convergjnt'
<br /> converg 'hit 450 Shattuck Avenue South,Renton,Washington 98057
<br /> Phone:425-272-2250 Fax:425-251-0949
<br /> This document and the infolmaton/depicb,ns mnWinedlshown
<br /> is the exclusive property MConv mint Technologies LLC and shall
<br /> be handled as propnetary and wnfld.nti.1 information and must be
<br /> returned upon request.This dowmenl cannot be repradumd by any
<br /> Ineons without the wdtlen euthodutlon of Convergint Technologies LLC.
<br /> PROVIDENCE PACIFIC CAMPUS
<br /> ELEVATOR T. I .
<br /> 916 PACIFIC AVE, EVERETT, WA, 98201
<br /> SYMBOL LEGEND SCOPE OF WORK WIRE LEGEND MOUNTING HEIGHTS
<br /> SYM DESCRIPTION MODEL# MANUFACTURER BACK BOX THIS SCOPE OF WORK INCLUDES: ALL WIRING AND INSTALLATION METHODS SHALL BE IN COMPLIANCE WITH CURRENT RELEVANT
<br /> THE ADDITION OF HEAT DETECTORS IN BOTTOM OF ELEVATOR SHAFTS 1-5 AND MODULES IN NATIONAL AND LOCAL ELECTRICAL CODE ARTICLES AND RELATED SECTION CODE REQUIREMENTS. A/C SUPPLY DIFFUSER
<br /> UNIVERSAL INPUT/OUTPUT MODULE CORRESPONDING UIOs FOR THE ADDITION OF ELEVATOR SHUNT TRIP.SHUNT TRIP DISCONNECT
<br /> ulo==aR MOTHERBOARD UIO EST MOUNTED IN TERMINAL CABINET SWITCH TO BE PROVIDED BY ELECTRICAL CONTRACTOR. WIRING INSTALLATION NOTES: CEILING MOUNTED
<br /> 4,a 5623-FIXED HEAT 135° 'LABEL ALL ZONE WIRES WITH ZONE NUMBER TAG AND DESCRIPTION.
<br /> SMOKEIHEAT FLUORESCENT LIGHT
<br /> H 5623 EST 4"OCTAGON BOX,1-1/2"DEEP DESIGN CRITERIA APPLICABLE STANDARDS AND GUIDANCE: 'LABEL ALL SIGNAL CIRCUIT WIRES WITH SIGNAL CIRCUIT NUMBER TAG AND DESCRIPTION. DETECTOR TYP. 3'MIN
<br /> a° WALL MOUNT ( )
<br /> NFPA 72,2016 EDITION 'LABEL ALL NETWORK,ANNUNCIATOR AND I/O CONTROL CIRCUIT WIRING WITH CIRCUIT NUMBER NOTE:DIMENSIONS SHOWN
<br /> STANDARD ADDRESSABLE SMOKE Zola WASHINGTON STATE BUILDING CODE ARE TO THE CLOSEST
<br /> Qs SIGA-OSD EST 4"OCTAGON BOX,1-1/2"DEEP TAG AND DESCRIPTION. CEILING EDGE OF THE DErECTOR
<br /> SIGA-SB4-STANDARD BASE 2018 WASHINGTON STATE MECHANICAL CODE •VERIFY W ITH OWNER AND GENERAL CONTRACTOR THAT OPEN CABLE IS ALLOWED ON SPECIFIC
<br /> 2020 NATIONAL ELECTRICAL CODE WITH STATE OF WASHINGTON AMENDMENTS
<br /> NAC POWER SUPPLY-6A SITE.(FPL,FPLP,RISER,OR 2 HOUR RATED)
<br /> Nac:xs
<br /> SIGA-CCiS MODULE EBPS6A EST INCLUDED-17"H X 13"W X 3.5"D 2018 WASHINGTON STATE FIRE CODE 'WHERE REQUIRED,OUR DRAWINGS WILL NOTE WIRE OR PATHWAY REQUIRING SURVIVABILITY.
