(E) POTTER PAD300-PD <br /> The Symbol of Protection Photoelectric Smoke Detector <br /> Air Velocity Ratings <br /> The PAD300-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. <br /> The system has a maximum of 30 LEDs that can be turned on simultaneously.If the system already has 30 LEDs on,the PAD300-PD will operate even <br /> though the LED may not illuminate. <br /> Operation <br /> The PAD300-PD is an analog addressable detector that uses one address on the Signaling Line Circuit(SLC)of a compatible fire alarm control panel. <br /> The unit communicates with the control panel as it is polled.The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is <br /> in an active status.The polling LED can be turned off if desired for less conspicuous operation. <br /> The PAD300-PD with the PAD300-4DB or PAD300-6DB has a low profile of less than two(2)inches to blend into the surrounding environment.The <br /> detector includes an insect screen to prevent foreign objects from reaching the chamber and can be cleaned to restore operation of a dirty detector. <br /> Detector Sensitivity <br /> The PAD300-PD and the compatible control panel work in tandem to keep the sensitivity consistent.As the detector is installed over time,the detector <br /> compensates for the dirt in the unit until it is out of range.At that time,the panel will indicate a dirty detector.The detector will then have to be cleaned <br /> or replaced. <br /> The PAD300-PD can be programmed to provide a maintenance alert prior to reaching the dirty detector level which will allow for intervention prior to <br /> the detector going into trouble. This allows for detector replacement or cleaning prior to a nuisance trouble occurs. <br /> NOTE.As required by NFPA, do not install the detectors until all construction is complete and the work area has been thoroughly cleaned. If the <br /> detectors have been installed in a construction environment,they should be cleaned or replaced before the system is placed into service. <br /> Spacing <br /> The PAD300-PD is UL listed with a recommended maximum spacing of 30 feet.Refer to NFPA 72 for specific information regarding detector spacing, <br /> placement and special applications. <br /> Compatible Bases <br /> All bases will mount on a single gang,3-1/2"octagon,3-1/2"square,double gang,4"octagon,4"square,50mm c/c,60mm c/c and 70mm c/c boxes. <br /> Device Description Stock No. <br /> PAD300-4DB 4"Detector Base 3992781 <br /> PAD300-61)B 6"Detector Base 3992782 <br /> PAD300-IB 6"base with an isolator module included 3992783 <br /> PAD300-RB 6"base with one Form-C relay contact. 2A @ 30VDC,0.5A @ 125VAC 13992784 <br /> PAD300-SB 6"base with sounder module included.Sound pattern is provided from external source 1 3992785 <br /> PAD300-LFSB 6"base with 520Hz sounder module included.Sound pattern is provided from external source 3992786 <br /> Ordering Information <br /> Model Description Stock No. <br /> PAD300-PD Photoelectric Smoke Detector 3992775 <br /> Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com <br /> 8830216-REV B 2/23 PAGE 2 OF 2 <br />