIRCUIT BREAKERS SHALL BE THE SAME MANUFACTURER AS THE PANELBOARD OR
<br /> SWITCHBOARD IN WHICH THEY ARE INSTALLED. SPECIFICATIONS
<br /> A. ALL WORK SHALL INCLUDE A WARRANTY FOR A MINIMUM PERIOD OF ONE YEAR
<br /> FROM THE DATE OF ACCEPTANCE BY THE OWNER.THE WARRANTY PERIOD FOR CERTAIN B. CIRCUIT BREAKERS SHALL BE MOLDED-CASE BOLT-ON TYPE. PLUG-IN TYPES ARE
<br /> ITEMS SHALL BE LONGER,AS INDICATED IN THE SPECIFICATIONS FOR THOSE ITEMS. NOT ACCEPTABLE.MULTI-POLE BREAKERS SHALL HAVE INTERNAL TRIP AND SINGLE ISSUANCE
<br /> HANDLE OPERATION. No. Description Date
<br /> B. SHOULD ANY MALFUNCTION DEVELOP DURING THE WARRANTY TIME PERIOD DUE TO PERMIT SET 07/0812024
<br /> DEFECTIVE MATERIAL,FAULTY WORKMANSHIP,OR NON-COMPLIANCE WITH PLANS, C. PROVIDE ALL NECESSARY MOUNTING HARDWARE,ACCESSORIES AND CLOSURE
<br /> SPECIFICATIONS,CODE OR DIRECTIONS OF THE OWNER OR OWNER'S REPRESENTATIVE, DEVICES AS NECESSARY.
<br /> THE CONTRACTOR SHALL FURNISH ALL NECESSARY LABOR AND MATERIALS TO CORRECT
<br /> THE MALFUNCTION AT NO ADDITIONAL COST TO THE OWNER. D. SHORT CIRCUIT INTERRUPTING CAPACITY SHALL BE AS INDICATED ON PLANS OR TO
<br /> MATCH RATING OF THE EXISTING PANELBOARD INTO WHICH THE CIRCUIT BREAKER IS TO
<br /> PART 2- PRODUCTS BE INSTALLED.
<br /> 2.1 MATERIAL 2.10 EQUIPMENT IDENTIFICATION
<br /> A. MATERIALS SHALL BE NEW, FREE OF DEFECTS AND OF CURRENT MANUFACTURE.
<br /> EXISTING MATERIALS SHALL NOT BE REUSED UNLESS SPECIFICALLY NOTED OTHERWISE. A. ENCLOSED CIRCUIT BREAKERS,DISCONNECT SWITCHES,RECEPTACLES AND LIGHT
<br /> SWITCHES: PRINTED LABEL WITH(PANEL)NAME AND CIRCUIT NUMBER. (EXAMPLE:
<br /> 2.2 WIRE AND CABLE(600 VOLT AND LESS) "PP4-23"FOR PANEL PP4,CIRCUIT 23)
<br /> NORMAL POWER:9"BLACK LETTERS
<br /> A. PRODUCTS SHALL COMPLY WITH UL 44 AND UL 83 SINGLE CONDUCTOR INSULATED
<br /> WIRE. PART 3-EXECUTION
<br /> B. WIRE AND CABLE FOR USE ON SYSTEMS OF 600 VOLTS AND LESS SHALL BE 600
<br /> VOLT WITH NEC TYPE THHN/rHWN OR XHHW INSULATION FOR BRANCH CIRCUITS AND 3.1 INSTALLATION OF ELECTRICAL EQUIPMENT
<br /> FEEDERS SMALLER THAN 12AWG.XHHW INSULATION SHALL BE USED FOR#2AWG AND
<br /> LARGER FEEDER CONDUCTORS. A. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS,NECA
<br /> 1. USE TYPE THHN/THWN CONDUCTORS FOR ALL BRANCH POWER AND LIGHTING STANDARD OF INSTALLATION AND IN ACCORDANCE WITH THE UL LISTING FOR THE
<br /> CIRCUITS. EQUIPMENT OR MATERIAL
<br /> 2. USE TYPE XHHW IN AMBIENT TEMPERATURES BELOW 327.USE TYPE XHHW-2 FOR ALL DISCONNECTS,FUSES,CIRCUIT BREAKERS SHALL BE PROVIDED AS INDICATED AND
<br /> ALL WIRING CONNECTED TO GFCI BREAKERS. FOR PROPER PROTECTION OF THE EQUIPMENT SERVED.PROVIDE ALL FLEXIBLE CONDUIT,
<br /> BOXES,PULL BOXES,FITTINGS,SEALS,AND OTHER MATERIALS REQUIRED FOR A
<br /> C. ALL GROUNDING CONDUCTORS SHALL BE INSULATED. COMPLETE AN OPERATIONAL SYSTEM.
<br /> THE WORK UNDER THIS DIVISION INCLUDES FURNISHING ALL PERMITS,MATERIALS,
<br /> D. MC OR HCF-MC CABLE SHALL BE PERMITTED FOR LIMITED USE AS FOLLOWS: EQUIPMENT,LABOR,SUPERVISION,TOOLS AND ITEMS NECESSARY FOR THE
<br /> CONSTRUCTION,INSTALLATION,CONNECTION,TESTING AND OPERATION OF ALL ELECTRICAL
<br /> 1. TEMPORARY POWER PROVISIONS WORK FOR THIS PROJECT,AS INTENDED BY THE CONTRACT DOCUMENTS.
<br /> 2. EQUIPMENT CONNECTIONS TO COMPENSATE FOR MOVEMENT AND VIBRATION.
<br /> 3. TERMINAL CONNECTIONS TO LIGHT FIXTURES NOT TO EXCEED 6 FEET IN LENGTH.
<br /> 4. LIGHTING AND BRANCH CIRCUITS.5. CONCEALED AREAS INDOORS. 3.2 INSTALLATION OF RACEWAY AND FITTINGS
<br /> PROJECT INFORMATION
<br /> A. INSTALL RIGID STEEL CONDUIT WHERE EXPOSED TO WEATHER,PLACED PROJECT NUMBER: B24-1032
<br /> UNDERGROUND,IN OR UNDER CONCRETE OR MASONRY CONSTRUCTION, IN CONTACT WITH PROJECT LEAD: JGG
<br /> EARTH AND AS INDICATED ON PLANS.
<br /> DRAWN BY: CMB
<br /> a
<br /> B. EMT MAY BE USED IN ABOVE GRADE INTERIOR DRY LOCATIONS AND WHERE
<br /> PROTECTED FROM PHYSICAL DAMAGE.
<br /> C. FLEXIBLE METAL CONDUIT SHALL BE USED WHERE REQUIRED TO MAKE SHEET NO
<br /> E0.01 -CT