7.6.4 Overcurrent Protection <br /> Overcurrent protection was provided by a 600 Amp breaker with a <br /> 450 Amp trip unit. Additional overcurrent protection was provided <br /> by devices as shown on the electrical diagrams. <br /> 7.6.5 Wiring <br /> All wiring was found to be UL listed or recognized type MTW/THHN <br /> or equivalent. <br /> 7.6.6 Equipment Discrepancies <br /> No discrepancies were observed during the evaluation of the <br /> equipment listed in Section 5.0. <br /> 8.0 TESTING RESULTS AND INSTRUMENTS <br /> 8.1 Field Testing <br /> The following field-testing was completed with the summary results as <br /> indicated. Please refer to the Product Evaluation Data Sheet in Appendix <br /> B in this report for complete details on the specific tests completed. <br /> 8.1.1 Operation of EMO Switches <br /> Each EMO switch provided on the equipment listed in Section 5.0 <br /> was operated individually while the machine was operating. <br /> Actuation of each EMO switch was verified to properly stop the <br /> operation of the equipment. <br /> 8.1.2 Bonding Test <br /> The equipment bonding was verified as being properly installed. <br /> The resistance was measured from the main equipment grounding <br /> terminal to all applicable exposed metal structures or surfaces and <br /> installed equipment ground points. The maximum resistance <br /> permitted is 0.1 Ohm. The test results indicated satisfactory <br /> bonding with all resistance measures below 0.1 Ohm. <br /> Reference No.: 1108546 Page 11 <br />