& D CONSTRUCTION COMPANY LLC <br /> COMMERCIAL& RESIDENTIAL-GENERAL CONTRACTORS, BUILDING-EXCAVATION-DEMO <br /> LANDSCAPING-CLEARING-CONSTRUCTION CONTRACTOR REGISTRATION #TDCONDC81805 <br /> To the City of Everett Mechanical Division April 16, 2023 <br /> Mechanical Application and or permit t� <br /> M2303-045 D 1-- `J <br /> � <br /> C/O Drew Martin RIL 19 <br /> Answer to corrections round 1 CITY O F F'/E r\E T T <br /> Per �zrv16es <br /> Answers <br /> 1. The drawing of the wall is for reference and is in all our drawings to show what is <br /> There and what the hood will be sitting against. <br /> 2. 2A.The make up air unit weighs 240LB The curb it sits on weighs 25LBS <br /> 2B. There is nothing over 400LBS to be sitting on roof, the Hood weighs 300LB <br /> 3. The hood does comply, it is a UL710 Hood, and this requirement is a field <br /> Upon install. As per code it is 18" per side or a 3" air gap if sitting next to a wall. <br /> 4. The Exhaust ductwork will be wrapped as shown on the drawings sheet H-12 <br /> Listed Fire wrap zero clearance from top of hood to inside of curb. To be installed <br /> After light test. <br /> 5. The horizontal load is transferred to back of wall as we hang all 4 corners and pin <br /> the back of hood that demonstrates left to right and front to back stabilization. <br /> 6. The Electrical is not in our scope however as in all installations we put hinges on all <br /> Exhaust fans and per electrical code yes a whip is used. <br /> Thank you Drew I hope this helps clarify all the codes and information that you <br /> need. <br /> Thank you,Terry <br /> PO BOX 3602 FEDERAL WAY WASHINGTON 98063 206-856-3163 <br />