<br /> SHUNT TRIP PANEL(PROVIDED BY ELECTRICAL SUBSTITUTE THE RELEVANT CABLE WITH AN EQUIVALENT CABLE COMPATIBLE WITH THE MEANS OF AUDIONISUAL&VISUAL 3 12"
<br /> sTP CONTRACTOR) DOCUMENTATION AVAILABLE TO CONVERGINT TECHNOLOGIES SURVIVABILITY.THIS OFTEN INCLUDES;CI-C OR Cl CABLE(CIRCUIT INTEGRITY),CONCRETE ONLY DEVICES MAX
<br /> ENCASEMENT OR OTHER MEANS AS APPROVED BY THE AHJ.REFER TO NFPA 72 FOR FURTHER b'
<br /> H ADDRESSABLE FIXED HEAT SIGA-HFD EST 4"OCTAGON BOX,1-1/2"DEEP INFORMATION.
<br /> SIGA-SB4-STANDARD BASE ELECTRICAL DRAWINGS BY ELEVATOR CONSULTING SERVICES DATED 04-01-2021 FIRE ALARM REMOTE MANUAL PULL
<br /> NON PLENUM: SINGLE COND.: PLENUM RATED: FIRE ALARM ANNUNCIATOR STATION
<br /> CIRCUIT DESCRIPTION (FPLR,FPL) (THHN,TFFN) (FPLP) CONTROL PANEL
<br /> A ZONE/INPUT CIRCUIT BELDEN 5220UL (2)#16 AWG BELDEN 6220UL
<br /> 2 COND.16 AWG [3.850][24pF/FT] [3.850][37pF/F7] 80"MIN.TO BOTTOM
<br /> OFLENS
<br /> C NA CIRCUIT CIRCUIT BELDEN 5120UL (2)#14 AWG BELDEN 612OUL OR �+
<br /> 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT] 96'MAX.TO TOP
<br /> O w
<br /> D MASS.NOTIFICATION NAC CIRCUIT BELDEN 5120UL (2)#14 AWG BELDEN 612OUL OF LENS 72'AFF 60"AFF z
<br /> 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT] 411"MAX(ADA) _
<br /> 42"MIN/54"MAX(NFPA)
<br /> E DOOR HOLDER/CONTROL CIRCUIT BELDEN 5120UL (2)#14 AWG BELDEN 612OUL
<br /> FT]
<br /> CONTACT INFORMATION 2COND.14 AWG [2.430][23pF/FT] [2.430][37pF/
<br /> F FAN/HVAC SHUTDOWN BELDEN 5120UL (2)#14 AWG BELDEN 61 20UL FINISHED FLOOR
<br /> PROJECT MANAGER FIRE ALARM DESIGNER 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT] "DEVICES SHOWN DEPICT DEVICE TYPES ONLY.
<br /> KEVI425_5 -581 DUANE_9591 Z G FUTUREADANAC BELDEN 5120UL (2)#14AWG BELDEN 612OUL
<br /> KEVIN.1-5815 DUAN 6-9591 CIRCUIT 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/F7]
<br /> KEVIN.FREY@CONVERGINT.COM DUANE.STRANTZ@CONVERGINT.COM
<br /> SALES REPRESENTATIVE H PHONE CIRCUIT BELDEN 5220FL N/A BELDEN 6220FL '
<br /> KEVIN CURREY 2 COND.16 AWG SHIELDED [3.90][65.5pF/FT] [3.850][77pF/FT] _
<br /> 206-941-4692 (2)#16 AWG BELDEN 6220UL \Pe aS -4 J SPEAKER CIRCUIT BELDEN 5220UL
