Laserfiche WebLink
DEDICATED OUTSIDE AIR UNIT(DOAS)SCHEDULE EXHAUST FAN SCHEDULE <br /> EQUIP. FAN ENERGY ELECTRICAL WEIGHT EQUIP FAN AIRFLOW EXT.SP MOTOR BONES WEIGHT <br /> NO. ARRANGEMENT I DISCHARGE AIRFLOW ESP RECOVERY LBS MANUFACTURER&MODEL REMARKS NO AREA SERVED TYPE CFM IN WG RPM (INLET) DRIVE MANUFACTURER I MODEL (LBS.) CONTROL REMARKS <br /> CFM IN WG EFF.% VOLTS PHASE AMPS WATTS ( ) HP(W) VOLTS/PHASE ( <br /> ERV-1 HORIZONTAL DUCTED 300 0.4 70 208 1 2.0 155 80 MITSUBISHI LGH-F300RVX-E CREF-1 COMPRESSED AIR ROOM ROOFTOP CENTRIFUGAL 9,000 0.375 630 2 46013 15.8 DIRECT GREENHECKGB-300 VGD-20 175 DDC <br /> ERV-2 ROOFTOP 225 0.4 70 208 3 5.7 350 RENEWAIREHEIXRT ROOFTOP ADD VFD,BALANCE TO <br /> (E)EF-18 TIRE SHOP CENTRIFUGAL 1,000 0.5 NIA 5 46013 NIA N/A NIA NIA DDC 1,000 CFM <br /> EF-19 WELDING ROOFTOP 3,370 0.5 803 3l4 115/1 10.9 BELT GREENHECKGB-200-7 99 DDC <br /> NOTES: DOAS UNIT SHALL COMPLY WITH WSEC 403.6.3 CENTRIFUGAL <br /> EF-25 ELEC.ROOM ROOFTOP 1,200 0.125 921 114 11511 7.0 DIRECT GREENHECKG-133-VG 47 DDC <br /> ELECTRIC UNIT HEATER SCHEDULE CENTRIFUGAL ROO TOP <br /> ELECTRICAL (E)IP-2 INSPECTION PIT CENTRIFUGAL 5,000 3.74 1750 5 48013 NIA BELT GREENHECK CUBE-38XP•VGD-50 NIA NIA <br /> EQUIP. TYPE SERVICE MANUFACTURER&MODEL WEIGHT REMARKS ROOFTOP <br /> N0. VOLTS KW PHASE LBS GEF-1 MAINTENANCE BAYS CENTRIFUGAL 6,500 0.375 917 2 48013 20 BELT GREENHECKGB-220-VGD 150 DDC - <br /> UH-1 SUSPENDED COMPRESSED AIR-199 KING KBP 208 4.0 1 25 1,2,3,4 GEF-2 MAINTENANCE BAYS ROOFTOP CENTRIFUGAL 5,000 0.58 788 1 460/3 15.2 BELT GREENHECK GB-220-10 138 DDC <br /> GEF3 BODY SHOP ROOFTOP CENTRIFUGAL 7,000 0.67 901 2 46013 19.7 BELT GREENHECKGB-240-20 148 DDC <br /> GEF4 INSPECTION PITS ROOFTOP REMARKS: CENTRIFUGAL 14,000 0.5 596 5 48013 22 BELT GREENHECKGB-380-50 277 DDC <br /> 1.CEILING SUSPENDED FAN POWERED ELECTRIC UNIT HEATER. <br /> 2.COORDINATE LOCATION OF UNIT WITH ARCHITECTURAL FEATURES AND ALL OTHER TRADES. <br /> 3.REFER TO ELECTRICAL DRAWINGS FOR DISCONNECT SWITCH. 1.FANS SHALL BE SIZED SO TOTAL EFFICIENCY IS WITHIN 15%OF THE FAN MAXIMUM TOTAL EFFICIENCY. <br /> 4.PROVIDE WITH MOUNTING BRACKET AND ALL SUPPORT ACCESSORIES. <br /> VEHICLE EXHAUST HOSE REEL SCHEDULE <br /> HOSE HOSE <br /> EQUIP AIRFLOW EXTTP MOTOR MANUFACTURER <br /> N0. AREA SERVED FAN TYPE CFM IN WG RPM DRIVE LENGTH, DIAMETER, &MODEL CONTROL REMARKS <br /> HP VOLTS PHASE FT. IN, <br /> HR-1 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-2 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-3 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR4 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-5 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-6 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-7 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-8 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-9 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3.384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-10 BUS SERVICE BAY CENTRIFUGAL 800 6.5 1 3.384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-11 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3.384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-12 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-13 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 23 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,3,4 <br /> HR-14 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-15 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-16 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-17 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-18 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-19 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 j 2 j 460 3 j DIRECT 23 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,3,4 <br /> HR-20 BUS SERVICE BAY CENTRIFUGAL 800 6.6 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-21 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-22 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-23 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 23 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,3,4 <br /> HR-24 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-25 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-26 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-27 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-28 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-29 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-30 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-31 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> HR-32 BUS SERVICE BAY CENTRIFUGAL 800 6.5 3,384 2 460 3 DIRECT 35 8 NEDERMAN SERIES 865 PENDANT SWITCH 1,2,4 <br /> REMARKS: <br /> 1.PROVIDE WITH NFC 4.2 HOSE FOR EXHAUST,MODEL NO.86900683. <br /> 2.PROVIDE WITH N27 FAN AND FAN ADAPTER,MODEL NO,20373556. <br /> 3.EXISTING UNIT TO REMAIN. <br /> 4.115V/1PH DIRECT DRIVE TUBE MOTOR.INCLUDE PENDANT CONTROLAND CABLE BRACKET,MODEL NO.20373712. <br /> BE NO, DATE REVISION MCOB MAINTENANCE IMPROVEMENTS DRAWN:BSB FIR ECTNO.:20.002 <br /> 1 "��.� FACILITIES MASTERPLAN PHASE 3A DESIGNED:BSB DATE:APRIL 13,2021 <br /> 7100 HARDESON ROAD,EVERETT WA 98203 CHECKED:LWB ITB#2021.011 <br /> 1601 6th Avenue,Suite 1600 ]1]9 <br /> WA 98101 RESia <br /> 206.62 re DRAWING NO.: M .4-M B <br /> soe.8]2.88YP FSS�ONAIENB�a MECHANICAL SCHEDULES <br /> www.kpff.aom BOGARD ENGINEERS,PS Page 213 of 363 <br />