Laserfiche WebLink
Typical Wiring <br /> Modules will accept#18 AWG(0.75mm2),#16(1.Omm2), and#14AWG(1.50mm2)I and#12 AWG(2.5Omm2)wire sizes. <br /> Note: Sizes#16 AWG(1.Omm2)and#18 AWG(0.75mm2)are preferred for ease of installation.See Signature Loop Controller catalog <br /> sheet for detailed wiring requirement specifications. <br /> Initiating(Slave)Device Circuit Wire Specifications <br /> Maximum Allowable Wire Resistance 50 ohms(25 ohms per wire)per Circuit <br /> Maximum Allowable Wire Capacitance 0.1 uF per Circuit <br /> For Design Reference: Wire Size Maximum Distance to EOLR <br /> #18 AWG(0.75 mm2) <br /> #16 AWG(1.00 mm2) 4,000 ft(1,219 m) <br /> 414 AWG(1.50 mm2) <br /> #12 AWG(1.50 mm2) <br /> Typical N.O.Initiating Device Typical N.O.Initiating Device <br /> JE INPUT 1 INPUT 2 <br /> C IC <br /> Q1 Q2 Q4 Style B(Class B) 31 <br /> TB2 <br /> TB2 <br /> 8 7 UL/ULC Listed Style B(Class B) <br /> • • • 47KQ EOL UL/ULC Listed 8 7 6 5 UL/ULC Listed <br /> 47KEI EOL 1��2 ® • • • 47KQ EOL <br /> Red LED Green LED <br /> (Alarm/Active) 0 Oo (Normal) Red LED Green LED <br /> 4 3 2 1 (Alarm/Active) 4 3 2 1 (Normal) <br /> TBl TBl <br /> DATA IN(+) DATA OUT(+) {(DATA IN(+) DATA OUT <br /> DATA IN(-) (+) <br /> j( l DATA IN 0 DATA <br /> l DATA OUT(-) <br /> To Next Device From Signature Controller To Next Device <br /> From Signature Controller or Previous Device <br /> or Previous Device 0 S <br /> SIGA-CT1, SIGA-CT1 HT SIGA-CT2 <br /> III Typical NO Initiating Device �I�I <br /> NOTES uuuLcustee <br /> Inputz Inputl UL/DLC Listed <br /> 47KW EOL 47KW EOL <br /> Q Maximum 25 Ohm resistance per wire. <br /> Q Maximum#12 AWG(2.5 mm2)wire;Minimum#18 AWG(0.75 mm2). AAA <br /> 30 Refer to Signature controller installation sheet for wiring specifications. <br /> ®Maximum 10 Vdc @ 350 pA Mtt2 <br /> 0 The SIGA-UI06R and the SIGA-UI02R do not come with TB14. 23° U1011RI series motherboard <br /> 6 All wiring is supervised and power-limited. Dataln+ <br /> 7 These modules will not support 2-wire smoke detectors. ®= 0 <br /> Signature TB14 No connections required for <br /> Data Mtt2 <br /> Cirtuit+ eR TB7 <br /> Other modules may require <br /> Data Out ion. <br /> Warnings & Cautions <br /> Green LED INormall TB15 <br /> This module will not operate without electrical power.As fires fre- Red LED(Active) <br /> quently cause power interruption,we suggest you discuss further ° •. <br /> safeguards with your local fire protection specialist. <br /> quired for MCT2. <br /> Compatibility SIGA-MCT2 <br /> These modules are part of EDWARDS'S Signature Series intelligent <br /> processing and control platform.They are compatible with EST3, <br /> EST3X and iO Series control panels. <br /> Page 3 of 4 DATA SHEET E85001-0241 <br /> Not to be used for installation purpo� Issue 1 <br />