<br /> KEVIN.CURREY@CONVERGINT.COM 2COND.I6 AWG [3.850][24pF/FT] [3.850][37pF/FT] cc �pC a
<br /> L ELEVATOR CONTROL BELDEN 5120UL (2)#14 AWG BELDEN 6120UL
<br /> GENERAL NOTES 2COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT] Wall St 'N
<br /> <,
<br /> M AUDIO RISER BELDEN 5220FL N/A BELDEN 6220FL rD
<br /> 2 COND.16 AWG SHIELDED [3.90][65.5pF/FT] [3.850][77pF/FT] .. in `< D
<br /> THE FOLLOWING NOTES ARE INTENDED TO BE GENERAL IN NATURE AND ARE NOT SPECIFIC TO EACH N NETWORK COMMUNICATIONS BELDEN 5220UL (2)#16 AWG BELDEN 6220UL n
<br /> PROJECT.THESE NOTES ARE TO BE FOLLOWED WHERE APPLICABLE TO INDIVIDUAL PROJECTS AND 2 COND.16 AWG [3.850][24pF/FT] [3.850][37pF/F7]
<br /> SHOULD NOT BE TAKEN AS SCOPE OR DIRECTION WHERE THEY CONFLICT WITH INFORMATION FOUND Z
<br /> ELSEWHERE IN THIS DRAWING SET. P 24VDC AUX.POWER BELDEN 5120UL (2)#14 AWG BELDEN 612OUL O
<br /> 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT] A Pacific Ave' Pacific Ave
<br /> 1. ALL WIRE AND CONDUIT SHALL BE INSTALLED IN ACCORDANCE WITH PLANS AND Q VESDA NET BELDEN 9841 N/A BELDEN 89841 <
<br /> SPECIFICATIONS AND SHALL MEET ALL APPLICABLE CODES. 2 COND.22 AWG [240][12.SpF/FT] [240][12pF/FT] A
<br /> 2. ALL WIRE AND CABLE SHALL BE RATED FOR FIRE ALARM USE PER THE LATEST REVISIONS OF R REMOTE LED CIRCUIT BELDEN 5220UL (2)#16 AWG BELDEN 6220UL d� PORT G A R D N E R
<br /> THE NATIONAL ELECTRICAL CODE(NEC)SECTION 760.THIS IS A POWER LIMITED FIRE ALARM 2 COND.16 AWG [3.850][24pF/FT] [3.85D][37pF/FT]
<br /> SYSTEM.ALL CABLE MUST BE MARKED FPL,FPLP,FPLR OR Cl.FURTHER NEC,REQUIRES ALL °Ynysr yJi1
<br /> WIRE BE RATED FOR THE ENVIRONMENT FOR WHICH IT IS INSTALLED.ANY REFERENCES TO S ADDRESSABLE DATA SLC LOOP BELDEN 5220UL (2)#16 AWG BELDEN 6220UL
<br /> WIRE DESIGNATIONS ASSUME ELECTRICAL CONTRACTOR WILL SUBSTITUTE APPROPRIATE 2 COND.16 AWG [3.85Q][24pF/FT] [3.85Q][37pF/FT] 32nd St
<br /> WIRE TO MEET CODE. T1 ANALOG TWO-WAY COMM.CABLE N/A RATH RP66010001 vi-en Ave
<br /> 2 COND.18 AWG N/A [2-HOUR CIC] Providence
<br /> 3. ALL CONDUCTORS SHALL TEST FREE OF GROUNDS AND SHORTS BEFORE MAKING ANY Medical Center
<br /> 2er
<br /> CONNECTION TO THE FIRE ALARM CONTROL PANEL. T2 ANALOG TWO-WAY COMM.CABLE RATH 66120 N/A -Pacific Campus '^
