Laserfiche WebLink
Four Corners- Building D Page 14 of 15 <br />All <br />Engineering <br />Smoke Control Weekly Self Test Verification <br />Test Conditions <br />Item <br />I Protocol <br />Yes <br />No <br />1 <br />All systems set to NORMAL. <br />X <br />2 <br />Activate the weekly self test. <br />X <br />Initiating <br />Device: MP <br />3 <br />Activate an alarm initiating device. <br />X <br />4 <br />Verify self test aborts and smoke control <br />system initiates proper response. <br />X <br />Building/FI <br />oor: G <br />5 <br />Alarm system activates fire alarm visual & <br />audible appliances throughout building. <br />X <br />6 <br />Alarm, fan, damper status correctly <br />annunciated on FSCP. <br />X <br />7 <br />Verify smoke control fans and dampers <br />ON/OPEN per matrix. <br />X <br />8 <br />Return all systems to NORMAL. <br />X <br />9 <br />Set weekly self test to activate. <br />X <br />10 <br />Activate an alarm initiating device. <br />X <br />11 <br />Wait for weekly test to initiate and verify that <br />that weekly self test does not interrupt alarm <br />levent. <br />X <br />12 <br />lReturn all systems to NORMAL. <br />X <br />Verified by: Company: Date: <br />Travis Allen Allen Engineering, PLLC 2/15/2024 <br />Comments: <br />