Laserfiche WebLink
7.5.3 Guarding of Live Parts <br /> All internal components are enclosed in a grounded, screw closed, <br /> metal enclosure, and are effectively guarded per NEC', Section <br /> 110.27. <br /> 7.5.4 Overcurrent Protection <br /> Overcurrent protection was provided by a 125 Amp NRTL breaker. <br /> Additional overcurrent protection was provided by devices as <br /> shown on the electrical diagrams. <br /> 7.5.5 Wiring <br /> All wiring was found to be UL listed or recognized type MTW/THHN <br /> or equivalent. <br /> 7.5.6 Equipment Discrepancies <br /> No discrepancies were observed during the evaluation of the <br /> equipment listed in Section 5.0. <br /> 7.6 Cells 7 and 8 Bus Lower Bus Expansion and Gates <br /> 7.6.1 System Description <br /> The equipment inspected consists of Cells 7 and 8 Bus Lower Bus <br /> Expansion and Gates manufactured by El. The equipment is rated <br /> at 600VAC, 3 Phase, 60HZ, 450 Amps, 10KA and the lower bus <br /> bar was extended and addition safety zones and a safety gate was <br /> added. The equipment is installed indoors in an ordinary (non- <br /> hazardous) location, and has been evaluated for use in this location <br /> only. <br /> 7.6.2 Grounding <br /> Exposed non-current carrying parts of the equipment were verified <br /> to be effectively grounded in accordance with the applicable <br /> provisions of NEC°, Article 250. <br /> 7.6.3 Guarding of Live Parts <br /> All internal components are enclosed in a grounded, screw closed, <br /> metal enclosure, and are effectively guarded per NEC', Section <br /> 110.27. <br /> Reference No.: 1108546 Page 10 <br />