<br /> 4. TO RETAIN WARRANTY,THE FIRE ALARM EQUIPMENT MUST BE POWERED UP UNDER THE 2 COND.18 AWG [2-HOUR] WA '� &PaV lion for N
<br /> SUPERVISION OF A QUALIFIED MANUFACTURERS TECHNICIAN. TP ANALOG TWO-WAY POWER CABLE N/A RATH R66010001 Women&Chifdrerl DESIGNER OF RECORD
<br /> 2 COND.18 AWG N/A [2-HOUR CIC] `� 33 rQ St Z
<br /> 111"E TRANCE
<br /> 5. THE INSTALLING ELECTRICAL CONTRACTOR SHALL COORDINATE ALL FIELD CHANGES WITH THE a,
<br /> FIRE ALARM CONTRACTOR.THIS INCLUDES CHANGES IN DEVICES,WIRE,CONDUIT RUNS AND U SUPPRESSION RELEASING CIRCUIT BELDEN 5120UL (2)#14 AWG BELDEN 612OUL > NICET iV
<br /> 2 COND.I4 AWG 2.430 23 F/F 2.430 37 F/ `C FIRE ALARM sysTEMS
<br /> OPERATION OF THE SYSTEM.FIRE ALARM CONTRACTOR SHALL NOT BEHELD RESPONSIBLE [ ][ F 17 [ ][ p Niles Ave w
<br /> FOR UNDOCUMENTED CHANGES OR THE RESULTS OF THOSE CHANGES. W SINGLE MODE FIBER NETWORK BUDGET SMXL02/SMXHI2:15/25 dBm E
<br /> 6. FIRE ALARM NOTIFICATION DEVICES SHALL BE AUDIBLE THROUGHOUT THE SPACE AND SHALL 8.3p SM CONNECTOR:DUPLEX SC EXPIRE
<br /> Y FOR VERiPlcanoN,PI-SE VISIT:
<br /> HAVE A SOUND PRESSURE LEVEL NOT LESS THAN 15db ABOVE THE AVERAGE AMBIENT SOUND X MULTIMODE FIBER NETWORK BUDGET MMXVR:10 dBm 34th St
<br /> LEVEL OR 5db ABOVE THE MAXIMUM SOUND LEVEL,MEASURED AT 5'0"ABOVE THE FINISHED 50/125p,62.5/125p OR 100/140p MM CONNECTOR:ST
<br /> FLOOR. Y TWO-WAY COMMUNICATIONS BELDEN1583A N/A BELDEN1515A VICINITY MAP cn �
<br /> 7. MAIN BUILDING FIRE ALARM&SUPPRESSION SYSTEMS SHALL BE CLASS"B"WIRING. CAT5E-(4)PAIR 22 AWG
<br /> PRE-ACTION&DELUGE ALARM SYSTEMS SHALL BE CLASS"A"WIRING.CLASS"A"APPLICATIONS Z FIRE/SMOKE DAMPER INTERFACE BELDEN 5120UL (2)#14 AWG BELDEN 6120UL conve rg j nt SHALL MAINTAIN A MINIMUM SEPARATION OF 48 INCHES HORIZONTALLY&12 INCHES 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT]
<br /> VERTICALLY BETWEEN OUTGOING AND RETURN CIRCUITS.
<br /> NOTE:ALL LISTED RESISTANCE AND CAPACITANCE ARE CONDUCTOR TO CONDUCTOR.ALL
<br /> 8. ALL PULL STATIONS AND NOTIFICATION DEVICES SHALL BE MOUNTED AT HEIGHTSSPECIFIED RESISTANCE VALUES ARE PER 1000 FEET. ABBREVIATIONS
<br /> PER NFPA 72 AND ADA REQUIREMENTS.
