Laserfiche WebLink
Installation Application <br /> SIGA-CR and SIGA-CRR:modules mount to North American The operation of Signature Series control relays is determined by <br /> 21/2 inch(64 mm)deep 1-gang boxes and 1 t/2 inch(38 mm)deep their sub-type code or"Personality Code." <br /> 4 inch square boxes with 1-gang covers and SIGA-MP mounting <br /> plates.The terminals are suited for#12 to#18 AWG(2.5 mm2 to Personality Code 8:CONTROL RELAY(SIGA-CR/MCR) <br /> 0.75 mm2)wire size. -Dry Contact Output.This setting configures the module to <br /> provide one Form "C" DRY RELAY CONTACT to control Door <br /> Closers, Fans, Dampers, etc. Contact rating is 2.0 amp Q <br /> ✓ Compatible electrical box 24 Vdc;0.5 amp @ 120 Vac(or 0.25A Q 220 Vac for non-UL <br /> applications). Personality Code 8 is assigned at the factory. No <br /> user configuration is required. <br /> Personality Code 8: POLARITY REVERSAL RELAY MODULE <br /> (SIGA-CRR/MCRR).This setting configures the module to <br /> Wall plate,wnite reverse the polarity of its 24 Vdc output. Contact rating is 2.0 <br /> (1 gang) amp Q 24 Vdc(pilot duty). Personality Code 8 is assigned at the <br /> mm factory. No user configuration is required. <br /> a <br /> R c, <br /> 0 <br /> mm, <br /> a Compatibility <br /> M These modules are part of EDWARDS's Signature Series intelligent <br /> Status LEDs processing and control platform.They are compatible with EST3, <br /> m EST3X and iO Series control panels. <br /> LED viewing ports • • <br /> O, <br /> Warnings & Cautions <br /> This module will not operate without electrical power.As fires <br /> SIGA-MCR and SIGA-MCRR:mount the UIO motherboard frequently cause power interruption,we suggest you discuss <br /> inside a suitable EDWARDS enclosure with screws and washers further safeguards with your local fire protection specialist. <br /> provided. Plug the module into any available position on the <br /> motherboard and secure the module to the motherboard with the <br /> captive screws.Wiring connections are made to the terminals on Testing & Maintenance <br /> the motherboard(see wiring diagram). UIO motherboard terminals <br /> are suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. The module's automatic self-diagnosis identifies when it is <br /> defective and causes a trouble message.The user-friendly <br /> L11 <br /> maintenance program shows the current state of each module <br /> —ulo Motherboard and other pertinent messages. Single modules may be turned <br /> off(deactivated)temporarily,from the control panel.Availability of <br /> maintenance features is dependent on the fire alarm system used. <br /> -- -- -�--� Scheduled maintenance(Regular or Selected)for proper system <br /> Plug-in(Ulo) operation should be planned to meet the requirements of the <br /> Module Authority Having Jurisdiction(AHJ). Refer to current NFPA 72 and <br /> -- -- fl--"I ULC CAN/ULC 536 standards. <br /> Cabinet or electrical enclosure <br /> Electronic Addressing -The loop controller electronically <br /> addresses each module, saving valuable time during system <br /> commissioning. Setting complicated switches or dials is not <br /> required. Each module has its own unique serial number stored <br /> in its on-board memory.The loop controller identifies each device <br /> on the loop and assigns a"soft"address to each serial number. <br /> If desired,the modules can be addressed using the SIGA-PRO <br /> Signature Program/Service Tool. <br /> EDWARDS recommends that this module be installed according <br /> to latest recognized edition of national and local fire alarm codes. <br /> Page 2 of 6 D A T_ E85001-0239 <br /> Not to be used for installa, purposes. Issue 1.1 <br />