1 I 2 I 3 I 4 I 5 <br /> ' ea ACOFFMAN <br /> ENGINEERS <br /> 135 W.Fairhaven Ave <br /> Suite 102 <br /> Burlington,WA 98233 <br /> GENERAL HVAC NOTES SPECIFICATIONS ph 360.707.5656 <br /> DIVISION 23-HEATING VENTILATION AND AIR CONDITIONING www.coffman.com <br /> 1. SHEET METAL DUCTWORK AND COMPONENTS INCLUDING HANGING, HANGERS AND SUPPORTS FOR HVAC,PIPING AND EQUIPMENT <br /> SEALING,PLENUMS,&ACCESSORIES SHALL BE CONSTRUCTED IN STRICT <br /> ACCORDANCE WITH THE LATEST EDITION OF SMACNA STANDARDS FOR • HANGERS,BRACKETS,ANCHORS AND MISCELLANEOUS SUPPORTS SHALL BE PROVIDED <br /> BRACEAC ALLUCT CONSTRUCTIONDLARGER WHICHARE SUSPENDEDARDS.EARTHQUAKE FOR THE INSTALLATION OF ALL PIPING AND HVAC EQUIPMENT. D C, BRAT <br /> D ALL DUCTS 28"DIA AND LARGER ARE MORE • SUPPORTING DEVICES SHALL BE ATTACHED TO CEILING,WALLS AND FLOORS BY BOLTS ,�,A pt 0 <br /> THAN 12"BELOW STRUCTURAL SYSTEM. AND FASTENERS. Q.y <br /> 2. PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE • PIPE HANGERS AND VERTICAL SUPPORT SPACING SHALL BE IN COMPLIANCE WITH THE " $tt` _ <br /> WITH THE CURRENT IBC 1613. 2018 INTERNATIONAL MECHANICAL CODE. '� A , <br /> 3. ALL DUCTWORK OPENINGS SEATO SHALL BE OPEN DURING CONSTRUCTION. • ROUNTS,EQUIRE TSANCHORS AND BRACINGRESHALLP MEET 2016 I.B.0 AND I.M.C. SEISMIC <br /> ALL DAMPERS TO BE SET TO FULL OPEN DURING CONSTRUCTION PRIOR TO REQUIREMENTS AND MANUFACTURER'S SPECIFICATIONS. <br /> BALANCING. �llM11� <br /> VIBRATION AND SEISMIC CONTROLS FOR HVAC <br /> 4. PROVIDE UL LISTED FLEXIBLE CONNECTION ON INTAKE AND DISCHARGE OF <br /> ALL MECHANICAL EQUIPMENT.HVAC UNIT FLEXIBLE DUCT CONNECTIONS THE SEISMIC BRACING AND ANCHORAGE OF DUCTWORK AND EQUIPMENT SHALL BE 8124/22 <br /> SHALL BE MINIMUM OF 6 INCHES LONG AND HELD IN PLACE WITH HEAVY CONSTRUCTED WITH"GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS <br /> METAL BANDS,SECURELY ATTACHED TO PREVENT ANY LEAKAGE AT THE AND PLUMBING PIPING SYSTEMS",PUBLISHED BY SMACNA(MOST RECENT EDITION). <br /> CONNECTION POINTS.FLEXIBLE CONNECTIONS SHALL BE FABRICATED <br /> FROM APPROVED FLAME PROOF FABRIC CONFORMING TO NFPA90A. CONTROLS FOR HVAC <br /> ASBESTOS CLOTH IS NOT ACCEPTABLE. <br /> 5. CONTRACTOR SHALL PROVIDE TRANSITION TO CONNECT TO ALL A.RESPONSIBILITY <br /> MECHANICAL EQUIPMENT. THE CONTROLS ARE TO BE PROVIDED AS PART OF A COMPLETE HVAC SYSTEM. _ <br /> 6. DUCT DIMENSIONS SHOWN ARE INSIDE SHEET METAL DIMENSIONS OR B. SPECIFICATIONS <br /> CLEAR OPENING INSIDE LINED DUCT.THE FIRST NUMBER REPRESENTS THE • ALL CONTROLS SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES INCLUDING <br /> WIDTH OF DUCT IN PLAN VIEW. THE 2018 VERSIONS OF THE INTERNATIONAL CODES AND WASHINGTON STATE ENERGY <br /> 7. ALL ELBOWS SHALL BE LONG RADIUS ELBOWS WHEREVER POSSIBLE OR CODE. <br /> SHALL HAVE TURNING VANES WHERE INDICATED ON PLANS.NO SQUARE • ALL CRITERIA NOT SPECIFIED HEREIN,BUT NECESSARY FOR COMPLETE SYSTEMS <br /> THROAT OR ZERO RADIUS ELBOWS ALLOWED. SHALL BE PROVIDED. <br /> 8. ALL DUCT BRANCH CONNECTIONS