<br /> 9. ALL DETECTOR SPACING SHALL BE PER NFPA 72&LOCAL CODES. AC-ABOVE CEILING FSD-FIRE SMOKE DAMPER(THIRD PARTY)
<br /> AFF-ABOVE FINISHED FLOOR HVAC-HEATING,VENTILATION,AND AIR
<br /> 10. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ROUGH-IN LOCATIONS WITH OTHER Sheet List Table ADA-AMERICAN DISABILITIES ACT CONDITIONING(THIRD PARTY)
<br /> Sheet Number Sheet Title AHJ-AUTHORITY HAVING JURISDICTION LA-LOW AIR(THIRD PARTY)
<br /> TRADES. FA-0-1 COVER SHEET AHU-AIR HANDLING UNIT(THIRD PARTY) NIA-NOTAPPLICABLE
<br /> 11. ALL FIRE ALARM DEVICES SHALL BE SECURELY FASTENED TO WALLS OR CEILINGS. FA-0-2 NOTES ASD-ASPIRATION SMOKE DETECTION NAC-NOTIFICATION APPLIANCE CIRCUIT
<br /> FA-1-LL LOWER LEVEL CD-CANDELA(EX.15CD) NFPA-NATIONAL FIRE PROTECTION ASSOCIATION
<br /> FA-1-R ROOF CIS-COMMON INTELLIGIBILITY SCALE NIC-NOT IN CONTRACT
<br /> 12. SMOKE DETECTORS SHALL NOT BE LOCATED CLOSER THAN 36"TO ANY AIR REGISTER OR FA-4-1 DEVICE DETAILS DH-DOOR HOLDER(THIRD PARTY UNO) NTS-NOT TO SCALE
<br /> DIFFUSER. EF-EXHAUST FAN(THIRD PARTY) PS-POWER SUPPLY
<br /> 13. HEAT DETECTORS SHALL NOT BE LOCATED CLOSER THAN 36"TO ANY AIR REGISTER OR ELEV-ELEVATOR(THIRD PARTY) RTU-ROOF TOP UNIT(THIRD PARTY)
<br /> EOL-END OF LINE SLC-SIGNALING LINE CIRCUIT
<br /> DIFFUSER. EPF-ELEVATOR PRESSURIZATION FAN(THIRD PARTY) SPF-STAIR PRESSURIZATION FAN(THIRD PARTY)
<br /> 14. PER NFPA 72,CHAPTER 17;SMOKE DETECTORS INSTALLED PRIOR TO FINAL CLEAN MUST BE FA-FIRE ALARM STI-SPEECH TRANSMISSION INDEX
<br /> CLEANED AND VERIFIED TO BE OPERATING IN ACCORDANCE WITH THE LISTED SENSITIVITY,OR FAA-FIRE ALARM ANNUNCIATOR NP-TYPICAL
<br /> THEY SHALL BE REPLACED PRIOR TO THE FINAL COMMISSIONING OF THE SYSTEM. FACP-FIRE ALARM CONTROL PANEL UNO-UNLESS NOTED OTHERWISE
<br /> CONVERGINT BEARS NO RESPONSIBILITY FOR LABOR OR MATERIAL ASSOCIATED WITH FACU-FIRE ALARM CONTROL UNIT VAV-VARIABLE AIR VOLUME(THIRD PARTY)
<br /> CLEANING,SENSITIVITY TESTING OR REPLACEMENT OF SMOKE DETECTORS INSTALLED PRIOR FBO--FIRE ALARM TERMINAL CABINET VFD-VARIABLE FREQUENCY DRIVE(THIRD PARK)
<br /> FBO-FURNISHED BY OTHERS W/-WITH
<br /> TO FINAL CLEANING. FCU-FAN COIL UNIT(THIRD PARTY) W-WATT(EX.1/2W)
<br /> 15. HEAT DETECTORS SHALL NOT BE LOCATED CLOSER THAN 36"TO ANY HEAT GENERATING FFT-FIREFIGHTER'S TELEPHONE WP-WEATHERPROOF
<br /> DEVICE(FUSES,BOILERS,WATER HEATERS,ETC.)IN MECHANICAL ROOMS. FM-FACTORY MUTUAL XP-EXPLOSION PROOF
<br /> RIEV JON-DESCRIPTION DATE
<br /> 16. HEAT DETECTORS SHALL NOT BE LOCATED CLOSER THAN 18"TO ANY PART OF ANY LIGHT FLOOR PLAN KEY OR
<br /> FIXTURE. I J00150M ISSUED FOR PERMIT
<br /> DEVICE ADDRESS KEY DETAIL BUBBLE KEY
<br /> 17. HEAT DETECTORS SHALL BE MOUNTED WITHIN 24"OF A SPRINKLER HEAD WHEN USED FOR
<br /> ELEVATOR SHUNT TRIP IN ELEVATOR MACHINE ROOMS&SHAFTS. L DETAIL NUMBER
<br /> FIRE ALARM PANE #
<br /> 18. INITIATING AND SIGNALING CIRCUITS MAY BE RUN IN SAME CONDUIT. DEVICE ADDRESS 4DETAIL
<br /> s ////19. ALL CONDUCTORS SHALL BE LABELED BY ZONE OR SLC LOOP NUMBER. z-x-xxzz-x LOCATION I- SAME SHEET)
<br /> p 20. THESE DRAWINGS ARE INTENDED TO SHOW PROJECT SPECIFIC PANELS,DEVICES AND WIRING DATACARD1 _ISOLATED
<br /> REDBRANCH
<br /> U DEPICTED DIAGRAMMATICALLY.WIRING SHOWN IS NOT INTENDED TO DEPICT RACEWAY OR LOGICAL ADDRESS (A ) MaxNLU H.
