Laserfiche WebLink
Four Corners- Building D <br />Page 15 of 15 <br />Allen <br />Engineering <br />11 Non -Conforming Condition Log <br />Building/Log No. <br />Date <br />Status <br />Description <br />Corrected Datz <br />D-1 <br />2/15/2024 <br />Complete <br />The damper associated with pressurization Fan 1 does not correctly report a loss of AC FAULT condition. <br />2/15/2024 <br />D-2 <br />2/15/2024 <br />Complete <br />Stair 1, level G door to exterior and garage failed to close and latch. <br />2/15/2024 <br />D-3 <br />2/15/2024 <br />Complete <br />Stair 2, level G door to exterior and garage failed to close and latch. <br />2/15/2024 <br />D-4 <br />2/15/2024 <br />Complete <br />Building D main waterflow did not illuminate appropriate lamps on FSCP <br />2/15/2024 <br />www.AllenFPE.com 4412 Shelby Road. Lynnwood WA 98087 (425) 954-2050 15 of 15 <br />