TO DIFFUSERS OR GRILLES AND TO OR • THE CONTRACTOR IS RESPONSIBLE FOR INSTALLING THE CONTROLS PER <br /> FROM MAIN DUCTS,SHALL INCLUDE MANUAL VOLUME DAMPERS.AU. MANUFACTURER'S INSTALLATION INSTRUCTIONS. LUNA MEXICAN GRILL <br /> SPIN-IN FITTINGS SHALL BE CONICAL.RECTANGULAR BRANCH DUCT C.HVAC CONTROLS 6600 EVERGREEN WAY <br /> TAKEOFFS SHALL HAVE 45°TAKEOFFS. • THE PLANS ARE SCHEMATIC BY NATURE AND DO NOT SHOW EVERY ASPECT OF THE <br /> 9. PROVIDE CONCEALED OR REMOTE DAMPER REGULATORS OR ACCESS COMPONENTS AND CONTROLS OF THE SYSTEMS.THE CONTRACTOR SHALL SUBMIT TO EVERETT,WA <br /> DOORS FOR ALL INACCESSIBLE.REFER TO ARCHITECTURAL DRAWINGS ORCELINGTYPES. DEMONSTRATE HOW ANUAL VOLUME DAMPERS LOCATED THAT ARE THE OWNER RTHE HVAC SYSTEM WILL BECONTROLLED.COMPONENTS AND ENOUGH FlC INFORMATION TO 98203 <br /> ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT <br /> PRIOR TO INSTALLATION. D.EXECUTION C <br /> • THE MECHANICAL CONTRACTOR SHALL COORDINATE AND PROVIDE INTERFACING C <br /> 10.PROVIDE RETURN DUCT SMOKE DETECTOR AUTOMATIC SHUT DOWN OF ALL BETWEEN THE CONTROLS FURNISHED WITH INDIVIDUAL PIECES OF EQUIPMENT. <br /> NEW HEATING,COOLING,OR VENTILATION EQUIPMENT MOVING 2,000 CFM <br /> OR GREATER PER SECTION 606 OF THE CURRENT IMC.THE ELECTRICAL <br /> CONTRACTOR SHALL PROVIDE POWER AND INTERLOCK WIRING TO THE DUCTING SYSTEMS: <br /> BUILDING FIRE ALARM SYSTEM.BAS TO MONITOR FIRE ALARM CONTROL <br /> PANEL AND SHUT DOWN ALL FAN TERMINAL UNITS DURING ANY BUILDING 1. RIGID DUCTWORK SHALL BE CONSTRUCTED,ERECTED,AND SEALED IN ACCORDANCE <br /> FIRE ALARM EVENT,IN ACCORDANCE WITH THE CURRENT IMC 606.2.2. WITH THE 2018 INTERNATIONAL MECHANICAL CODE.(603) <br /> 11.PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE <br /> SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO AS TO MAINTAIN <br /> THE INTEGRITY AND RATING OF THE FLOOR OR WALL 2. ALL RIGID HVAC DUCTWORK IS 2.0 INCH W.C.PRESSURE CLASSIFICATION(603.3) <br /> 12.CONTRACTOR SHALL FURNISH COMBINATION STARTERS SIZED IN 3. RIGID DUCTWORK SHALL BE GALVANIZED MEETING SMACNA HVAC DUCT <br /> ACCORDANCE WITH THE MOTOR RATING OF THE MECHANICAL EQUIPMENT. CONSTRUCTION STANDARDS-METAL AND FLEXIBLE. <br /> STARTERS SHALL BE SUPPLIED WITH FUSES OR CIRCUIT BREAKERS, <br /> CONTROL TRANSFORMER,OVERLOADS,ONE N.O.AND ONE N.C.AUXILIARY 4. RIGID DUCTWORK SHALL BE ALUMINUM FOR HIGH MOISTURE MEETING SMACNA HVAC <br /> CONTACT AND H.O.A.SWITCH MOUNTED IN THE COVER.STARTER DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE. <br /> ENCLOSURE SHALL BE NEMA RATED FOR ITS LOCATION.STARTER SHALL BE — <br /> INSTALLED AND WIRED BY THE ELECTRICAL CONTRACTOR.MOTOR <br /> STARTERS NOT LISTED AS BEING PROVIDED IN THE HVAC EQUIPMENT MECHANICAL INSULATION <br /> SCHEDULES ARE TO BE PROVIDED BY ELECTRICAL CONTRACTOR. <br /> 13.COORDINATE LOCATIONS OF ALL ROOM THERMOSTATS OR ROOM A. GENERAL <br /> TEMPERATURE SENSORS WITH ARCHITECT PRIOR TO INSTALLATION. <br /> 14.SUPPLY DUCTWORK 2"STATIC PRESSURE CLASS WITH ALL TRANSVERSE