ROOFTOP MULTIZONE UNIT SCHEDULE <br /> AS HEATING <br /> EQUIP SUPPLY FAN G #OF ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 WEIGHT LENGTH WIDTH HEIGHT <br /> N0, AREA SERVED MIN.WHEEL EXTSP MOTOR QTY.OF INPUT OUTPUT ZONES CFM CFM CFM CFM CFM CFM MANUFACTURER I MODEL LBS.) (IN) (IN) (IN) CONTROL REMARKS <br /> FAN TYPE CIA.(IN. CFM N. <br /> W.G. BHP MOTORS VOLTSIPHASE (MBH) (MBH) <br /> MZ-1 MAINTENANCE SUPPORT AIRFOIL 30.0 27,000 4.5 25.77 2 460/3 700 560 6 795 5,645 1,590 6,820 11,265 870 ENGINEERED AIR/DJE 100 8,800 297 134 107 ZONE T-STATS 1 <br /> REMARKS: <br /> 1. OUTPUT CAPACITIES OF HEATING AND COOLING EQUIPMENT AND SYSTEMS SHALL BE NO GREATER THAN THE SMALLEST AVAILABLE EQUIPMENT SIZE THAT EXCEEDS THE CALCULATED LOADS. <br /> ROOFTOP AIR CONDITIONING UNIT SCHEDULE <br /> EQUIP SUPPLY FAN COOLING COIL NAT.GAS HEATING MIN. ELECTRICAL WEIGHT <br /> NO. AREA SERVED EXT SP I MOTOR TOTAL ISENSIBLE EAT DB EAT WB INPUT OUTPUT OSA MANUFACTURER I MODEL CONTROL REMARKS <br /> FAN TYPE CFM IN.W.G. HP MBH MBH LAT(F) °F (MBH) (MBH) CFM VOLTS PHASE Hz MCA MFS (LBS.) <br /> AHU-3 PARTS/STORAGE FORWARD 5,000 0.5 3 156 124 55 80 67 250 200 1,500 460 3 60 29 40 TRANEYSD150G4 1,718 DDC SYSTEM 1 <br /> CURVED <br /> REMARKS: <br /> 1, PROVIDE WITH ECONOMIZER AND POWERED EXHAUST. <br /> ROOF HOOD SCHEDULE AIR COMPRESSOR SCHEDULE <br /> EQUIP. <br /> NOMINAL COMPRESSOR <br /> EQUIP AIRFLOW HOOD SIZE,IN DUCT SIZE,IN MANUFACTURER& N0. SERVICE MANUFACTURER&MODEL TYPE CAPACITY MAX DELIVERY WEIGHT <br /> PRESS.PSIG LBS. REMARKS <br /> N0. AREA SERVED TYPE CFM W L H W L MODEL REMARKS ACFM HP VOLTS PHASE ( ) <br /> AC-1 ALL AREAS ROGERS KRV-50-150 ROTARY 176 150 50 460 3 3.105 <br /> RH-1 ERV-1 EXHAUST AIR EXHAUST 225 21 21 10 10 10 GREENHECK GRSR AC-2 ALL AREAS ROGERS KRV-50-150 ROTARY 176 150 50 460 3 3,105 <br /> RH-2 ERV-1OUTSIDE AIR INTAKE 225 21 21 10 10 10 GREENHECKGRSI <br /> RH-3 MAKEUPAIR INTAKE 7000 65 60 19 28 30 GREENHECKFGI PLUMBING FIXTURE CONNECTION SCHEDULE <br /> RH-4 MAKEUPAIR INTAKE 5000 21 21 10 26 26 GREENHECKFGI TAG ITEM DESCRIPTION W V CW HW <br /> RH-5 MAKEUPAIR INTAKE 7000 65 60 19 28 30 GREENHECKFGI <br /> BF-1 BOTTLE FILLER 1-1/2" 1-1/2" 1/2" HAWS CORPORATION MODEL <br /> RH-6 MAKEUPAIR