<br /> 0 PATHWAY LOCATIONS.DEVICE AND PANEL LOCATIONS SHALL BE COORDINATED BY INSTALLING PROJECT DESIGNER: ANES.
<br /> JCONTRACTOR AS PART OF THE CONSTRUCTION PROCESS. KEVIN F.
<br /> Q NOTIFICATION DEVICE CIRCUIT KEY DRAWING SHEET INDEX KEY
<br /> U 21. ALL REFERENCES TO INTERNATIONAL BUILDING CODE(IBC)ARE FROM THE 2015 EDITION.ALL AESHOWN usot.wo mEeza ov arzozs
<br /> U REFERENCES TO NFPA 72 ARE FROM THE 2013 EDITION AS CURRENTLY ADOPTED BY IBC.THE SPEAKER CIRCUIT NUMBER FIRE ALARM �LEVEUFLOOR/ARFA
<br /> < ADOPTED VERSION FOR THE PROJECT JURISDICTION MAY BE DIFFERENT AND UPON REQUEST CIRCUIT
<br /> In CONVERGINT WILL PROVIDE UPDATED REFERENCE SECTIONS TO MATCH ADOPTED VERSION. CIRCUIT NUMBER Sp.X FA-X.XX PROVIDENCE PACIFIC CAMPUS
<br /> W
<br /> � THE SCOPE SECTION OF OUR DRAWINGS WILL PROVIDE THE VERSION REFERENCED FOR THE POWER SUPPLY ELEVATOR T.I.
<br /> SUFFIX Eel! �
<br /> FIRE ALARM DESIGN. � 0=COVER SHEET 916 PACIFIC AVE
<br /> 7 XX-MX.X 1=FLOOR PLANS
<br /> x 22. AS THE FIRE ALARM VENDOR UTILIZED FOR THIS BUILDING,NFPA 72 REQUIRES WE KEEP `\ 2-RISER DIAGRAMS EVERETT,WA,98201
<br /> ACCURATE RECORD DRAWING INFORMATION.AS SUCH,IT IS NECESSARY THAT WE DEPICT `LOGICAL DEVICE NUMBER 3=FIRE PANEL DETAILS
<br /> EXISTING DEVICES AND WIRING IN ADDITION TO THOSE COMPONENTS ASSOCIATED WITH YOUR 4-DEVICE DETAILS
<br /> 5=CALCULATIONS
<br /> � SCOPE WHERE APPLICABLE.UNLESS OTHERWISE NOTED,IT IS ASSUMED EXISTING 6=2-WAY COMMUNICATION
<br /> 0 COMPONENTS WILL REMAIN UN-DISTURBED BY YOUR OFAID IN IDENTIFYING
<br /> Z NEW S.EXSTNG,WE WILL TURN EXISTING CO PONEN SPTOALIGHTERSHADE.REMOVAL F COVER SHEET
<br /> U THE EXISTING DEVICES AND WIRING MAY OTHERWISE IMPACT THE CONTEXT OF THE
<br /> COMPLETE,CODE REQUIRED FIRE ALARM SYSTEM,THEREFORE THEY CANNOT BE OMITTED
<br /> Z FROM OUR DRAWNG PACKAGE. FIRE ALARM SYSTEM
<br /> IRANNII:
<br /> o FA-0-1
<br /> tL
<br />
|