Laserfiche WebLink
/PAS <br /> AM/SOLAR <br /> 3211 Martin Luther King Jr Way S. <br /> PV Electrical Calculations Seattle,WA 98144(206)707-9937 <br /> I i <br /> Total AC Comb. EGC <br /> Inverter Specs Watts(w) Output(A) AC Voltage #of Inverters I OCPD out.(A) OCPD (AC) Array Specs (Adjusted for Temperature) <br /> di <br /> SolarEdge SE50KUS ' 50000 139.50 208 1 175 Inverter _ SolarEdge SE50KUS SolarEdge SE14.4KUS I ****N/A**** <br /> SolarEdgeSE14.4KUS 14400 40.00 208 1 50 179.5 225 #4 Mppt Input 1 2 3 1 2 3 1 2 3 <br /> ****N/A**** 0 0.00 0 0 I 0 Amperage (Imp) 15.83 17.41 0.00 21.37 0.00 0.00 0.00 0.00 0.00 <br /> I EGC THIS DRAWING CONSTITUTES THE <br /> Module Specs Watts(w) Imp Vmp Voc Isc Temp.Coef V(oc) Voltage(Vmp) 600.0 600.0 0.0 400.0 0.0 0.0 0.0 0.0 0.0 `AND I TERECEPTOR POS ES ION DOESO R N <br /> 1 (DC) CONFER ANY RIGHT IN OR LICENSE TO USE IT <br /> OR THE INFORMATTION DISCLOSED HERE IN <br /> 475 10.66 44.54 53.58 11.24 Max Volta e DC 600.0 600.0 0.0 600.0 0.0 0.0 0.0 O 0 O 0 NOR ANY RIGHT TO REPRODUCETHIS <br /> Q.Peak DUO XL G10.2 475 g ( )iDRAWING OR ANY PART HERE IN WITHOUT <br /> -0.27 #10 THE WRITTEN CONSENT OF A&R SOLAR. <br /> Temp.Adjusted 40.8 57.9 Max Amps (DC) 18.00 18.00 0.00 18.00 0.00 0.00 0.00 0.00 0.00 <br /> Optimizer? P960 SolarEdge Dual Optimizer Max current output: 18A, Max Voltage:80V" Max Array Power(STC): 87.4 kW DC <br /> Z r <br /> Equipment SolarEdge SE50KUS SolarEdge SE14.4KUS ****N/A**** Max Continuous AC Power: 64.4kW AC 0 © <br /> N <br /> Mppt Input 1 2 3 1 2 3 1 2 3 _ U GI <br /> Module Q.Peak DUO XL-G10.2 475 Q.Peak DUO XL-G10.2 475 ****SELECT**** Z Up ce Q <br /> #Modules per String 20 22 0 18 0 0 0 0 0 Interconnection Caics a Site Conditions E <br /> cn <br /> #Strings 3 4 0 2 0 0 0 0 0 1 Main Breaker 800 ASHRAE Site: Everett H 0 I- <br /> #of Mods per group 60 88 0 36 0 0 0 0 0 Bus Bar 1200 Low Temp(°F) 23 < o w <br /> #of Mods/inverter 148 36 0 Max PV OCD Allowed 640 High 2%Temp(°F) 79 CL rsi z > <br /> w <br /> #of Inverters 1 1 0 PVOCPD Device Used 225 High 0.4%Temp(°F) 91 H <br /> Total#of Modules 184 Tap or Breaker? Breaker Ct Q <br /> wit W UU w > <br /> Z iz <br /> Distance (QTY)Phase Neutral Neutral EGC Conduit Min. 90°C Temp Fill Derated 75°C ' Current Operating Voltage 12 w <br /> w <br /> Ref. Conductors AW,vG! (QTY) (AWG) Type ' Conduit Rating Correct Derate Ampacity Rating 0125% Voltage Drop u co 2 <br /> A (String)toJbox 150 CU #10 2 N/A N/A #10 PV Wire 600V AIR 1 N/A 40 1 100% 40.00 30 1 22.5 600 0.98% rt op p w <br /> B lboxtoInverter 90 CU #10 10 N/A N/A #10 THWN-2 EMT 1.25" 40 1 50% 20.00 30 22.5 600 0.59% 0 Q w <br /> C Inverted to Load Center 10 AL 4/0 3 #6 1 #6 THWN-2 EMT 2" 205 1 100% 205.00 180 174.4 208 0.12% w N <br /> D Inverter2 to Load Center 10 AL #6 3 #10 1 #10 THWN-2 EMT 0.75" 55 1 100% 55.00 50 50.0 208 0.27% cc T' <br /> aco <br /> E Load Center to Disco. 10 AL 300 3 #4 1 #4 THWN-2 EMT 2.5" 260 1 100% 260.00 230 224.4 208 0.11% <br /> F Disco.To Interconnection 15 AL 300 3 #4 1 #4 THWN-2 EMT 2.5" 260 1 100% 260.00 230 224.4 208 0.16% REVISIONS <br /> G REV. # DATE: <br /> 0 Oct 26, 2021 <br /> H 1 May 17,2022 <br /> DC Voltage Drop:1.83% AC Voltage Drop: 0.54% 2 Jun 08, 2022 <br /> 3 Jan 05,2023 <br /> DESIGNED: DANIEL H. <br /> PM: ANDREW HOULE <br /> CELL: (262) 331-0485 <br /> t ( )ELECTRICAL <br /> CALCULATIONS E2.1 ELECTRICAL <br /> CALCULATIONS- <br /> NTS <br /> I,_ BUILDING A <br />