INTAKE 7000 65 60 19 28 30 GREENHECKFGI 19000R APPROVED EQUAL. <br /> RH-7 MAKEUPAIR INTAKE 7000 65 60 19 28 1 30 GREENHECKFGI FD-1 O FLOOR DRAIN 2" 2" - - <br /> HS-1 } HOSE BIBB - - 3/4" - <br /> ROOFTOP HEAT AND VENT UNIT SCHEDULE <br /> L-1 ® LAVATORY-RESTROOM 2" 2" 1/2" 112" <br /> EQUIP. - - - <br /> AIRFLOW MIN. INPUT MOTOR MANUFACTURER& WEIGHT, <br /> NO. AREA SERVED TYPE CFM OUTSIDE CAPACITY HP VOLTS PHASE FILTERS MODEL LBS REMARKS RD-1 Go ROOF DRAIN WITH OVERFLOW 3" <br /> AIR CFM MBH <br /> HV-1 MAINTENANCE BAYS NATURAL GAS 33,600 10,000 3,016 25 460 3 2"DISP. APPLIED AIR DFC-225 5,015 1,2 S-1 ® UTILITY SINK 3" 2" 112" 1/2" <br /> HV-2 NOT USED <br /> HV3 MAINTENANCE BAYS NATURAL GAS 16,000 1,650 1,419 15 460 3 2"DISP. APPLIED AIR DFC-218 2,502 1,2 S-2 ® KITCHEN SINK 2" 2" 112" 1/2" <br /> HV4 MAINTENANCE BAYS NATURAL GAS 10,500 2,400 932 7.5 460 3 2"DISP. APPLIED AIR DFC-215 2,155 1,2 TD-1 TRENCH DRAIN Y. - - - <br /> HV-5 BODY SHOP NATURAL GAS 18,000 1,800 1,597 15 460 3 2"DISP. APPLIED AIR DFC-220 3,580 1,2 WH-1 WALL HYDRANT - - 3/4" - <br /> REMARKS: <br /> 1. DIRECT FIRED UNIT. WC-1 WATER CLOSET-FLUSH VALVE 4" 2" V _ PROVIDE WITH WATER HAMMER <br /> 2. NEW UNITS TO BE ADAPTED TO EXISTING CURB. ARRESTOR <br /> PIPE&EQUIPMENT INSULATION SCHEDULE <br /> MEAN TEMP INSULATION THICKNESS(INCHES)BY PIPE SIZE <br /> ROOFTOP AIR HANDLER EQUIPMENT DEMOLITION SCHEDULE PIPING SYSTEM TEMP RANGE THERMAL COND INSULATION <br /> Deg.F Btu*in/ hr*ft z*D F RATING MATERIAL NOTES <br /> MIN INPUT g ( ) Deg.F <1" 1"TO<1-1/2" 1-1/2"TO<4" 4"TO<8" >8" <br /> EQUIP. AIRFLOW MOTOR WEIGHT, <br /> NO. AREA SERVED TYPE CFM OUTSIDE CAPACITY HP VOLTS PHASE MANUFACTURER&MODEL LBS REMARKS <br /> AIR CFM MBH DOMESTIC COLD WATER ALL 0.21-0.27 75 FIBERGLASS 0.5 0.5 1.0 1.0 1.0 1,2,3 <br /> (E)HV-1 MAINTENANCE BAYS NATURAL GAS 33,600 10,000 2,630 20 460 3 APPLIED AIR DFC-225 5,015 1,2,3 DOMESTIC HOT WATER >105 0.21-0.28 100 FIBERGLASS 1.0 1.0 1.5 1.5 1.5 1,2,3 <br /> (E)HV-3 MAINTENANCE BAYS NATURAL GAS 16,000 7,200 1,315 15 460 3 APPLIED AIR DFC-218 2,502 1,2,3 STORM DRAIN ALL 0.23-0.27 75 FIBERGLASS 1.0 1.0 1.0 1.0 1.0 1,2,3 <br /> (E)MZ-1 MAINT.SUPPORT NATURAL GAS 27,000 WA 700 30 460 3 OCTAGON OAS-XX-27C-700G 8,600 1,2,3 <br /> (E)AHU-3 PARTS I STORAGE NATURAL GAS 5,000 1,500 250 3 460 3 TRANE YCD150C4 1,790 1,2,3 NOTES: <br /> REMARKS: 1. FOR HOT&COLD PIPING LARGER THAN 2",UTILIZE RIGID INSERTS,INSULATION THROUGH THE HANGER,SHEET METAL SHIELD. <br /> 1. ROOFTOP EQUIPMENT DEMOLITION SCHEDULE IS FOR COORDINATION ONLY AND DOES NOT REFLECT ALL EQUIPMENT TO BE DEMOLISHED,SEE DEMOLITION PLANS. 2. FOR COLD PIPES 2"AND SMALLER,UTILIZE RIGID INSERTS,INSULATION CONTINUOUS THROUGH THE HANGER,SHEET METAL SHIELD. <br /> 2. EXISTING EQUIPMENT CAPACITIES AND WEIGHTS MAY NOT REFLECT ALL ACCESSORIES AND APPERTENANCES. 3. JACKETING:METAL JACKET(SEALED WATERTIGHT)SHALL BE USED AT ALL EXTERIOR INSULATION EXPOSED TO WEATHER.PVC JACKET WITH RIGID <br /> 3. EXISTING ROOF CURBS TO REMAIN FOR ADAPTATION TO NEW UNITS. CALCIUM SILICATE INSULATION SHALL BE USED ON ALL HORIZONTAL PIPING AT OR NEAR THE FLOOR SUBJECT TO POTENTIAL FOOT TRAFFIC.PVC JACKET <br /> WILL BE UTILIZED ON ALL INTERIOR EXPOSED INSULATION WITHIN 6 FEET OF THE FLOOR ELEVATION(I.E.MECHANICAL ROOMS AND GARAGE HOSE BIBBS). <br /> HEAT PUMP SCHEDULE <br /> INDOOR COOLING CAPACITY HEATING ELECTRICAL(OUTDOOR ONLY) LIQUID SUCTION <br /> EQUIP NO AREA SERVED CONFIGURATION TOTAL SENS SEER CAPACITY CFM INDOOR MODEL OUTDOOR MODEL MOP REFRIGERANT REFRIGERANT REMARKS <br /> MBH MBH MBH VOLTS PHASE MCA (AMPS) SIZE,IN. SIZE,IN. <br /> HP-1/FC-1 BREAK ROOM HORIZONTAL DUCTED 11.8 9.8 21 9.0 400 MITSUBISHI PEAD-Al2HA7 MITSUBISHI PUZ-Al2NKA7 208 1 11 28 1A" 1/2" 1 <br /> HP-2 l FC-2 OFFICES HORIZONTAL DUCTED 17.7 13.6 20.2 12.3 625 MITSUBISHI PVA-A18HA7 MITSUBISHI PUZ-A18NKA7 208 1 11 28 1/4" 1/2" 1 <br /> REMARKS: 1. OUTPUT CAPACITIES OF HEATING AND COOLING EQUIPMENT AND SYSTEMS SHALL BE NO GREATER THAN THE SMALLEST AVAILABLE EQUIPMENT SIZE THAT EXCEEDS THE CALCULATED LOADS. <br /> OBE <br /> NO. DATE REVISION MCOB MAINTENANCE IMPROVEMENTS DRAWN:BSB PROJECT NO.:20-002 <br /> ""� FACILITIES MASTERPLAN PHASE 3A DESIGNED:BSB DATE:APRIL 13,2021 <br /> 1q)ff '' 7100 HARDESON ROAD,EVERETT WA 98203 CHECKED:LWB ITS#2021-011 <br /> 1601 5th Avenue,Suite 1600 z�38 - <br /> seame,wAs61o1 90 Reea ��`` DRAWING NO.: <br /> Zww.622.522 eSS�ONALENO\ MECHANICAL SCHEDULES Page 212of363 M 1 .3-M B <br /> HOGAM ENGMEM,PS <br />