MANUFACTURERS:MANVILLE,OWENS-CORNING,CERTAINTEED,OR KNAUF.INSTALL <br /> JOINTS,LONGITUDINAL SEAMS,AND DUCT WALL PENETRATIONS SEALED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. <br /> (SMACNA SEAL CLASS A).SPIRAL LOCK SEAMS IN ROUND AND FLAT OVAL INSULATION THICKNESS:PER WSEC. <br /> DUCTWORK DO NOT REQUIRE SEAUNG. <br /> PERMIT <br /> 15.EXHAUST AND RETURN DUCTWORK:2"STATIC PRESSURE CLASS WITH ALL B. INSULATION MATERIALS <br /> TRANSVERSE JOINTS,LONGITUDINAL SEAMS,AND DUCT WALL <br /> PENETRATIONS SEALED(SMACNA SEAL CLASS A).1"PRESSURE CLASS INDOOR PIPE INSULATION:FIBERGLASS PIPE INSULATION WITH ALL-SERVICE(VAPOR <br /> ACCEPTABLE BETWEEN GRILLES AND FIRST DAMPER. BARRIER)JACKET SHALL BE PROVIDED FOR ALL PIPING SYSTEMS,EXCEPT <br /> IS.GREASE DUCTWORK PRIOR TO CONCEALMENT BY FIRE-WRAP REFRIGERANT PIPING.FITTINGS SHALL BE MITERED SECTIONS OF INSULATION WITH <br /> APPLICATION,PERFORM A LEAKAGE TEST IN ACCORDANCE WITH SECTION THE SAME THICKNESS AS ADJACENT PIPE INSULATION WITH FACTORY-PREMOLDED, <br /> B 506.3 ONE-PIECE,UL LISTED(25/50)PVC FITTING COVERS.INSTALLATION MUST REFLECT B <br /> CAREFUL WORKMANSHIP,AND BE NEAT IN APPEARANCE.VAPOR BARRIER SHALL BE <br /> 17.MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL BE SEALED AT ALL JOINTS ON COLD PIPING. <br /> LISTED AND LABELED AS HAVING A FLAME SPREAD INDEX OF NOT MORE <br /> THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN OUTDOOR PIPE INSULATION:INSULATION AND FITTINGS SAME AS SPECIFIED FOR <br /> TESTED IN ACCORDANCE WITH ASTM E 840R UL 723,EXCEPT AS NOTED IN INDOOR PIPE INSULATION.PROVIDE METAL JACKETS OF 0.016"ALUMINUM WITH <br /> C SECTIONS 602,2.1.1 THROUGH 602.2.1.7 OF THE CURRENT IMC. INTEGRAL VAPOR RETARDER,SELF-SEALING,WATERTIGHT METAL BANDS FOR BUTT <br /> a JOINTS.SEAL JOINTS WITH ALUMINUM PIGMENTED VAPOR RETARDER MASTIC, <br /> Eli FOSTER 60-65,OR APPROVED EQUIVALENT. <br /> ROOF DRAIN BODY INSULATION:FLEXIBLE FIBERGLASS BLANKET CONFORMING TO <br /> ASTM C 553,TYPE I,AND NOMINAL DENSITY NOT LESS THAN 1 LB.PER CUBIC FOOT, <br /> COVERED WITH 8-OUNCE CANVAS AND VAPOR RETARDER CEMENT. <br /> REFRIGERANT PIPING INSULATION:3/4"THICK IMCOA"IMCOLOCK"OR"IMCOSHIELD" REV DATE DESCRIPTION <br /> INSULATION ON ALL REFRIGERATION GAS PIPING,AND ALL OUTDOOR <br /> REFRIGERANT LIQUID PIPING.NOT FOR USE ON OTHER PIPING SYSTEMS.PROVIDE <br /> METAL JACKETS OF 0.016"ALUMINUM ON OUTDOOR INSULATION. PROJ.NO. 221999 <br /> Li <br /> a DUCT AND PLENUM INSULATION:FIBERGLASS,0.75-POUND DENSITY,FLEXIBLE DUCT DRAWN NH <br /> INSULATION WITH KRAFT VAPOR BARRIER.VAPOR BARRIER SHALL BE SEALED AT ALL <br /> 5 JOINTS AND ACCESS DOORS,ETC.IN GENERAL,INSTALLATION MUST REFLECT CHECKED TB <br /> CAREFUL WORKMANSHIP,NEAT IN APPEARANCE. <br /> DATE 08/24/2022 <br /> ©COFFMAN ENGINEERS INC. <br /> 8 <br /> SHEET TITLE: <br /> MECHANICAL <br /> S SPECIFICATIONS <br /> y A A <br /> 3 <br /> 3 <br /> 5 <br /> a <br /> 3 <br /> O <br /> SHEET NO: <br /> M0.2 <br /> 0.S SHEET OF XXX <br /> .- 1 I 2 I 3 I 4 I 5 <br />